Section 291-061-0250 - Lighting

Universal Citation: OR Admin Rules 291-061-0250

Current through Register Vol. 63, No. 9, September 1, 2024

(1) All rooms in which food or drink is prepared or in which utensils are washed shall be uniformly lighted with a minimum of 30 foot candles on all work surfaces and ten foot candles at floor level. Store rooms shall be uniformly lighted with a minimum of four foot candles at floor level.

(2) Lighting equipment shall be kept clean.

(3) Dining rooms shall be provided with lighting fixtures capable of providing a minimum of ten foot candles of light at floor level and shall be used during cleaning operations.

Stat. Auth.: ORS 179.040, ORS 423.020, ORS 423.030 & ORS 423.075

Stats. Implemented: ORS 179.040, ORS 423.020, ORS 423.030 & ORS 423.075

Disclaimer: These regulations may not be the most recent version. Oregon may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.