Oklahoma Administrative Code
Title 748 - Oklahoma Uniform Building Code Commission
Chapter 20 - Adopted Codes
Subchapter 6 - IRC[®] 2018
Section 748:20-6-13 - IRC[®] 2018 Chapter 8 Roof-Ceiling Construction
Current through Vol. 42, No. 1, September 16, 2024
Chapter 8 of the IRC® 2018 is adopted with the following modifications:
(1) Section R801.3 Roof drainage. This section has been stricken from the code.
(2) Section 802.3 Ridge. This section has been modified to clarify a ridge beam shall be designed in accordance with acceptable engineer practices when the roof load exceeds specific criteria to carry one-half of the tributary load. This section has been modified to read: R802.3 Ridge. A ridge board used to connect opposing rafters shall be not less than 1 inch (25 mm) nominal thickness and not less in depth than the cut end of the rafter. Where ceiling joists or rafter ties do not provide continuous ties across the structure, a ridge beam shall be designed, in accordance with acceptable engineer practices, and supported on each end of the wall or girder, when roof loads exceed 10 per square foot pound dead loads and 20 per square foot pound live loads. In the case where rafters are used to support roof and finished ceiling (also known as a cathedral ceiling) with no connection of opposing rafters, ridge beam shall be designed, in accordance with acceptable engineer practices to carry one half of tributary load of the roof.
(3) Section R802.4.1 Rafter size. This section has been modified to provide guidance for builders framing rafters above the top sill of the wall system and provide an exception to require collar ties to be sized not less than the required size of the rafters they are connected to. This section has been modified to read: 802.4.1 Rafter size. Rafters shall be sized based on the rafter spans in Tables R802.4.1(1) through R802.4.1(8). Rafter spans shall be measured along the horizontal projection of the rafter. For other grades and species and for other loading conditions, refer to the AWC STJR. The tabulated rafter spans in Tables R802.4.1(1) through R802.4.1(8) assume ceiling joists are located at the bottom of the attic space or some other method of resisting the outward push of the rafter on the bearing walls, such as rafter ties is provided at that location. Where ceiling joists or rafter ties are located higher in the attic space, the rafter span in these tables shall be multiplied by the following rafter reduction factors: Where ceiling joists or rafter ties are located at one third the span of the rafter the adjustment factor is 0.67, at one quarter of the span of the rafter the rafter adjustment factor is 0.76, at one fifth the span of the rafter the adjustment factor is 0.83, at one sixth of the span of the rafter, the adjustment factor is 0.90, and at two fifteenths of the rafter or less, there is no need for adjusting the rafter capacity. Exception: Collar Ties. Installation of the collar ties to reduce the span of the rafters is permitted as shown in Figure R802.4.5. Collar ties shall be installed at every rafter and sized not less than the required size of the rafters they are connected.
(4) Section R802.4.2 Framing details. This section has been modified to change the rafter framing details. This section has been modified to read: R802.3 Framing details.
(5) Section 802.4.3 Hips and valleys. This section has been modified to provide an exception for the use of a "Blind Valley," and provide a definition of a brace. This section has been modified to read: R802.4.3 Hips and Valleys. Hip and valley rafters shall be not less than 2 inches (51 mm) nominal in thickness and not less in depth than the cut end of the rafter. Hip and valley rafters shall be supported at the ridge by a brace to a bearing partition, or beam, or be designated to carry and distribute the specific load at that point. Exception: The use of a "Blind Valley" also known as a "Farmers Valley" or "California Valley" will be allowed. In this type of valley, the main roof is framed as usual, it may or may not be sheathed and the intersecting roof is framed on top of the main roof. The two valley plates or sleeps lie on the top of the main roof rafters or sheathing and provide a nailing base for the jack rafters and the ridge board of the intersecting roof. A definition of a brace includes:
(6) Section R802.5.1 Purlins. This section has been modified to include an exception for spacing the braces at not more than 6 feet (1829 mm) when certain conditions are met. The section has been modified to read: R802.5.1 Purlins. Installation of purlins to reduce the span of rafters is permitted as shown in Figure R802.5.1. Purlins shall be sized not less than the required size of the rafters that they support. Purlins shall be continuous and shall be supported by 2-inch by 4-inch (51 mm by 102 mm) braces installed to bearing walls at a slope not less than 45 degrees (0.79 rad) from the horizontal. The braces shall be spaced not more than 4 feet (1219 mm) on center and the unbraced length of the braces shall not exceed 8 feet (2438 mm). Exception: Braces may be spaced not more than 6 feet (1829 mm) on center if:
(7) Section R802.5.2 Ceiling joist and rafter connections. This section has been modified to reflect current framing practices. This section has been modified to read: R802.3.1 Ceiling joists and rafter connections. Where ceiling joists run parallel to rafters, they shall be connected to rafters at the top wall plate in accordance with Table R802.5.2. Where ceiling joists are not connected to the rafters at the top of the wall plate, they shall be installed in the bottom third of the rafter height in accordance with Figure R802.4.5 and Table R802.5.2 Where ceiling joists do not run parallel to the rafters, the ceiling joists shall be connected to top plates in accordance with Table R602.3(1). Each rafter shall be tied across the structure with a rafter tie spaced 4 ft (1219 mm) on center. Where ceiling joists or rafter ties are not provided, the ridge formed by these rafters shall be supported by a wall or girder designed in accordance with accepted engineer practices.
(8) Section R802.7.1.2 Ceiling joist taper cut. This section has been modified to include an exception to the section requirements for ceiling joists not carrying more than a 25-pound live load for limited attic storage. This section has been modified to read: R802.7.1.2 Ceiling joists taper cut. Taper cuts at the ends of the ceiling joists shall not exceed one-fourth the depth of the member in accordance with Figure R802.7.1.2. Exception: For ceiling joists not carrying more than 25 pounds of live load (limited attic storage) then taper cut at end of joist may be able to be increased to D/2.
(9) Section R806.5 Unvented attic and unvented enclosed rafter assemblies. This section has been modified to provide guidance on where the air permeable and impermeable insulation should be installed and provide exceptions to the section related to when air supply to the attic is not required. This section has been modified to read: R806.5 Unvented attic and unvented enclosed rafter assemblies. Unvented attics and unvented enclosed roof framing assemblies created by ceilings that are applied directly to the underside of the roof framing members and structural roof sheathing applied directly to the top of the roof framing members/rafters, shall be permitted where all of the following conditions are met: