Current through all regulations passed and filed through September 16, 2024
[Comment: When a reference is made
within this rule to a federal statutory provision, an industry consensus
standard, or any other technical publication, the specific date and title of
the publication as well as the name and address of the promulgating agency are
listed in rule
4101:8-44-01
of the Administrative Code. The application of the referenced standards shall
be limited and as prescribed in section 102.5 of rule
4101:8-1-01 of the
Administrative Code.]
SECTION
2001
BOILERS
2001.1
Installation.
In
addition to the requirements of this code, the installation of boilers shall
conform to the manufacturer's instructions. The manufacturer's rating data, the
nameplate and operating instructions of a permanent type shall be attached to
the boiler. Boilers shall have their controls set, adjusted and tested by the
installer. A complete control diagram together with complete boiler operating
instructions shall be furnished by the installer. Solid and liquid fuel-burning
boilers shall be provided with combustion air as required by Chapter 17.
2001.1.1
Standards.
Packaged
oil-fired boilers shall be listed and labeled in accordance with UL 726.
Packaged electric boilers shall be listed and labeled in accordance with UL
834. Solid fuel-fired boilers shall be listed and labeled in accordance with UL
2523. Boilers shall be designed, constructed and certified in accordance with
the "ASME Boiler and Pressure Vessel Code, Section I or IV." The boiler
shall be provided with safety devices and controls as required in the
applicable section of the "ASME Boiler and Pressure Vessel Code." For boilers
with fuel input ratings of 12,500,000 Btu/hr (3663 kW) or less, controls and
safety devices meeting the requirements of ASME CSD-1 is an acceptable
alternative. Gas-fired boilers shall conform to the requirements
listed in Chapter 24.
2001.2
Clearance.
Boilers
shall be installed in accordance with their listing and label.
2001.3
Valves.
Every boiler or
modular boiler shall have a shutoff valve in the supply and return piping. For
multiple boiler or multiple modular boiler installations, each boiler or
modular boiler shall have individual shutoff valves in the supply and return
piping.
Exception:
Shutoff valves are not required in a system having a
single low-pressure steam boiler.
2001.4
Flood-resistant installation.
In flood hazard areas established in Table 301.2(1),
boilers, water heaters and their control systems shall be located or installed
in accordance with Section 322.1.6.
SECTION 2002
OPERATING AND SAFETY
CONTROLS
2002.1
Safety controls.
Electrical and mechanical operating and safety controls for
boilers shall be listed and labeled.
2002.2
Hot
water boiler gauges.
Every hot water
boiler shall have a pressure gauge and a temperature gauge, or combination
pressure and temperature gauge. The gauges shall indicate the temperature and
pressure within the normal range of the system's operation.
2002.3
Steam
boiler gauges.
Every steam boiler shall
have a water-gauge glass and a pressure gauge. The pressure gauge shall
indicate the pressure within the normal range of the system's operation. The
gauge glass shall be installed so that the midpoint is at the normal water
level.
2002.4
Pressure relief valve.
Boilers shall be equipped with pressure relief valves with
minimum rated capacities for the equipment served. Pressure relief valves shall
be set at the maximum rating of the boiler. Discharge shall be piped to drains
by gravity to within 18 inches (457 mm) of the floor or to an open
receptor.
2002.5
Boiler low-water cutoff.
Steam and hot water boilers shall be protected with a
low-water cutoff control.
Exception:
A low-water cutoff is not required for coil-type and
water-tube-type boilers that require forced circulation of water through the
boiler and that are protected with a flow-sensing control.
2002.6
Operation.
Low-water
cutoff controls and flow-sensing controls required by Section 2002.5 shall
automatically stop the combustion operation of the appliance when the water
level drops below the lowest safe water level as established by the
manufacturer or when the water circulation flow is less than that required for
safe operation of the appliance, respectively.
SECTION 2003
EXPANSION TANKS
2003.1
General.
Hot water
boilers shall be provided with expansion tanks. Nonpressurized expansion tanks
shall be securely fastened to the structure or boiler and supported to carry
twice the weight of the tank filled with water. Provisions shall be made for
draining nonpressurized tanks without emptying the system.
2003.1.1
Pressurized expansion tanks.
Pressurized expansion tanks shall be consistent with
the volume and capacity of the system. Tanks shall be capable of with-standing
a hydrostatic test pressure of two and one-half times the allowable working
pressure of the system.
2003.2
Minimum
capacity.
The minimum capacity of
expansion tanks shall be determined from Table 2003.2.
TABLE 2003.2
EXPANSION TANK MINIMUM
CAPACITYa FOR FORCED HOT-WATER
SYSTEMS
SYSTEM
VOLUMEb(gallons)
|
PRESSURIZED DIAPHRAGM
TYPE
|
NONPRESSURIZED
TYPE
|
10
|
1.0
|
1.5
|
20
|
1.5
|
3.0
|
30
|
2.5
|
4.5
|
40
|
3.0
|
6.0
|
50
|
4.0
|
7.5
|
60
|
5.0
|
9.0
|
70
|
6.0
|
10.5
|
80
|
6.5
|
12.0
|
90
|
7.5
|
13.5
|
100
|
8.0
|
15.0
|
For SI: 1 gallon = 3.785 L, 1 pound per square
inch gauge = 6.895 kPa, °C = [(°F)-32]/ 1.8.
a.
Based on average
water temperature of 195°F, fill pressure of 12 psig and an operating
pressure of not greater than 30 psig.
b.
System volume
includes volume of water in boiler, convectors and piping, not including the
expansion tank.
SECTION 2004
WATER HEATERS USED FOR SPACE
HEATING
2004.1
General.
Water heaters
used to supply both potable hot water and hot water for space heating shall be
installed in accordance with this chapter, Chapter 24, the plumbing
code as modified by Chapter 25 and the manufacturer's
instructions.
SECTION
2005
WATER HEATERS
2005.1
General.
Water heaters
shall be installed in accordance with the plumbing code as modified by
Chapter 25, the manufacturer's instructions and the requirements of
this code. Water heaters installed in an attic shall comply with the
requirements of Section M1305.1.2. Gas-fired water heaters shall comply with
the requirements in Chapter 24. Domestic electric water heaters shall comply
with UL 174. Oiled-fired water heaters shall comply with UL 732. Solar thermal
water heating systems shall comply with Chapter 23 and SRCC 300. Solid
fuel-fired water heaters shall comply with UL 2523.
2005.2
Prohibited locations.
Fuel-fired water heaters shall not be installed in a room
used as a storage closet. Water heaters located in a bedroom or bathroom shall
be installed in a sealed enclosure so that combustion air will not be taken
from the living space. Installation of direct-vent water heaters within an
enclosure is not required.
2005.2.1
Water heater access.
Access to water heaters that are located in an attic or
under floor crawl space is permitted to be through a closet located in a
sleeping room or bathroom where ventilation of those spaces is in accordance
with this code.
2005.3
Electric
water heaters.
Electric water heaters
shall be installed in accordance with the applicable provisions of NFPA
70 as modified in Chapter 34.
2005.4
Supplemental water-heating devices.
Potable water-heating devices that use
refrigerant-to-water heat exchangers shall be approved and installed in
accordance with the manufacturer's instructions.
SECTION 2006
POOL HEATERS
2006.1
General.
Deleted.
2006.2
Clearances.
Deleted.
2006.3
Bypass
valves.
Deleted.
Replaces: 4101:8-20-01