Oklahoma Administrative Code
Title 748 - Oklahoma Uniform Building Code Commission
Chapter 20 - Adopted Codes
Subchapter 16 - IPC[®] 2018
Section 748:20-16-11 - IPC[®] 2018 Chapter 6 Water Supply and Distribution
Current through Vol. 42, No. 1, September 16, 2024
Chapter 6 of the Oklahoma adopted IPC® 2018 is adopted with the following modifications:
(1) Section 604.5 Size of fixture supply. This section has been modified to add an exception to allow domestic dishwashers and drinking fountains to terminate more than 30 inches (762 mm) from the point of connection to the fixture. This section has been modified to read: 604.5 Size of fixture supply. The minimum size of a fixture supply pipe shall be as shown in Table 604.5. The fixture supply pipe shall terminate not more than 30 inches (762 mm) from the point of connection to the fixture. A reduced size flexible water connector installed between the supply pipe and the fixture shall be of an approved type. The supply pipe shall extend to the floor or wall adjacent to the fixture. The minimum size of individual distribution lines utilized in gridded or parallel water distribution systems shall be as shown in Table 604.5. Exception: The fixture supply pipe for domestic dishwashers and drinking fountains shall be permitted to be terminated more than 30 inches (762 mm) from the point of connection to the fixture.
(2) Table 605.3 Water Service Pipe. This table has been modified to address errata published by the ICC® to correct a standard listing from "CSA B137.11" to "CSA B137.1" in the 16th line of the table. The table has been modified to read: Table 605.3 Water Service Pipe. The table contains 19 rows and 2 columns, and is described below:
(3) Section 608.16.4 Protection by a vacuum breaker. This section has been modified to address errata published by the ICC to specify the critical level of installation height of the vacuum breaker shall be not less than 12 inches (305 mm) above the highest elevation of downstream piping and flood level rim of the fixture or device. This section has been modified to read: 608.16.4 Protection by a vacuum breaker. Openings and outlets shall be protected by atmospheric-type or pressure-type vacuum breakers. The vacuum breaker has a critical level installation height of not less than 12 inches (305 mm) above the highest elevation of downstream piping and flood level rim of the fixture of device. Fill valves shall be set in accordance with Section 415.3.1. Vacuum breakers shall not be installed under exhaust hoods or similar locations that will contain toxic fumes or vapors. Pipe applied vacuum breakers shall be installed not less than 6 inches (152 mm) above the flood level rim of the fixture, receptor, or device served.
(4) Section 608.17.5 Connections to lawn irrigation systems. This section has been modified to add a spill resistant backflow preventer as an option for protection. This section has been modified to read: 608.17.5 Connections to lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric-type vacuum breaker, a pressure-type vacuum breaker assembly, a spill resistant backflow preventer or a reduced pressure principle backflow preventer. A valve shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principle backflow preventer assembly.
(5) Section 608.17.7 Chemical dispenser. This section has been modified to address errata published by the ICC®. The modification deletes a reference to a section that is not applicable to this section of code. This section has been modified to read: 608.17.7 Chemical dispenser. Where chemical dispensers connect to the potable water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.14.1, 608.14.2, 608.14.5, 608.14.6 or 608.14.8.