Current through all regulations passed and filed through September 16, 2024
[Comment: When a reference is made
within this rule to a federal statutory provision, an industry consensus
standard, or any other technical publication, the specific date and title of
the publication as well as the name and address of the promulgating agency are
listed in rule
4101:8-44-01
of the Administrative Code. The application of the referenced standards shall
be limited and as prescribed in section 102.5 of rule
4101:8-1-01 of the
Administrative Code.]
SECTION
2200
SCOPE
2200.1
Scope.
This chapter shall govern the design, installation,
construction and repair of fuel oil and diesel oil storage and piping systems
supplying and piped to building service equipment. The storage of fuel oil and
flammable and combustible liquids not associated with building services
equipment shall be in accordance with Chapters 6 and 34 of the fire code and
enforced by the fire official.
SECTION 2201
OIL TANKS
2201.1
Materials.
Supply tanks
shall be listed and labeled and shall conform to UL 58 for underground tanks
and UL 80 for indoor tanks.
2201.2
Above-ground tanks.
The
maximum amount of fuel oil
or diesel oil stored above ground
or inside of a building shall be 660 gallons (2498 L). The supply tank shall be
supported on rigid noncombustible supports to prevent settling or
shifting.
Exceptions:
1.
The storage of
fuel oil, used for space or water heating, above ground or inside buildings in
quantities exceeding 660 gallons (2498 L) shall comply with NFPA
31.
2.
The storage of diesel oil supplying and piped to
engine-driven building services equipment, including emergency and standby
generators, above ground or inside buildings in quantities exceeding 660
gallons shall comply with NFPA 37.
2201.2.1
Tanks
within buildings.
Supply tanks for use
inside of buildings shall be of such size and shape to permit installation and
removal from dwellings as whole units. Supply tanks larger than 10 gallons (38
L) shall be placed not less than 5 feet (1524 mm) from any fire or flame either
within or external to any fuel-burning appliance.
2201.2.2
Outdoor above-ground tanks.
Tanks installed outdoors, above ground shall be not
less than 5 feet (1524 mm) from an adjoining property line. Such tanks shall be
suitably protected from the weather and from physical damage.
2201.3
Underground tanks.
Excavations for underground tanks shall not undermine the
foundations of existing structures. The clearance from the tank to the nearest
wall of a basement, pit or property line shall be not less than 1 foot (305
mm). Tanks shall be set on and surrounded with noncorrosive inert materials
such as clean earth, sand or gravel well-tamped in place. Tanks shall be
covered with not less than 1 foot (305 mm) of earth. Corrosion protection shall
be provided in accordance with Section 2203.7.
2201.3.1
Regulated underground storage of fuel
oil.
The design,
installation, registration, and inspection of regulated underground storage
tanks shall be in accordance with the fire code and rules adopted by the state
fire marshal and enforced by the fire official, in accordance with sections
3737.87 to
3737.89 of the Revised Code.
Underground storage tanks not regulated by the state fire marshal's Bureau of
Underground Storage tanks shall comply with the applicable requirements of
Chapter 23 of NFPA 30.
2201.4
Multiple
tanks.
Cross connection of two supply
tanks shall be permitted in accordance with Section 2203.6.
2201.5
Oil
gauges.
Inside tanks shall be provided
with a device to indicate when the oil in the tank has reached a predetermined
safe level. Glass gauges or a gauge subject to breakage that could result in
the escape of oil from the tank shall not be used. Liquid-level indicating
gauges shall comply with UL 180.
2201.6
Flood-resistant installation.
In flood hazard areas as established by Table 301.2(1),
tanks shall be installed in accordance with Section 322.2.4 or
322.3.10.
2201.7
Tanks abandoned or removed.
Outdoor above-grade fill piping shall be removed when
tanks are abandoned or removed. Tank abandonment and removal shall be in
accordance with thefire code.
SECTION 2202
OIL PIPING, FITTING AND
CONNECTIONS
2202.1
Materials.
Piping shall consist of steel pipe, copper and copper-alloy
pipe and tubing or steel tubing conforming to ASTM A539. Aluminum tubing shall
not be used between the fuel-oil tank and the burner units.
2202.2
Joints
and fittings.
Piping shall be connected
with standard fittings compatible with the piping material. Cast-iron fittings
shall not be used for oil piping. Unions requiring gaskets or packings, right
or left couplings, and sweat fittings employing solder having a melting point
less than 1,000°F (538°C) shall not be used for oil piping. Threaded
joints and connections shall be made tight with a lubricant or pipe thread
compound.
2202.3
Flexible connectors.
Flexible metallic hoses shall be listed and labeled in
accordance with UL 536 and shall be installed in accordance with their listing
and labeling and the manufacturer's installation instructions. Connectors made
from combustible materials shall not be used inside of buildings or above
ground outside of buildings.
SECTION 2203
INSTALLATION
2203.1
General.
Piping shall
be installed in a manner to avoid placing stresses on the piping, and to
accommodate expansion and contraction of the piping system.
2203.2
Supply
piping.
Supply piping used in the
installation of oil burners and appliances shall be not smaller
than3/8-inch (9 mm) pipe
or3/8 -inch (9 mm) outside diameter tubing. Copper
tubing and fittings shall be Type L or heavier.
2203.3
Fill
piping.
Fill piping shall terminate
outside of buildings at a point not less than 2 feet (610 mm) from any building
opening at the same or lower level. Fill openings shall be equipped with a
tight metal cover.
2203.4
Vent piping.
Vent piping shall be not smaller than
11/4 -inch (32 mm) pipe. Vent piping shall be
laid to drain toward the tank without sags or traps in which the liquid can
collect. Vent pipes shall not be cross connected with fill pipes, lines from
burners or overflow lines from auxiliary tanks. The lower end of a vent pipe
shall enter the tank through the top and shall extend into the tank not more
than 1 inch (25 mm).
2203.5
Vent termination.
Vent piping shall terminate out- side of buildings at a
point not less than 2 feet (610 mm), measured vertically or horizontally, from
any building opening. Outer ends of vent piping shall terminate in a
weather-proof cap or fitting having an unobstructed area equal to or greater
than the cross-sectional area of the vent pipe, and shall be located
sufficiently above the ground to avoid being obstructed by snow and
ice.
2203.6
Cross connection of tanks.
Cross connection of two supply tanks, not exceeding 660
gallons (2498 L) aggregate capacity, with gravity flow from one tank to
another, shall be acceptable providing that the two tanks are on the same
horizontal plane.
2203.7
Corrosion protection.
Underground tanks and buried piping shall be protected
by corrosion-resistant coatings or special alloys or fiberglass-reinforced
plastic.
SECTION
2204
OIL PUMPS AND VALVES
2204.1
Pumps.
Oil pumps shall
be positive displacement types that automatically shut off the oil supply when
stopped. Automatic pumps shall be listed and labeled in accordance with UL 343
and shall be installed in accordance with their listing.
2204.2
Shutoff
valves.
A manual shutoff valve shall be
installed between the oil supply tank and the burner. Such valve shall be
provided with ready access. Where the shutoff valve is installed in the
discharge line of an oil pump, a pressure relief valve shall be incorporated to
bypass or return surplus oil. Valves shall comply with UL 842.
2204.3
Maximum
pressure.
Pressure at the oil supply inlet
to an appliance shall be not greater than 3 pounds per square inch ( 20.7
kPa).
2204.4
Relief valves.
Fuel-oil
lines incorporating heaters shall be provided with relief valves that will
discharge to a return line when excess pressure
exists.
Replaces: 4101:8-22-01