Section 748:20-2-10 - IBC[®] 2018 Chapter 5 General Building Heights and Areas

Universal Citation: OK Admin Code 748:20-2-10

Current through Vol. 41, No. 13, March 15, 2024

Chapter 5 of the Oklahoma adopted IBC 2018 is adopted with the following modification: Table 509 Incidental uses has been modified to remove the row related to stationary storage battery systems. This table has been modified read as follows: Table 509 Incidental uses. The table contains 18 rows with 2 columns in each row as described below:

(1) Row 1 is the header row and contains the headers for the two columns as listed below:

(A) Row 1, column 1 header is entitled "Room or Area."

(B) Row 1, column 2 header is entitled "Separation and/or Protection."

(2) Row 2 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 2, column 1 contains the wording "Furnace room where any piece of equipment is over 400,000 Btu per hour input."

(B) Row 2, column 1 contains the wording "1 hour or provide automatic sprinkler system."

(3) Row 3 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 3, column 1 contains the wording "Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower."

(B) Row 3, column 2 contains the wording "1 hour or provide automatic sprinkler system."

(4) Row 4 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 4, column 1 contains the wording "Refrigerant machinery room."

(B) Row 4, column 2 contains the wording "1 hour or provide automatic sprinkler system."

(5) Row 5 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 5, column 1 contains the wording "Hydrogen fuel gas rooms, not classified as Group H."

(B) Row 5, column 2 contains the wording "1 hour in Group B, F, M, S and U occupancies; 2 hours in Group A, E, I and R occupancies."

(6) Row 6 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 6, column 1 contains the wording "Incinerator rooms."

(B) Row 6, column 2 contains the wording "2 hours and provide automatic sprinkler system."

(7) Row 7 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 7, column 1 contains the wording "Paint shops, not classified as Group H, located in occupancies other than Group F."

(B) Row 7, column 2 contains the wording "2 hours; or 1 hour and provide an automatic sprinkler system."

(8) Row 8 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 8, column 1 contains the wording "In Group E occupancies, laboratories and vocational shops not classified as Group H."

(B) Row 8, column 2 contains the wording "1 hour or provide automatic sprinkler system."

(9) Row 9 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 9, column 1 contains the wording "In Group I-2 occupancies, laboratories not classified as Group H."

(B) Row 9, column 2 contains the wording "1 hour and provide automatic sprinkler system."

(10) Row 10 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 10, column 1 contains the wording "In ambulatory care facilities, laboratories not classified as Group H."

(B) Row 10, column 2 contains the wording "1 hour or provide automatic sprinkler system."

(11) Row 11 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 11, column 1 contains the wording "Laundry rooms over 100 square feet."

(B) Row 11, column 2 contains the wording "1 hour or provide automatic sprinkler system."

(12) Row 12 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 12, column 1 contains the wording "In Group I-2, laundry rooms over 100 square feet."

(B) Row 12, column 2 contains the wording "1 hour."

(13) Row 13 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 13, column 1 contains the wording "Group I-3 cells and Group I-2 patient rooms equipped with padded surfaces."

(B) Row 13, column 2 contains the wording "1 hour."

(14) Row 14 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 14, column 1 contains the wording "In Group I-2, physical plant maintenance shops."

(B) Row 14, column 2 contains the wording "1 hour."

(15) Row 15 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 15, column 1 contains the wording "In ambulatory care facilities or Group I-2 occupancies, waste and linen collection rooms with containers that have an aggregate volume of 10 cubic feet or greater."

(B) Row 15, column 2 contains the wording "1 hour."

(16) Row 16 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 16, column 1 contains the wording "In other than ambulatory care facilities and Group I-2 occupancies, waste and linen collection rooms over 100 square feet."

(B) Row 16, column 2 contains the wording "1 hour or provide automatic sprinkler system."

(17) Row 17 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 17, column 1 contains the wording "In ambulatory care facilities or Group I-2 occupancies, storage rooms greater than 100 square feet."

(B) Row 17, column 2 contains the wording "1 hour."

(18) Row 18 contains the following information in each of the two columns listed for the header row number 1:

(A) Row 18, column 1 contains the wording "Electrical installations and transformers."

(B) Row 18, column 2 contains the wording "See Sections 110.26 through 110.34 and Sections 450.8 through 450.48 of NFPA 70® for protection and separation requirements."

(19) At the bottom of the table the following appears: "For SI: 1 square foot equals 0.0929 square meters, 1 pound per square inch (psi) equals 6.9 kPa, 1 British thermal unit (Btu) per hour equals 0.293 watts, 1 horsepower equals 746 watts, 1 gallon equals 3.785 L, and 1 cubic foot equals 0.0283 meters cubed."

Disclaimer: These regulations may not be the most recent version. Oklahoma may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.