Section 918-225-0380 - Refrigeration Chillers

Universal Citation: OR Admin Rules 918-225-0380

Current through Register Vol. 63, No. 12, December 1, 2024

(1) Waterside vessels of refrigeration chillers are exempt under ORS 480.510 to 480.665 if:

(a) The design pressure does not exceed 300 pounds per square inch gauge, the temperature does not exceed 210°F., and the system includes an ASME-approved relieving device set at a maximum working pressure of 300 pounds per square inch gauge at 210°F;

(b) The refrigerant side is built in accordance with the minimum safety standards and equipped with an ASME-approved relieving device set at or below the maximum working pressure and temperature as specified on the nameplate for the vessel; and

(c) All installations of refrigeration chillers comply with ORS 480.630.

(2) Systems connected to an outside heat energy source shall not be exempt from ORS 480.510 to 480.665.

(3) If any of the limitations in section (1) of this rule are exceeded, the chiller must comply with the minimum safety standards.

(4) This exemption does not apply to systems using ammonia as a refrigerant.

Publications: The publication(s) referred to or incorporated by reference in this rule are available from the agency.

Stat. Auth.: ORS 480.560

Stats. Implemented: ORS 480.560

Disclaimer: These regulations may not be the most recent version. Oregon may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.