Oklahoma Administrative Code
Title 380 - Department of Labor
Chapter 25 - Boiler and Pressure Vessel Rules
Subchapter 7 - General Requirements
Section 380:25-7-16 - Exit from boiler

Universal Citation: OK Admin Code 380:25-7-16
Current through Vol. 41, No. 13, March 15, 2024

All boiler rooms exceeding 500 square feet floor area and containing one or more boilers having a fuel burning capacity of 1,000,000 BTU, or equivalent electrical heat input, shall have at least two means of exit. Each exit shall be remotely located from the other. Each elevation in such boiler room shall have two means of exit, each remotely located from the other.

Disclaimer: These regulations may not be the most recent version. Oklahoma may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.