Section 109.1009 - System operational requirements
Current through Register Vol. 55, No. 13, March 29, 2025
(a) General facilities operation. Facilities of bottled water and vended water systems, retail water facilities and bulk water hauling systems approved by written permit from the Department shall be operated in a manner consistent with the terms and conditions of the permit to achieve the level of treatment for which the facilities were designed.
(b) Special bottled water system requirements. Bottled water systems shall be operated in accordance with the standards of the Food and Drug Administration in 21 CFR Part 129 (relating to processing and bottling of bottled drinking water). Proof of this determination shall be submitted to the Department annually under § 109.1008(a)(1)(ii) (relating to system management responsibilities).
(c) Disinfectant residual requirements. A disinfectant residual acceptable to the Department shall be maintained at the entry point of the bottled water or vended water system, retail water facility or bulk water hauling system sufficient to assure compliance with the microbiological MCL specified in § 109.1002 (relating to MCLs, MRDLs or treatment techniques). The Department will determine the acceptable residual of the disinfectant considering factors such as type and form of disinfectant, temperature and pH of the water, and other characteristics of the water system.
(d) Disinfection of facilities following construction, modification or repair. After repairing, constructing or modifying a bottled water, vended water, retail water or bulk water hauling facility and before the facility is placed in service, it shall be properly cleaned and disinfected. Cleaning shall be in accordance with 21 CFR 129.80(c) and (d) (relating to processes and controls) and disinfection shall be with 50 ppm chlorine for 1 minute at 75°F or the equivalent.
(e) Dedicated equipment. Bottled water, vended water, retail water and bulk water may not be transported, stored or processed through equipment or lines used for any nonfood product. Bottled water, vended water, retail water and bulk water transported, stored or processed through equipment used for a food product other than water shall comply with the following cleaning and disinfection procedures:
(f) Special operational requirements for bottled water systems and retail water facilities.
(g) Special operational requirements for water vending machine systems.
(h) Special operational requirements for bulk water hauling systems.
This section cited in 25 Pa. Code § 109.1008 (relating to system management responsibilities).