Current through all regulations passed and filed through September 16, 2024
SECTION
1801
GENERAL
1801.1
Venting
required.
Fuel-burning appliances shall be
vented to the outdoors in accordance with their listing and label and
manufacturer's installation instructions except appliances listed and labeled
for unvented use. Venting systems shall consist of approved chimneys or vents,
or venting assemblies that are integral parts of labeled appliances. Gas-fired
appliances shall be vented in accordance with Chapter 24.
This section should not be construed as
permitting the installation of portable unvented heaters in locations otherwise
prohibited by section
3701.82 of the Revised Code or
rules adopted by the state fire marshal pursuant to
3701.82 of the Revised
Code.
1801.2
Draft requirements.
A venting system shall satisfy the draft requirements
of the appliance in accordance with the manufacturer's installation
instructions, and shall be constructed and installed to develop a positive flow
to convey combustion products to the outside atmosphere.
1801.3
Existing
chimneys and vents.
Where an appliance is
permanently disconnected from an existing chimney or vent, or where an
appliance is connected to an existing chimney or vent during the process of a
new installation, the chimney or vent shall comply with Sections 1801.3.1
through 1801.3.4.
1801.3.1
Size.
The chimney or
vent shall be resized as necessary to control flue gas condensation in the
interior of the chimney or vent and to provide the appliance, or appliances
served, with the required draft. For the venting of oil-fired appliances to
masonry chimneys, the resizing shall be done in accordance with NFPA
31.
1801.3.2
Flue passageways.
The
flue gas passageway shall be free of obstructions and combustible deposits and
shall be cleaned if previously used for venting a solid or liquid fuel-burning
appliance or fireplace. The flue liner, chimney inner wall or vent inner wall
shall be continuous and free of cracks, gaps, perforations, or other damage or
deterioration that would allow the escape of combustion products, including
gases, moisture and creosote.
1801.3.3
Cleanout.
Masonry
chimneys shall be provided with a cleanout opening complying with Section
1003.17.
1801.3.4
Clearances.
Chimneys
and vents shall have airspace clearance to combustibles in accordance with this
code and the chimney or vent manufacturer's installation instructions.
Exception:
Masonry chimneys equipped with a chimney lining system
tested and listed for installation in chimneys in contact with combustibles in
accordance with UL 1777, and installed in accordance with the manufacturer's
instructions, shall not be required to have a clearance between combustible
materials and exterior surfaces of the masonry chimney. Noncombustible fire
stopping shall be provided in accordance with this code.
1801.4
Space around lining.
The space surrounding a flue lining system or other vent
installed within a masonry chimney shall not be used to vent any other
appliance. This shall not prevent the installation of a separate flue lining in
accordance with the manufacturer's installation instructions and this
code.
1801.5
Mechanical draft systems.
A mechanical draft system shall be used only with
appliances listed and labeled for such use. Provisions shall be made to prevent
the flow of fuel to the equipment when the draft system is not operating.
Forced draft systems and portions of induced draft systems under positive
pressure during operation shall be designed and installed to prevent leakage of
flue gases into a building.
1801.6
Direct-vent appliances.
Direct-vent appliances shall be installed in accordance with
the manufacturer's instructions.
1801.7
Support.
Venting
systems shall be adequately supported for the weight of the material
used.
1801.8
Duct penetrations.
Chimneys, vents and vent connectors shall not extend into or
through supply and return air ducts or plenums.
1801.9
Fireblocking.
Vent and
chimney installations shall be fireblocked in accordance with Section
602.8.
1801.10
Unused openings.
Unused
openings in any venting system shall be closed or capped.
1801.11
Multiple-appliance venting systems.
Two or more listed and labeled appliances connected to
a common natural draft venting system shall comply with the following
requirements:
1.
Appliances that are connected to common venting systems
shall be located on the same floor of the dwelling.
Exception:
Engineered systems as provided for in Section
2427.
2.
Inlets to common venting systems shall be offset such
that no portion of an inlet is opposite another inlet.
3.
Connectors serving
appliances operating under a natural draft shall not be connected to any
portion of a mechanical draft system operating under positive
pressure.
1801.12
Multiple solid fuel prohibited.
A solid fuel-burning appliance or fireplace shall not
connect to a chimney passageway venting another
appliance.
SECTION
1802
VENT COMPONENTS
1802.1
Draft
hoods.
Draft hoods shall be located in the
same room or space as the combustion air openings for the
appliances.
1802.2
Vent dampers.
Vent
dampers shall comply with Sections 1802.2.1 and 1802.2.2.
1802.2.1
Manually operated.
Manually operated dampers shall not be installed except in
connectors or chimneys serving solid fuel-burning appliances.
1802.2.2
Automatically operated.
Automatically operated dampers shall conform to UL 17 and be
installed in accordance with the terms of their listing and label. The
installation shall prevent firing of the burner when the damper is not opened
to a safe position.
1802.3
Draft
regulators.
Draft regulators shall be
provided for oil-fired appliances that must be connected to a chimney. Draft
regulators provided for solid fuel-burning appliances to reduce draft intensity
shall be installed and set in accordance with the manufacturer's installation
instructions.
1802.3.1
Location.
Where
required, draft regulators shall be installed in the same room or enclosure as
the appliance so that a difference in pressure will not exist between the air
at the regulator and the combustion air supply.
SECTION 1803
CHIMNEY AND VENT
CONNECTORS
1803.1
General.
Connectors shall be used to connect fuel-burning appliances
to a vertical chimney or vent except where the chimney or vent is attached
directly to the appliance.
1803.2
Connectors for oil and solid fuel-burning
appliances.
Connectors for oil and solid
fuel-burning appliances shall be constructed of factory-built chimney material,
Type L vent material or single-wall metal pipe having resistance to corrosion
and heat and thickness not less than that of galvanized steel as specified in
Table 1803.2.
TABLE 1803.2
THICKNESS FOR SINGLE-WALL METAL PIPE
CONNECTORS
DIAMETER OF CONNECTOR
(inches)
|
GALVANIZED SHEET METAL GAGE
NUMBER
|
MINIMUM THICKNESS
(inch)
|
Less than 6
|
26
|
0.019
|
6 to 10
|
24
|
0.024
|
Over 10 through 16
|
22
|
0.029
|
For SI: 1 inch = 25.4 mm.
1803.3
Installation.
Vent and
chimney connectors shall be installed in accordance with the manufacturer's
instructions and within the space where the appliance is located. Appliances
shall be located as close as practical to the vent or chimney. Connectors shall
be as short and straight as possible and installed with a slope of not less
than 1/4 inch (6 mm) rise per foot of run. Connectors shall be securely
supported and joints shall be fastened with sheet metal screws or rivets.
Devices that obstruct the flow of flue gases shall not be installed in a
connector unless listed and labeled or approved for such installation.
1803.3.1
Floor,
ceiling and wall penetrations.
A chimney
connector or vent connector shall not pass through any floor or ceiling. A
chimney connector or vent connector shall not pass through a wall or partition
unless the connector is listed and labeled for wall pass-through, or is routed
through a device listed and labeled for wall pass-through and is installed in
accordance with the conditions of its listing and label. Connectors for
oil-fired appliances listed and labeled for Type L vents, passing through walls
or partitions shall be in accordance with the following:
1.
Type L vent
material for oil appliances shall be installed with not less than listed and
labeled clearances to combustible material.
2.
Single-wall metal
pipe shall be guarded by a ventilated metal thimble not less than 4 inches (102
mm) larger in diameter than the vent connector. Not less than 6 inches (152 mm)
of clearance shall be maintained between the thimble and
combustibles.
1803.3.2
Length.
The horizontal
run of an uninsulated connector to a natural draft chimney shall not exceed 75
percent of the height of the vertical portion of the chimney above the
connector. The horizontal run of a listed connector to a natural draft chimney
shall not exceed 100 percent of the height of the vertical portion of the
chimney above the connector.
1803.3.3
Size.
A connector shall
not be smaller than the flue collar of the appliance.
Exception:
Where installed in accordance with the appliance
manufacturer's instructions.
1803.3.4
Clearance.
Connectors
shall be installed with clearance to combustibles as set forth in Table
1803.3.4. Reduced clearances to combustible materials shall be in accordance
with Table 1306.2 and Figure 1306.1.
TABLE 1803.3.4
CHIMNEY AND VENT CONNECTOR CLEARANCES TO
COMBUSTIBLE MATERIALSa
TYPE OF
CONNECTOR
|
MINIMUM CLEARANCE
(inches)
|
Single-wall metal pipe
connectors:
Oil and solid-fuel
appliances
Oil appliances listed for use with Type
L vents
|
18
9
|
Type L vent piping
connectors:
Oil and solid-fuel
appliances
Oil appliances listed for use with Type
L vents
|
9
3b
|
For SI: 1 inch = 25.4 mm.
a.
These minimum
clearances apply to unlisted single-wall chimney and vent connectors. Reduction
of required clearances is permitted as in Table 1306.2.
b.
Where listed Type
L vent piping is used, the clearance shall be in accordance with the vent
listing.
1803.3.5
Access
The
entire length of a connector shall allow access for inspection, cleaning and
replacement.
1803.4
Connection to fireplace flue.
Connection of appliances to chimney flues serving
fireplaces shall comply with Sections 1803.4.1 through 1803.4.4.
1803.4.1
Closure and accessibility.
A noncombustible seal shall be provided below the point
of connection to prevent entry of room air into the flue. Means shall be
provided for access to the flue for inspection and cleaning.
1803.4.2
Connection to factory-built fireplace flue.
A different appliance shall not be connected to a flue
serving a factory-built fireplace unless the appliance is specifically listed
for such an installation. The connection shall be made in compliance with the
appliance manufacturer's instructions.
1803.4.3
Connection to masonry fireplace flue.
A connector shall extend from the appliance to the flue
serving a masonry fireplace to convey the flue gases directly into the flue.
The connector shall be provided with access or shall be removable for
inspection and cleaning of both the connector and the flue. Listed
direct-connection devices shall be installed in accordance with their
listing.
1803.4.4
Size of flue.
The size
of the fireplace flue shall be in accordance with Section
1805.3.1.
SECTION
1804
VENTS
1804.1
Type of
vent required.
Appliances shall be
provided with a listed and labeled venting system as set forth in Table
1804.1.
TABLE 1804.1
VENT SELECTION CHART
VENT TYPES
|
APPLIANCE
TYPES
|
Type L oil vents
|
Oil-burning appliances listed and
labeled for venting with Type L vents
|
Pellet vents
|
Pellet fuel-burning appliances listed
and labeled for use with pellet vents
|
1804.2
Termination.
Vent termination shall comply with Sections 1804.2.1 through
1804.2.6.
1804.2.1
Through the roof.
Vents
passing through a roof shall extend through flashing and terminate in
accordance with the manufacturer's installation requirements.
1804.2.2
Decorative shrouds.
Decorative shrouds shall not be installed at the termination
of vents except where the shrouds are listed and labeled for use with the
specific venting system and are installed in accordance with the manufacturer's
instructions.
1804.2.3
Natural draft appliances.
Vents for natural draft appliances shall terminate not
less than 5 feet (1524 mm) above the highest connected appliance outlet, and
natural draft gas vents serving wall furnaces shall terminate at an elevation
not less than 12 feet (3658 mm) above the bottom of the
furnace.
1804.2.4
Type L vent.
Type L
venting systems shall conform to UL 641 and shall terminate with a listed and
labeled cap in accordance with the vent manufacturer's installation
instructions not less than 2 feet (610 mm) above the roof and not less than 2
feet (610 mm) above any portion of the building within 10 feet (3048
mm).
1804.2.5
Direct vent terminations.
Vent terminals for direct-vent appliances shall be
installed in accordance with the manufacturer's instructions.
1804.2.6
Mechanical draft systems.
Mechanical draft systems shall comply with UL 378 and
shall be installed in accordance with their listing, the manufacturer's
instructions and, except for direct-vent appliances, the following
requirements:
1.
The vent terminal shall be located not less than 3 feet
(914 mm) above a forced air inlet located within 10 feet (3048
mm).
2.
The vent terminal shall be located not less than 4 feet
(1219 mm) below, 4 feet (1219 mm) horizontally from, or 1 foot (305 mm) above
any door, window or gravity air inlet into a dwelling.
3.
The vent
termination point shall be located not closer than 3 feet (914 mm) to an
interior corner formed by two walls perpendicular to each
other.
4.
The bottom of the vent terminal shall be located not
less than 12 inches (305 mm) above finished ground level.
5.
The vent
termination shall not be mounted directly above or within 3 feet (914 mm)
horizontally of an oil tank vent or gas meter.
6.
Power exhauster
terminations shall be located not less than 10 feet (3048 mm) from lot lines
and adjacent buildings.
7.
The discharge shall be directed away from the
building.
1804.3
Installation.
Type L
and pellet vents shall be installed in accordance with the terms of their
listing and label and the manufacturer's instructions.
1804.3.1
Size
of single-appliance venting systems.
An
individual vent for a single appliance shall have a cross-sectional area equal
to or greater than the area of the connector to the appliance, but not less
than 7 square inches (4515 mm2) except where the vent is an integral part of a
listed and labeled appliance.
1804.4
Door
swing.
Appliance and equipment vent
terminals shall be located such that doors cannot swing within 12 inches (305
mm) horizontally of the vent terminals. Door stops or closers shall not be
installed to obtain this clearance.
SECTION 1805
MASONRY AND FACTORY-BUILT
CHIMNEYS
1805.1
General.
Masonry and factory-built chimneys shall be built and
installed in accordance with Sections 1003 and 1005, respectively. Flue lining
for masonry chimneys shall comply with Section 1003.11.
1805.2
Masonry
chimney connection.
A chimney connector
shall enter a masonry chimney not less than 6 inches (152 mm) above the bottom
of the chimney. Where it is not possible to locate the connector entry not less
than 6 inches (152 mm) above the bottom of the chimney flue, a cleanout shall
be provided by installing a capped tee in the connector next to the chimney. A
connector entering a masonry chimney shall extend through, but not beyond, the
wall and shall be flush with the inner face of the liner. Connectors, or
thimbles where used, shall be firmly cemented into the masonry.
1805.3
Size of
chimney flues.
The effective area of a
natural draft chimney flue for one appliance shall be not less than the area of
the connector to the appliance. The area of chimney flues connected to more
than one appliance shall be not less than the area of the largest connector
plus 50 percent of the areas of additional chimney connectors.
Exception:
Chimney flues serving oil-fired appliances sized in
accordance with NFPA 31.
1805.3.1
Size
of chimney flue for solid-fuel appliance.
Except where otherwise specified in the manufacturer's
installation instructions, the cross-sectional area of a flue connected to a
solid fuel-burning appliance shall be not less than the area of the flue collar
or connector, and not larger than three times the area of the flue
collar.