Oregon Administrative Rules
Chapter 918 - DEPARTMENT OF CONSUMER AND BUSINESS SERVICES, BUILDING CODES DIVISION
Division 261 - ELECTRICAL EXEMPTIONS
Section 918-261-0025 - Exemption for Limited Energy Underground Signaling Circuits
Current through Register Vol. 63, No. 9, September 1, 2024
(1) A license and permit is not required to install limited energy underground signaling circuits or loops defined in this rule. Unlicensed individuals are allowed to install underground signaling circuits or loops, and cover these circuits or loops without a permit or inspection.
(2) For purposes of this rule "underground signaling circuits or loops" means Class 2 circuits defined in Article 725 of the Electrical Specialty Code intended for use as traffic signal devices, gate controllers, weigh stations, counters or other similar devices.
(3) A license and permit is required to splice, connect, or extend the signaling circuits, loops, or loop conductor, or to connect to any of the following:
Stat. Auth.: ORS 479.740
Stats. Implemented: ORS 479.540