Oklahoma Administrative Code
Title 310 - Oklahoma State Department of Health
Chapter 315 - Public Bathing Place Facility Standards
Subchapter 5 - Water and Sewer Facilities
Section 310:315-5-1 - Water supply
Current through Vol. 42, No. 1, September 16, 2024
(a) Potable water supply. The water supply serving the bathhouse and all plumbing fixtures, including drinking fountains, lavatories, and showers, shall be approved by the appropriate regulatory authority.
(b) Pool water supply. The water supply for artificially constructed bathing places shall meet the requirements as set forth in this Section.
(c) Backflow preventers. All portions of a public water distribution system serving the pool and ancillary facilities shall be protected against backflow. Water introduced into the pool either directly or through the recirculation system shall be introduced into the pool through an air gap providing two pipe diameters or six (6) inches vertical distance between the maximum flood level of the pool and the lowest point of the inlet pipe. The coping or deck constitutes the flood level, not a drain. The supply shall be protected by an air gap whenever possible. When such connections are not installed, the supply shall be protected by a suitable backflow preventer installed on the discharge side of the last control valve to the fixture, device, or appurtenance. All hose bibs in the bathing facility area shall be so equipped. For a pool auto fill system without an air gap, a RPZ backflow preventer is required. The requirements of the American National Standards Institute (ANSI) A40.6-1943; the American Society of Sanitary Engineering (ASSE) 1001-1970; ASSE 1011-1970, ASSE 1012-1972, ASSE 1013-1971, ASSE 1015-1972; or the American Water Works Association (AWWA) C506-69, or latest revisions thereof, will be used in determining substantial compliance with this requirement.
(d) Pool water quality. Unless pool water is to be supplied from an approved and properly operated public water supply system, an analysis of the proposed pool water supply shall be submitted with the plans and specifications or as part of a preliminary engineering report. The analysis shall include, as a minimum, the following parameters: pH, total alkalinity, dissolved solids, hardness both carbonate and non-carbonate, copper, iron, manganese and turbidity. Should any of the above parameters exceed the maximum limit set forth in OAC 310: Chapter 320, design and specifications of necessary treatment units required to reduce the contaminant to an acceptable level must be made a part of the swimming pool plans.
(e) Drinking fountains. Approved type angle-jet fountains with approved water supply under adequate and regulated pressure must be provided in locations available to pool patrons. In the case of non-municipal pools, this requirement will be considered met by compliance with 310:315-7-7, "Bathing places not open to the general public."