Section 918-400-0750 - Placing a Previously Disabled Elevator Back into Service
Current through Register Vol. 63, No. 9, September 1, 2024
When an installation previously placed out of service is intended to be returned to operating service:
(1) A written request shall be made to the division for an operating license.
(2) With permission from the division an elevator contractor may operate the elevator and make necessary repairs and adjustments to make the elevator operational.
(3) All testing required to place the type of elevator involved back in service shall be witnessed by a division elevator inspector.
(4) The elevator shall not be placed back into service before an inspection by the division and issuance of an operating permit under OAR 918-400-0465.