[Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:8-44-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:8-1-01 of the Administrative Code.]
SECTION 1501
GENERAL
Exception: Whole-house ventilation-type attic fans that discharge into the attic space of dwelling units having private attics shall be permitted.
SECTION 1502
CLOTHES DRYER EXHAUST
Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers.
TABLE 1502.4.5.1
DRYER EXHAUST DUCT FITTING EQUIVALENT LENGTH
DRYER EXHAUST DUCT FITTING TYPE |
EQUIVALENT LENGTH |
4-inch radius mitered 45-degree elbow |
2 feet 6 inches |
4-inch radius mitered 90-degree elbow |
5 feet |
6-inch radius smooth 45-degree elbow |
1 foot |
6-inch radius smooth 90-degree elbow |
1 foot 9 inches |
8-inch radius smooth 45-degree elbow |
1 foot |
8-inch radius smooth 90-degree elbow |
1 foot 7 inches |
10-inch radius smooth 45-degree elbow |
9 inches |
10-inch radius smooth 90-degree elbow |
1 foot 6 inches |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
Exception: Where a listed condensing clothes dryer is installed prior to occupancy of the structure.
SECTION 1503
DOMESTIC COOKING EXHAUST EQUIPMENT
Exception: Broiler units that incorporate an integral exhaust system, and that are listed and labeled for use without an exhaust hood, shall not be required to have an exhaust hood.
Exception: Where installed in accordance with the manufacturer's instructions and where mechanical or natural ventilation is otherwise provided, listed and labeled ductless range hoods shall not be required to discharge to the outdoors.
Exception: Ducts for domestic kitchen cooking appliances equipped with down-draft exhaust systems shall be permitted to be constructed of schedule 40 PVC pipe and fittings provided that the installation complies with all of the following:
Exceptions:
SECTION 1504
EXHAUST DUCTS AND EXHAUST OPENINGS
Exception: Duct length shall not be limited where the duct system complies with the manufacturer's design criteria or where the flow rate of the installed ventilating equipment is verified by the installer or approved third party using a flow hood, flow grid or other airflow measuring device.
TABLE 1504.2
DUCT LENGTH
DUCT TYPE |
FLEX DUCT |
SMOOTH-WALL DUCT |
||||||||||||||
Fan airflow rating (CFM @ 0.25 inch wca) |
50 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
50 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
Diameterb (inches) |
Maximum lengthc,d,e (feet) |
|||||||||||||||
3 |
X |
X |
X |
X |
X |
X |
X |
X |
5 |
X |
X |
X |
X |
X |
X |
X |
4 |
56 |
4 |
X |
X |
X |
X |
X |
X |
114 |
31 |
10 |
X |
X |
X |
X |
X |
5 |
NL |
81 |
42 |
16 |
2 |
X |
X |
X |
NL |
152 |
91 |
51 |
28 |
4 |
X |
X |
6 |
NL |
NL |
158 |
91 |
55 |
18 |
1 |
X |
NL |
NL |
NL |
168 |
112 |
53 |
25 |
9 |
7 |
NL |
NL |
NL |
NL |
161 |
78 |
40 |
19 |
NL |
NL |
NL |
NL |
NL |
148 |
88 |
54 |
8 and above |
NL |
NL |
NL |
NL |
NL |
189 |
111 |
69 |
NL |
NL |
NL |
NL |
NL |
NL |
198 |
133 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Fan airflow rating shall be in accordance with ANSI/AMCA 210-ANSI/ASHRAE 51.
b. For noncircular ducts, calculate the diameter as four times the cross-sectional area divided by the perimeter.
c. This table assumes that elbows are not used. Fifteen feet of allowable duct length shall be deducted for each elbow installed in the duct run.
d. NL = no limit on duct length of this size.
e. X = not allowed. Any length of duct of this size with assumed turns and fittings will exceed the rated pressure drop.
SECTION 1505
MECHANICAL VENTILATION
Equation 15-1
Exception: The whole-house mechanical ventilation system is permitted to operate intermittently where the system has controls that enable operation for not less than 25 percent of each 4-hour segment and the ventilation rate prescribed in Table 1505.4.3(1) is multiplied by the factor determined in accordance with Table 1505.4.3(2).
TABLE 1505.4.3(1)
CONTINUOUS WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS
DWELLING UNIT FLOOR AREA (square feet) |
NUMBER OF BEDROOMS |
||||
0 - 1 |
2 - 3 |
4 - 5 |
6 - 7 |
> 7 |
|
Airflow in CFM |
|||||
< 1,500 |
30 |
45 |
60 |
75 |
90 |
1,501 - 3,000 |
45 |
60 |
75 |
90 |
105 |
3,001 - 4,500 |
60 |
75 |
90 |
105 |
120 |
4,501 - 6,000 |
75 |
90 |
105 |
120 |
135 |
6,001 - 7,500 |
90 |
105 |
120 |
135 |
150 |
=> 7,500 |
105 |
120 |
135 |
150 |
165 |
For SI: 1 square foot = 0.0929 m2, 1 cubic foot per minute = 0.0004719 m3/s.
TABLE 1505.4.3(2)
INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSa,b
RUN-TIME PERCENTAGE IN EACH 4-HOUR SEGMENT |
25% |
33% |
50% |
66% |
75% |
100% |
Factora |
4 |
3 |
2 |
1.5 |
1.3 |
1.0 |
a. For ventilation system run time values between those given, the factors are permitted to be determined by interpolation.
b. Extrapolation beyond the table is prohibited.
TABLE 1505.4.4
MINIMUM REQUIRED LOCAL EXHAUST RATES FOR ONE-, TWO-AND THREE FAMILY DWELLINGS
AREA TO BE EXHAUSTED |
EXHAUST RATES |
Kitchens |
100 cfm intermittent or 25 cfm continuous |
Bathrooms-Toilet Rooms |
Mechanical exhaust capacity of 50 cfm intermittent or 20 cfm continuous |
For SI: 1 cubic foot per minute = 0.0004719 m3/s.