Title 4101:8 - Board of Building Standards: Residential Code of Ohio
Chapter 4101:8-34 - Electrical
Section 4101:8-34-01 - Electrical
Current through all regulations passed and filed through September 16, 2024
[Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:8-44-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:8-1-01 of the Administrative Code.]
SECTION 3401
ELECTRICAL
For the purposes of this Chapter, any reference in NFPA 70 to "one- and two-family dwellings" will include "one-, two- and three-family dwellings." Where the NFPA 70 requirement identifies a one-family dwelling or a two-family dwelling, a three-family dwelling is regulated as a "multi-family dwelling" (i.e. Section 210.52(E)(1)).
Exception No 5: A single receptacle located to serve a sump pump shall not be required to have ground-fault circuitinterrupter protection when there is a duplex receptacle with ground-fault circuit-interrupter protection within six (6) feet of the sump pump.
If equipment supplied by an outlet covered under the requirements of this section is replaced, the outlet is to be supplied with GFCI protection.
Exception No. 1: GFCI protection is not required on lighting outlets other than those covered in 210.8(C)
Exception No. 2: GFCI protection is not required for listed HVAC equipment.
SECTION 3402
EMERGENCY AND STANDBY POWER SYSTEMS