Current through all regulations passed and filed through September 16, 2024
(B) Definitions.
(1) "Circuit" means a conductor or system of
conductors through which an electric current is intended to flow.
(2) "Conductor" means a metallic material,
usually in the form of a wire or cable, suitable for carrying an electric
current. Does not include bus bars.
(3) "Current-carrying" means a conducting
part intended to be connected in an electric circuit to a source of voltage.
Noncurrent-carrying parts are those not intended to be connected.
(4) "De-energized" means being free from any
electrical connection to a source of a potential different from that of the
earth.
(5) "Energized" means
anything connected to an electrical source having a greater potential than that
of the earth.
(6) "Ground
connection" means the equipment used in establishing a path between an electric
circuit or equipment and earth. A ground connection consists of a ground
conductor, a ground electrode and the earth which surrounds the electrode.
(7) "Grounded" means connected to
earth or to some extended conducting body which serves instead of the earth
whether the connection is intentional or accidental.
(8) "Grounded effectively" means permanently
connected to earth through a ground connection or connections of sufficiently
low impedance and having sufficient current-carrying capacity to prevent the
building up of voltages which may result in undue hazard to connected equipment
or to employees.
(9) "Grounding
conductor" means a conductor which is used to connect the equipment or the
wiring system with a grounding electrode or electrodes.
(10) "Insulated" means separated from other
conducting surfaces by a dielectric substance or air space permanently offering
a high resistance to the passage of current and to disruptive discharge through
the substance or space. (Note: When any object is said to be insulated it is
understood to be insulated in a suitable manner for the conditions to which it
is subjected. Otherwise it is, within the purpose of this rule, uninsulated).
(11) "Insulating" (where applied
to the covering of a conductor or to clothing, guards, rods, and other safety
devices) means that a device, when interposed between an employee and
current-carrying parts, protects the employee making use of it against electric
shock, form the current-carrying parts with which the device is intended to be
used; the opposite ofconducting.
(12) "Phase" means one energized conductor of
an electrical system.
(13)
"Switch" means a device for opening and closing or for changing the connection
of a circuit. In this rule, a switch will always be understood to be manually
operated, unless otherwise stated.
(14) "Voltage (of a circuit)" means the
greatest root-mean-square (effective) difference of potential between any two
conductors of the circuit concerned. On various systems such as three-phase
four-wire, single-phase three-wire and three-wire direct current, there may be
various circuits of various voltages.
(15) "Voltage to ground" means, in grounded
circuits, the voltage between the given conductor and that point or conductor
of the circuit which is grounded; in grounded circuits, the greatest voltage
between the given conductor and any other conductor ofthe circuit.
(16) "Voltage" (or "volts") means the highest
effect electrical potential between any two conductors of the circuit concerned
except where, in certain paragraphs of this rule, reference is made to the term
"voltage (or volts) to ground".
(C) Installation and maintenance of temporary
wiring.
(1) All temporary wiring shall be
installed with approved overload protection and maintained in accordance with
the following:
(a) Main feed and secondary
conductors shall be no less than eight feet above the floor or ground level
unless in rigid or other conduit such as nonmetallic sheathed cable or metallic
sheathed cable which provides equivalent protection and support.
Extension cords shall not be considered as
secondary conductors. No branch circuits or feeder conductors shall be laid on
the floor except properly maintained extension cords feeding portable powered
tools.
(b) All receptacles shall
be grounded effectively.
(c) All
lamps for general illumination shall be protected from accidental contact or
breakage. Protection shall be provided by elevation ofno less than seven feet
from working surface or by a suitable fixture or lampholder with a guard.
(d) All temporary circuits shall
be grounded effectively.
(2) Bare conductors and earth returns.
No bare conductors nor earth returns shall be used for the
wiring of any temporary circuit.
(3) Disconnecting means.
Approved disconnecting switches or plug connectors shall be
installed to permit the disconnection of all ungrounded conductors of each
temporary circuit.
(4)
Construction sites.
All one-hundred-twenty-volt single-phase fifteen and twenty
ampere receptacle outlets which are not a part of the permanent wiring ofthe
building or structure, shall have ground fault circuit interrupters or the
implementation of an assured equipment grounding program on construction sites.
(5) All energized
equipment exposed to contact shall be guarded.
(6) Portable lights in damp locations shall
not exceed twelve volts, except that one hundred twenty volt lights may be used
if protected by a ground-fault circuit interrupter.
(D) Extension cords.
(1) Extension cords used with portable
electric tools and appliances shall be of three-wire type.
(2) Three-wire type extension cords to lights
or electrically powered tools or devices shall be equipped with a three-wire
grounding type receptacle and attachment plug of nonconductive material.
Splicing shall be done by vulcanized or plastic molded splice method.
Insulation shall be equal to the capable being spliced and wire connections
shall be soldered.
(3) Where
different voltages, frequencies, or type of current (alternating or direct) are
to be supplied by portable cords, receptacles shall be of such design that
attachment plugs used on such circuits are not interchangeable.
(E) Lockout and tagging of
de-energized equipment or circuits.
The employer shall instruct employees to lock out all
de-energized equipment or circuits and attach tags at all points where such
de-energized equipment or circuits can be energized.
(F) Circuits in excess of two hundred fifty
volts.
(1) The employer shall instruct
employees to de-energize and effectively ground circuits in excess of two
hundred fifty volts before working on such circuits unless personal protective
equipment is provided in accordance with paragraph (H)(3) of rule 4121:1-3-03
of the Administrative Code.
(2)
All circuits shall be worked as energized unless grounded effectively.