Section 918-225-0310 - Exemptions for Refrigerant Piping Systems

Universal Citation: OR Admin Rules 918-225-0310

Current through Register Vol. 63, No. 3, March 1, 2024

(1) The requirements of OAR 918-225-0430(2)(e) shall be enforced under this rule for all refrigerant piping systems consisting of welded, brazed or mechanically assembled piping and piping fittings exceeding 2 inches NPS, and containing any refrigerant chemical rated as other than A-1 or B-1 by the American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE 34) as adopted by the Oregon Mechanical Specialty Code.

(2) One and two-family dwelling units and air conditioning refrigeration systems used solely for human comfort are exempt from this rule.

(3) All refrigeration piping system requirements other than those regulated by this rule are subject to the Oregon Mechanical Specialty Code.

Publications: Publications referenced are available from the agency.

Statutory/Other Authority: ORS 480.550

Statutes/Other Implemented: ORS 480.550

Disclaimer: These regulations may not be the most recent version. Oregon may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.