Oregon Administrative Rules
Chapter 837 - DEPARTMENT OF THE STATE FIRE MARSHAL
Division 45 - SMOKE ALARMS AND SMOKE DETECTORS
Section 837-045-0060 - Power Source

Universal Citation: OR Admin Rules 837-045-0060

Current through Register Vol. 63, No. 12, December 1, 2024

(1) The power supply of a smoke alarm shall be a commercial power source, an integral battery or batteries or a combination of both. The power supply for a smoke detector shall be a commercial power source.

(2) When a smoke alarm or smoke detector is served from a commercial power source, the wiring shall be permanent and shall not have a disconnecting switch other than that required for over current protection.

(3) When a line cord and plug is used, it shall be plugged directly into a fixed outlet box and the plug shall be secured by a device that cannot be removed without the use of a tool.

(4) The owner of a dwelling unit, lodging house or hotel shall obtain a permit from the local building official for the installation of a 110-volt smoke alarm or a low-voltage smoke detector connected to a fire alarm control panel.

Stat. Auth.: ORS 479.255 & ORS 479.295

Stats. Implemented: ORS 479.250 - ORS 479.300

Disclaimer: These regulations may not be the most recent version. Oregon may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.