Section 109.710 - Disinfectant residual in the distribution system
Current through Register Vol. 55, No. 13, March 29, 2025
(a) Until April 28, 2019, a disinfectant residual acceptable to the Department shall be maintained throughout the distribution system of the community water system sufficient to assure compliance with the microbiological MCLs and the treatment technique requirements specified in § 109.202 (relating to State MCLs, MRDLs and treatment technique requirements). The Department will determine the acceptable residual of the disinfectant considering factors such as type and form of disinfectant, temperature and pH of the water, and other characteristics of the water system.
(b) Until April 28, 2019, a public water system that uses surface water or GUDI sources or obtains finished water from another permitted public water system using surface water or GUDI sources shall comply with the following requirements:
(c) Beginning April 29, 2019, a community water system using a chemical disinfectant or that delivers water that has been treated with a chemical disinfectant shall maintain a minimum residual disinfectant concentration throughout the distribution system sufficient to assure compliance with the microbiological MCLs and the treatment technique requirements specified in § 109.202. The minimum residual disinfectant concentration is 0.2 mg/L or another level approved by the Department for systems using an alternate oxidizing disinfection treatment. The residual disinfectant concentration shall be measured as follows:
(d) Beginning April 29, 2019, a nontransient noncommunity water system that has installed chemical disinfection or a transient noncommunity water system that has installed chemical disinfection in accordance with § 109.202(c)(1) or § 109.1302(b) (relating to treatment technique requirements) shall maintain a minimum residual disinfectant concentration throughout the distribution system sufficient to assure compliance with the microbiological MCLs and the treatment technique requirements specified in § 109.202. The minimum residual disinfectant concentration is 0.2 mg/L or another level approved by the Department for systems using an alternate oxidizing disinfection treatment. The residual disinfectant concentration shall be measured as follows:
(e) Beginning April 29, 2019, compliance with the disinfectant residual treatment technique will be based on the number of samples collected each month as specified in the system distribution sample siting plan submitted to the Department under § 109.701(a)(8) (relating to reporting and recordkeeping). Compliance will be determined as follows:
(f) Public water systems may increase residual chlorine or chloramine, but not chlorine dioxide, disinfectant levels in the distribution system to a level that exceeds the MRDL for that disinfectant and for a time necessary to protect public health or to address specific microbiological contamination problems caused by circumstances such as, but not limited to, distribution line breaks, storm runoff events, source water contamination events or cross-connection events.