Oregon Administrative Rules
Chapter 918 - DEPARTMENT OF CONSUMER AND BUSINESS SERVICES, BUILDING CODES DIVISION
Division 305 - ELECTRICAL CODES AND STANDARDS
Section 918-305-0460 - Grounding

Universal Citation: OR Admin Rules 918-305-0460

Current through Register Vol. 63, No. 9, September 1, 2024

(1) System substations shall be installed with a grounding grid to limit touch and step potentials to safe levels as recommended by IEEE 80, "Guide for Safety in Substation Grounding." AC and low-voltage equipment shall be bonded or grounded to this grid, except as otherwise provided for the utility neutral or ground. Calculations and ground resistance test reports for every substation shall be furnished to the division prior to final inspection and maintained by the operating entity.

(2) The service neutral conductor is not required to be bonded to the substation grounding grid, provided that:

(a) A warning sign is posted on the service equipment to provide notice of potential hazards to technical persons who may have access to the service equipment. The notice shall clearly indicate that the neutral is isolated and not grounded;

(b) An isolation barrier is installed over the neutral termination within the service equipment; and

(c) The ground grid is installed in a manner that will demonstrate a ground resistance of 5 ohms or less when tested in accordance with IEEE 81, "Guide for Testing Grounding Systems."

(3) Free-standing signal system cabinets, bungalows or buildings shall be separately grounded by means of a driven ground electrode or electrodes to obtain ground resistance of 25 ohms or less when tested in accordance with IEEE 81.

(4) 60 Hz, 120-volt AC systems for accessory power or lighting located within station platforms or substations shall meet the requirements of the Electrical Specialty Code.

(5) All service equipment receiving service voltage from the utility shall be posted with warning signs to provide notice of potential hazards to technical persons who may have access to the panel. The notice shall clearly indicate that the neutral is isolated and not grounded.

(6) All fencing located within 10 feet of a metallic railway substation, building, ground grid, bungalow or other structure shall be constructed of nonmetallic material.

Publications: Publications referenced are available from the agency.

Stat. Auth.: ORS 479.950

Stats. Implemented: ORS 479.950

Disclaimer: These regulations may not be the most recent version. Oregon may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.