Oklahoma Administrative Code
Title 748 - Oklahoma Uniform Building Code Commission
Chapter 20 - Adopted Codes
Subchapter 16 - IPC[®] 2018
Section 748:20-16-14 - IPC[®] 2018 Chapter 9 Vents
Current through Vol. 42, No. 1, September 16, 2024
Chapter 9 of the Oklahoma adopted IPC® 2018 is adopted with the following modifications:
(1) Section 903.1 Roof extension. This section has been modified to specify the number of inches where the open vent pipes that extend through the roof shall be terminated. This section has been modified to read: 903.1 Roof extension. Open vent pipes that extend through a roof shall be terminated not less than 10 inches (254 mm) above the roof. Where a roof is to be used for assembly or as a promenade, observation deck, sunbathing deck or similar purpose, open vent pipes shall terminate not less than 7 feet (2134 mm) above the finished occupiable surface within 10 feet (3048 mm) horizontal distance.
(2) Section 919.1 General. This section has been modified to address errata published by the ICC® to correct a specified section reference from "Section 105.3" to "Section 316." This section has been modified to read: 919.1 General. Engineered vent systems shall comply with this section and the design, submittal, approval, inspection and testing requirements of Section 316.