(1) The surface curbing required in OAR 690-210-0400 shall be of concrete, concrete tile, or steel. If concrete is used, the concrete wall thickness shall not be less than six inches. In the case of buried slab type wells, well casing meeting the minimum specifications given in 690-210-0190 through 690-210-0220 shall be used. (See Figure 210-13.)

(2) If precast concrete tile or steel casing is used for the surface curbing, the well diameter to the bottom of the surface curbing shall be eight inches greater than the outside diameter of the tile or steel, and the annular space shall be completely filled with grout in accordance with OAR 690-210-0310 through 690-210-0340. (See Figure 210-13).

To view attachments referenced in rule text, click here to view rule.

Statutory/Other Authority: ORS 536.090, ORS 537.505-537.795, ORS 536.027, ORS 536.900 & ORS 537.992

Statutes/Other Implemented: ORS 536.090, ORS 537.505-537.795, ORS 536.900 & ORS 537.992

Disclaimer: These regulations may not be the most recent version. Oregon may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.