Current through all regulations passed and filed through September 16, 2024
SECTION
1001
MASONRY FIREPLACES
1001.1
General.
Masonry
fireplaces shall be constructed in accordance with this section and the
applicable provisions of Chapters 3 and 4.
TABLE 1001.1
SUMMARY OF REQUIREMENTS
FOR
MASONRY FIREPLACES AND
CHIMNEYS
ITEM
|
LETTERa
|
REQUIREMENTS
|
Hearth slab thickness
|
A
|
4"
|
Hearth extension (each side of
opening)
|
B
|
8" fireplace opening < 6 square
feet.
12" fireplace opening >= 6 square
feet.
|
Hearth extension (front of
opening)
|
C
|
16" fireplace opening < 6 square
feet.
20" fireplace opening > 6 square
feet.
|
Hearth slab reinforcing
|
D
|
Reinforced to carry its own weight and
all imposed loads.
|
Thickness of wall of
firebox
|
E
|
10" solid brick or 8" where a firebrick
lining is used. Joints in firebrick1/4"
maximum.
|
Distance from top of opening to
throat
|
F
|
8"
|
Smoke chamber wall thickness Unlined
walls
|
G
|
6"
8"
|
Chimney Vertical
reinforcingb
|
H
|
Four No. 4 full-length bars for chimney
up to 40" wide. Add two No. 4 bars for each additional 40" or fraction of width
or each additional flue.
|
Horizontal reinforcing
|
J
|
1/4" ties at
18" and two ties at each bend in vertical steel.
|
Bond beams
|
K
|
No specified requirements.
|
Fireplace lintel
|
L
|
Noncombustible material.
|
Chimney walls with flue
lining
|
M
|
Solid masonry units or hollow masonry
units grouted solid with not less than 4-inch nominal thickness.
|
Distances between adjacent
flues
|
-
|
See Section 1003.13.
|
Effective flue area (based on area of
fireplace opening)
|
P
|
See Section 1003.15.
|
Clearances:
Combustible material
Mantel and trim
Above roof
|
R
|
See Sections 1001.11 and
1003.18.
See Section 1001.11, Exception
4.
3' at roofline and 2' at
10'.
|
Anchorageb
Strap
Number
Embedment into chimney
Fasten to
Bolts
|
S
|
3/16" × 1"
Two 12" hooked around outer bar with 6"
extension.
4 joists
Two1/2"
diameter.
|
Footing
Thickness
Width
|
T
|
12" min.
6" each side of fireplace
wall.
|
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1
square foot = 0.0929 m2. Note: This
table provides a summary of major requirements for the construction of masonry
chimneys and fireplaces. Letter references are to Figure 1001.1, which shows
examples of typical construction. This table does not cover all requirements,
nor does it cover all aspects of the indicated requirements. For the actual
mandatory requirements of the code, see the indicated section of
text.
a.
The letters
refer to Figure 1001.1.
b.
Not required
in Seismic Design Category A, B or C.
Click to
view image
For SI: 1 inch = 25.4 mm, 1 foot = 304.8
mm.
FIGURE 1001.1
FIREPLACE AND CHIMNEY
DETAILS
1001.2
Footings and foundations.
Footings for masonry fireplaces and their chimneys
shall be constructed of concrete or solid masonry not less than 12 inches (305
mm) thick and shall extend not less than 6 inches (152 mm) beyond the face of
the fireplace or foundation wall on all sides. Footings shall be founded on
natural, undisturbed earth or engineered fill below frost depth. In areas not
subjected to freezing, footings shall be not less than 12 inches (305 mm) below
finished grade.
1001.2.1
Ash dump cleanout.
Cleanout openings located within foundation walls below
fireboxes, where provided, shall be equipped with ferrous metal or masonry
doors and frames constructed to remain tightly closed except when in use.
Cleanouts shall be located to allow access so that ash removal will not create
a hazard to combustible materials.
1001.3
Seismic
reinforcing.Deleted.
1001.3.1
Vertical reinforcing.Deleted.
1001.3.2
Horizontal
reinforcing.Deleted.
1001.4
Seismic
anchorage.Deleted.
1001.5
Firebox
walls.
Masonry fireboxes shall be
constructed of solid masonry units, hollow masonry units grouted solid, stone
or concrete. Where a lining of firebrick not less than 2 inches (51 mm) thick
or other approved lining is provided, the minimum thickness of back and
sidewalls shall each be 8 inches (203 mm) of solid masonry, including the
lining. The width of joints between firebricks shall not be greater
than1/4 inch ( 6.4 mm). Where a lining is not
provided, the total minimum thickness of back and side walls shall be 10 inches
(254 mm) of solid masonry. Firebrick shall conform to ASTM C27 or C1261 and
shall be laid with medium-duty refractory mortar conforming to ASTM C199.
1001.5.1
Steel
fireplace units.
Installation of steel
fireplace units with solid masonry to form a masonry fireplace is permitted
where installed either in accordance with the requirements of their listing or
the requirements of this section. Steel fireplace units incorporating a steel
firebox lining shall be constructed with steel not less
than1/4 inch ( 6.4 mm) thick, and an air-circulating
chamber that is ducted to the interior of the building. The firebox lining
shall be encased with solid masonry to provide a total thickness at the back
and sides of not less than 8 inches (203 mm), of which not less than 4 inches
(102 mm) shall be of solid masonry or concrete. Circulating air ducts used with
steel fireplace units shall be constructed of metal or masonry.
1001.6
Firebox dimensions.
The
firebox of a concrete or masonry fireplace shall have a depth of not less than
20 inches (508 mm). The throat shall be not less than 8 inches (203 mm) above
the fireplace opening. The throat opening shall be not less than 4 inches (102
mm) deep. The cross-sectional area of the passageway above the firebox,
including the throat, damper and smoke chamber, shall be not less than the
cross-sectional area of the flue.
Exception:
Rumford fireplaces shall be permitted provided that the
depth of the fireplace is not less than 12 inches (305 mm) and not less than
one-third of the width of the fireplace opening, that the throat is not less
than 12 inches (305 mm) above the lintel and is not less than one-twentieth the
cross-sectional area of the fireplace opening.
1001.7
Lintel
and throat.
Masonry over a fireplace
opening shall be supported by a lintel of noncombustible material. The minimum
required bearing length on each end of the fireplace opening shall be 4 inches
(102 mm). The fireplace throat or damper shall be located not less than 8
inches (203 mm) above the lintel.
1001.7.1
Damper.
Masonry
fireplaces shall be equipped with a ferrous metal damper located not less than
8 inches (203 mm) above the top of the fireplace opening. Dampers shall be
installed in the fireplace or the chimney venting the fireplace, and shall be
operable from the room containing the fireplace.
1001.8
Smoke
chamber.
Smoke chamber walls shall be
constructed of solid masonry units, hollow masonry units grouted solid, stone
or concrete. The total minimum thickness of front, back and side walls shall be
8 inches (203 mm) of solid masonry. The inside surface shall be parged smooth
with refractory mortar conforming to ASTM C199. Where a lining of firebrick not
less than 2 inches (51 mm) thick, or a lining of vitrified clay not less
than5/8 -inch (16 mm) thick, is provided, the total
minimum thickness of front, back and side walls shall be 6 inches (152 mm) of
solid masonry, including the lining. Firebrick shall conform to ASTM C1261 and
shall be laid with medium-duty refractory mortar conforming to ASTM C199.
Vitrified clay linings shall conform to ASTM C315.
1001.8.1
Smoke
chamber dimensions.
The inside height of
the smoke chamber from the fireplace throat to the beginning of the flue shall
not be greater than the inside width of the fireplace opening. The inside
surface of the smoke chamber shall not be inclined more than 45 degrees ( 0.79
rad) from vertical where prefabricated smoke chamber linings are used or where
the smoke chamber walls are rolled or sloped rather than corbeled. Where the
inside surface of the smoke chamber is formed by corbeled masonry, the walls
shall not be corbeled more than 30 degrees ( 0.52 rad) from
vertical.
1001.9
Hearth and hearth extension.
Masonry fireplace hearths and hearth extensions shall
be constructed of concrete or masonry, supported by noncombustible materials,
and reinforced to carry their own weight and all imposed loads. Combustible
material shall not remain against the underside of hearths and hearth
extensions after construction.
1001.9.1
Hearth thickness.
The minimum thickness of fireplace hearths shall be 4
inches (102 mm).
1001.9.2
Hearth extension thickness.
The minimum thickness of hearth extensions shall be 2
inches (51 mm).
Exception:
Where the bottom of the firebox opening is raised not
less than 8 inches (203 mm) above the top of the hearth extension, a hearth
extension of not less than3/8-inch-thick (10 mm)
brick, concrete, stone, tile or other approved noncombustible material is
permitted.
1001.10
Hearth
extension dimensions.
Hearth extensions
shall extend not less than 16 inches (406 mm) in front of and not less than 8
inches (203 mm) beyond each side of the fireplace opening. Where the fireplace
opening is 6 square feet ( 0.6 m2) or larger, the
hearth extension shall extend not less than 20 inches (508 mm) in front of and
not less than 12 inches (305 mm) beyond each side of the fireplace
opening.
1001.11
Fireplace clearance.
Wood beams, joists, studs and other combustible material
shall have a clearance of not less than 2 inches (51 mm) from the front faces
and sides of masonry fireplaces and not less than 4 inches (102 mm) from the
back faces of masonry fireplaces. The airspace shall not be filled, except to
provide fireblocking in accordance with Section 1001.12.
Exceptions:
1.
Masonry fireplaces
listed and labeled for use in contact with combustibles in accordance with UL
127 and installed in accordance with the manufacturer's instructions are
permitted to have combustible material in contact with their exterior
surfaces.
2.
Where masonry fireplaces are part of masonry or
concrete walls, combustible materials shall not be in contact with the masonry
or concrete walls less than 12 inches (306 mm) from the inside surface of the
nearest firebox lining.
3.
Exposed combustible trim and the edges of sheathing
materials such as wood siding, flooring and gypsum board shall be permitted to
abut the masonry fireplace sidewalls and hearth extension in accordance with
Figure 1001.11, provided such combustible trim or sheathing is not less than 12
inches (305 mm) from the inside surface of the nearest firebox
lining.
4.
Exposed combustible mantels or trim is permitted to be
placed directly on the masonry fireplace front surrounding the fireplace
opening providing such combustible materials are not placed within 6 inches
(152 mm) of a fireplace opening. Combustible material within 12 inches (306 mm)
of the fireplace opening shall not project more
than1/8 -inch (3 mm) for each 1-inch (25 mm)
distance from such an opening.
Click to
view image
For SI: 1 inch = 25.4 mm.
FIGURE 1001.11
CLEARANCE FROM
COMBUSTIBLES
1001.12
Fireplace fireblocking.
Fireplace fireblocking shall comply with the provisions of
Section 602.8.
SECTION
1002
MASONRY HEATERS
1002.1
Definition.
A masonry
heater is a heating appliance constructed of concrete or solid masonry,
hereinafter referred to as masonry, that is designed to absorb and store heat
from a solid-fuel fire built in the firebox by routing the exhaust gases
through internal heat exchange channels in which the flow path downstream of
the firebox includes flow in a horizontal or downward direction before entering
the chimney and that delivers heat by radiation from the masonry surface of the
heater.
1002.2
Installation.
Masonry
heaters shall be installed in accordance with this section and comply with one
of the following:
1.
Masonry heaters shall comply with the requirements of
ASTM E1602.
2.
Masonry heaters shall be listed and labeled in
accordance with UL 1482 or CEN 15250 and installed in accordance with the
manufacturer's instructions.
1002.3
Footings
and foundation.
The firebox floor of a
masonry heater shall be a minimum thickness of 4 inches (102 mm) of
noncombustible material and be supported on a noncombustible footing and
foundation in accordance with Section 1003.2.
1002.4
Seismic
reinforcing.Deleted.
1002.5
Masonry
heater clearance.
Combustible materials
shall not be placed within 36 inches (914 mm) of the outside surface of a
masonry heater in accordance with NFPA 211 Section 8-7 (clearances for
solid-fuel-burning appliances), and the required space between the heater and
combustible material shall be fully vented to permit the free flow of air
around all heater surfaces.
Exceptions:
1.
Where the masonry
heater wall is not less than 8 inches (203 mm) thick of solid masonry and the
wall of the heat exchange channels is not less than 5 inches (127 mm) thick of
solid masonry, combustible materials shall not be placed within 4 inches (102
mm) of the outside surface of a masonry heater. A clearance of not less than 8
inches (203 mm) shall be provided between the gas-tight capping slab of the
heater and a combustible ceiling.
2.
Masonry heaters
listed and labeled in accordance with UL 1482 or CEN 15250 shall be installed
in accordance with the listing specifications and the manufacturer's written
instructions.
SECTION
1003
MASONRY CHIMNEYS
1003.1
Definition.
A masonry
chimney is a chimney constructed of solid masonry units, hollow masonry units
grouted solid, stone or concrete, hereinafter referred to as masonry. Masonry
chimneys shall be constructed, anchored, supported and reinforced as required
in this chapter.
1003.2
Footings and foundations.
Footings for masonry chimneys shall be constructed of
concrete or solid masonry not less than 12 inches (305 mm) thick and shall
extend not less than 6 inches (152 mm) beyond the face of the foundation or
support wall on all sides. Footings shall be founded on natural undisturbed
earth or engineered fill below frost depth. In areas not subjected to freezing,
footings shall be not less than 12 inches (305 mm) below finished
grade.
1003.3
Seismic reinforcing.
In
Seismic Design Category A, B or C, reinforcement and seismic anchorage are not
required.
1003.3.1
Vertical reinforcing.Deleted.
1003.3.2
Horizontal
reinforcing.Deleted.
1003.4
Seismic
anchorage.Deleted
1003.4.1
Anchorage.Deleted
1003.4.1.1
Cold-formed steel framing.Deleted
1003.5
Corbeling.
Masonry
chimneys shall not be corbeled more than one-half of the chimney's wall
thickness from a wall or foundation, nor shall a chimney be corbeled from a
wall or foundation that is less than 12 inches (305 mm) thick unless it
projects equally on each side of the wall, except that on the second story of a
two-story dwelling, corbeling of chimneys on the exterior of the enclosing
walls shall be permitted to be equal to the wall thickness. The projection of a
single course shall not exceed one-half the unit height or one-third of the
unit bed depth, whichever is less.
1003.6
Changes
in dimension.
The chimney wall or chimney
flue lining shall not change in size or shape within 6 inches (152 mm) above or
below where the chimney passes through floor components, ceiling components or
roof components.
1003.7
Offsets.
Where a masonry chimney is constructed with a fireclay flue
liner surrounded by one wythe of masonry, the maximum offset shall be such that
the centerline of the flue above the offset does not extend beyond the center
of the chimney wall below the offset. Where the chimney offset is supported by
masonry below the offset in an approved manner, the maximum offset limitations
shall not apply. Each individual corbeled masonry course of the offset shall
not exceed the projection limitations specified in Section
1003.5.
1003.8
Additional load.
Chimneys shall not support loads other than their own weight
unless they are designed and constructed to support the additional load.
Construction of masonry chimneys as part of the masonry walls or reinforced
concrete walls of the building shall be permitted.
1003.9
Termination.
Chimneys
shall extend not less than 2 feet (610 mm) higher than any portion of a
building within 10 feet (3048 mm), but shall be not less than 3 feet (914 mm)
above the highest point where the chimney passes through the roof.
1003.9.1
Chimney caps.
Masonry
chimneys shall have a concrete, metal or stone cap, a drip edge and a caulked
bond break around any flue liners in accordance with ASTM C1283. The concrete,
metal or stone cap shall be sloped to shed water.
1003.9.2
Spark
arrestors.
Where a spark arrestor is
installed on a masonry chimney, the spark arrestor shall meet all of the
following requirements:
1.
The net free area of the arrestor shall be not less
than four times the net free area of the outlet of the chimney flue it
serves.
2.
The arrestor screen shall have heat and corrosion
resistance equivalent to 19-gage galvanized steel or 24-gage stainless
steel.
3.
Openings shall not permit the passage of spheres having
a diameter greater than1/2 inch ( 12.7 mm) nor block
the passage of spheres having a diameter less
than3/8 inch ( 9.5 mm).
4.
The spark arrestor
shall be located with access for cleaning and the screen or chimney cap shall
be removable to allow for cleaning of the chimney flue.
1003.9.3
Rain caps.
Where a
masonry or metal rain cap is installed on a masonry chimney, the net free area
under the cap shall be not less than four times the net free area of the outlet
of the chimney flue it serves.
1003.10
Wall
thickness.
Masonry chimney walls shall be
constructed of solid masonry units or hollow masonry units grouted solid with
not less than a 4-inch (102 mm) nominal thickness.
1003.10.1
Masonry veneer chimneys.
Where masonry is used to veneer a frame chimney,
through-flashing and weep holes shall be installed as required by Section
703.
1003.11
Flue lining (material).
Masonry chimneys shall be lined. The lining material
shall be appropriate for the type of appliance connected, in accordance with
the terms of the appliance listing and manufacturer's instructions.
1003.11.1
Residential-type appliances (general).
Flue lining systems shall comply with one of the
following:
1.
Clay flue lining complying with the requirements of ASTM
C315.
2.
Listed and labeled chimney lining systems complying
with UL 1777.
3.
Factory-built chimneys or chimney units listed for
installation within masonry chimneys.
4.
Other approved
materials that will resist corrosion, erosion, softening or cracking from flue
gases and condensate at temperatures up to 1,800°F
(982°C).
1003.11.2
Flue
linings for specific appliances.
Flue
linings other than these covered in Section 1003.11.1, intended for use with
specific types of appliances, shall comply with Sections 1003.11.3 through
1003.11.6.
1003.11.3
Gas appliances.
Flue lining systems for gas appliances shall be in
accordance with Chapter 24.
1003.11.4
Pellet fuel-burning appliances.
Flue lining and vent systems for use in masonry
chimneys with pellet fuel-burning appliances shall be limited to the
following:
1.
Flue lining systems complying with Section
1003.11.1.
2.
Pellet vents listed for installation within masonry
chimneys (see Section 1003.11.6 for marking).
1003.11.5
Oil-fired appliances approved for use with Type L
vent.
Flue lining and vent systems for use
in masonry chimneys with oil-fired appliances approved for use with Type L vent
shall be limited to the following:
1.
Flue lining systems complying with Section
1003.11.1.
2.
Listed chimney liners complying with UL 641 (see
Section 1003.11.6 for marking).
1003.11.6
Notice of usage.
Where
a flue is relined with a material not complying with Section 1003.11.1, the
chimney shall be plainly and permanently identified by a label attached to a
wall, ceiling or other conspicuous location adjacent to where the connector
enters the chimney. The label shall include the following message or equivalent
language:
THIS CHIMNEY FLUE IS FOR USE ONLY WITH [Type or
category of appliance] APPLIANCES THAT BURN [Type of fuel]. DO NOT CONNECT
OTHER TYPES OF APPLIANCES.
1003.12
Clay
flue lining (installation).
Clay flue
liners shall be installed in accordance with ASTM C1283 and extend from a point
not less than 8 inches (203 mm) below the lowest inlet or, in the case of
fireplaces, from the top of the smoke chamber to a point above the enclosing
walls. The lining shall be carried up vertically, with a slope not greater than
30 degrees ( 0.52 rad) from the vertical.
Clay flue liners shall be laid in medium-duty
water insoluble refractory mortar conforming to ASTM C199 with tight mortar
joints left smooth on the inside and installed to maintain an airspace or
insulation not to exceed the thickness of the flue liner separating the flue
liners from the interior face of the chimney masonry walls. Flue liners shall
be supported on all sides. Only enough mortar shall be placed to make the joint
and hold the liners in position.
1003.12.1
Listed materials.
Listed materials used as flue linings shall be installed in
accordance with the terms of their listings and manufacturer's
instructions.
1003.12.2
Space around lining.
The space surrounding a chimney lining system or vent
installed within a masonry chimney shall not be used to vent any other
appliance.
Exception:
This shall not prevent the installation of a separate
flue lining in accordance with the manufacturer's instructions.
1003.13
Multiple flues.
Where
two or more flues are located in the same chimney, masonry wythes shall be
built between adjacent flue linings. The masonry wythes shall be not less than
4 inches (102 mm) thick and bonded into the walls of the chimney.
Exception:
Where venting only one appliance, two flues shall be
permitted to adjoin each other in the same chimney with only the flue lining
separation between them. The joints of the adjacent flue linings shall be
staggered not less than 4 inches (102 mm).
1003.14
Flue
area (appliance).
Chimney flues shall not
be smaller in area than that of the area of the connector from the appliance
[see Tables 1003.14(1) and 1003.14(2) ]. The sizing of a chimney flue to which
multiple appliance venting systems are connected shall be in accordance with
Section 1805.3.
TABLE 1003.14(1)
NET CROSS-SECTIONAL AREA OF ROUND FLUE
SIZESa
FLUE SIZE, INSIDE DIAMETER
(inches)
|
CROSS-SECTIONAL AREA (square
inches)
|
6
|
28
|
7
|
38
|
8
|
50
|
10
|
78
|
103/4
|
90
|
12
|
113
|
15
|
176
|
18
|
254
|
For SI: 1 inch = 25.4 mm, 1 square inch =
645.16 mm2.
a. Flue sizes are based on ASTM C315.
TABLE 1003.14(2)
NET CROSS-SECTIONAL AREA
OF
SQUARE AND RECTANGULAR FLUE
SIZES
FLUE SIZE, OUTSIDE NOMINAL
DIMENSIONS (inches)
|
CROSS-SECTIONAL AREA (square
inches)
|
4.5 × 8.5
|
23
|
4.5 × 13
|
34
|
8 × 8
|
42
|
8.5 × 8.5
|
49
|
8 × 12
|
67
|
8.5 × 13
|
76
|
12 × 12
|
102
|
8.5 × 18
|
101
|
13 × 13
|
127
|
12 × 16
|
131
|
13 × 18
|
173
|
16 × 16
|
181
|
16 × 20
|
222
|
18 × 18
|
233
|
20 × 20
|
298
|
20 × 24
|
335
|
24 × 24
|
431
|
For SI: 1 inch = 25.4 mm, 1 square inch =
645.16 mm2.
1003.15
Flue
area (masonry fireplace).
Flue sizing for
chimneys serving fireplaces shall be in accordance with Section 1003.15.1 or
1003.15.2.
1003.15.1
Option 1.
Round chimney
flues shall have a minimum net cross-sectional area of not less than
one-twelfth of the fireplace opening. Square chimney flues shall have a minimum
net cross-sectional area of one-tenth of the fireplace opening. Rectangular
chimney flues with an aspect ratio less than 2 to 1 shall have a minimum net
cross-sectional area of one-tenth of the fireplace opening. Rectangular chimney
flues with an aspect ratio of 2 to 1 or more shall have a minimum net
cross-sectional area of one-eighth of the fireplace opening. Cross-sectional
areas of clay flue linings are shown in Tables 1003.14(1) and 1003.14(2) or as
provided by the manufacturer or as measured in the field.
1003.15.2
Option 2.
The minimum
net cross-sectional area of the chimney flue shall be determined in accordance
with Figure 1003.15.2. A flue size providing not less than the equivalent net
cross-sectional area shall be used. Cross-sectional areas of clay flue linings
are shown in Tables 1003.14(1) and 1003.14(2) or as provided by the
manufacturer or as measured in the field. The height of the chimney shall be
measured from the firebox floor to the top of the chimney flue.
Click to
view image
For SI: 1 foot = 304.8 mm, 1 square inch =
645.16 mm2.
FIGURE 1003.15.2
FLUE SIZES FOR MASONRY
CHIMNEYS
1003.16
Inlet.
Inlets to masonry chimneys shall enter
from the side. Inlets shall have a thimble of fireclay, rigid refractory
material or metal that will prevent the connector from pulling out of the inlet
or from extending beyond the wall of the liner.
1003.17
Masonry
chimney cleanout openings.
Cleanout
openings shall be provided within 6 inches (152 mm) of the base of each flue
within every masonry chimney. The upper edge of the cleanout shall be located
not less than 6 inches (152 mm) below the lowest chimney inlet opening. The
height of the opening shall be not less than 6 inches (152 mm). The cleanout
shall be provided with a noncombustible cover.
Exception:
Chimney flues serving masonry fireplaces where cleaning
is possible through the fireplace opening.
1003.18
Chimney
clearances.
Any portion of a masonry
chimney located in the interior of the building or within the exterior wall of
the building shall have a minimum airspace clearance to combustibles of 2
inches (51 mm). Chimneys located entirely outside the exterior walls of the
building, including chimneys that pass through the soffit or cornice, shall
have a minimum airspace clearance of 1 inch (25 mm). The airspace shall not be
filled, except to provide fire blocking in accordance with Section
1003.19.
Exceptions:
1.
Masonry chimneys
equipped with a chimney lining system listed and labeled for use in chimneys in
contact with combustibles in accordance with UL 1777 and installed in
accordance with the manufacturer's instructions are permitted to have
combustible material in contact with their exterior surfaces.
2.
Where masonry
chimneys are constructed as part of masonry or concrete walls, combustible
materials shall not be in contact with the masonry or concrete wall less than
12 inches (305 mm) from the inside surface of the nearest flue
lining.
3.
Exposed combustible trim and the edges of sheathing
materials, such as wood siding and flooring, shall be permitted to abut the
masonry chimney side walls, in accordance with Figure 1003.18, provided such
combustible trim or sheathing is not less than 8 inches (203 mm) from the
inside surface of the nearest flue lining.
Click to
view image
For SI: 1 inch = 25.4 mm.
FIGURE 1003.18
CLEARANCE FROM
COMBUSTIBLES
1003.19
Chimney
fireblocking.
Spaces between chimneys and
floors and ceilings through which chimneys pass shall be fireblocked with
noncombustible material securely fastened in place. The fireblocking of spaces
between chimneys and wood joists, beams or headers shall be self-supporting or
be placed on strips of metal or metal lath laid across the spaces between
combustible material and the chimney.
1003.20
Chimney
crickets.
Chimneys shall be provided with
crickets where the dimension parallel to the ridgeline is greater than 30
inches (762 mm) and does not intersect the ridgeline. The intersection of the
cricket and the chimney shall be flashed and counterflashed in the same manner
as normal roof-chimney intersections. Crickets shall be constructed in
compliance with Figure 1003.20 and Table 1003.20.
TABLE 1003.20
CRICKET DIMENSIONS
ROOF SLOPE
|
H
|
12:12
|
1/2 of
W
|
8:12
|
1/3 of
W
|
6:12
|
1/4 of
W
|
4:12
|
1/6 of
W
|
3:12
|
1/8 of
W
|
Click to
view image
FIGURE 1003.20
CHIMNEY CRICKET
SECTION 1004
FACTORY-BUILT
FIREPLACES
1004.1
General.
Factory-built fireplaces shall be listed and labeled and
shall be installed in accordance with the conditions of the listing.
Factory-built fireplaces shall be tested in accordance with UL
127.
1004.2
Hearth extensions.
Hearth extensions of approved factory-built fireplaces shall
be installed in accordance with the listing of the fireplace. The hearth
extension shall be readily distinguishable from the surrounding floor area.
Listed and labeled hearth extensions shall comply with UL 1618.
1004.3
Decorative shrouds.
Decorative shrouds shall not be installed at the termination
of chimneys for factory-built fireplaces except where the shrouds are listed
and labeled for use with the specific factory-built fireplace system and
installed in accordance with the manufacturer's instructions.
1004.4
Unvented
gas log heaters.
An unvented gas log
heater shall not be installed in a factory-built fireplace unless the fireplace
system has been specifically tested, listed and labeled for such use in
accordance with UL 127.
1004.5
Gasketed
fireplace doors.
A gasketed fireplace door
shall not be installed on a factory-built fireplace except where the fireplace
system has been specifically tested, listed and labeled for such use in
accordance with UL 127.
SECTION
1005
FACTORY-BUILT
CHIMNEYS
1005.1
Listing.
Factory-built
chimneys shall be listed and labeled and shall be installed and terminated in
accordance with the manufacturer's installation instructions.
1005.2
Decorative shrouds.
Decorative shrouds shall not be installed at the termination
of factory-built chimneys except where the shrouds are listed and labeled for
use with the specific factory-built chimney system and installed in accordance
with the manufacturer's installation instructions.
1005.3
Solid-fuel appliances.
Factory-built chimneys installed in dwelling units with
solid-fuel-burning appliances shall comply with the Type HT requirements of UL
103 and shall be marked "Type HT and "Residential Type and Building Heating
Appliance Chimney."
Exception:
Chimneys for use with open combustion chamber
fireplaces shall comply with the requirements of UL 103 and shall be marked
"Residential Type and Building Heating Appliance Chimney."
Chimneys for use with open combustion chamber
appliances installed in buildings other than dwelling units shall comply with
the requirements of UL 103 and shall be marked "Building Heating Appliance
Chimney" or "Residential Type and Building Heating Appliance
Chimney."
1005.4
Factory-built fireplaces.
Chimneys for use with factory-built fireplaces shall
comply with the requirements of UL 127.
1005.5
Support.
Where
factory-built chimneys are supported by structural members, such as joists and
rafters, those members shall be designed to support the additional
load.
1005.6
Medium-heat appliances.
Factory-built chimneys for medium-heat appliances producing
flue gases having a temperature above 1,000°F (538°C), measured at the
entrance to the chimney, shall comply with UL 959.
1005.7
Factory-built chimney offsets.
Where a factory-built chimney assembly incorporates
offsets, no part of the chimney shall be at an angle of more than 30 degrees (
0.52 rad) from vertical at any point in the assembly and the chimney assembly
shall not include more than four elbows.
1005.8
Insulation shield.
Where factory-built chimneys pass through insulated
assemblies, an insulation shield constructed of steel having a thickness of not
less than 0.0187 inch ( 0.4712 mm) (No. 26 gage) shall be installed to provide
clearance between the chimney and the insulation material. The clearance shall
be not less than the clearance to combustibles specified by the chimney
manufacturer's installation instructions. Where chimneys pass through attic
space, the shield shall terminate not less than 2 inches (51 mm) above the
insulation materials and shall be secured in place to prevent displacement.
Insulation shields provided as part of a listed chimney system shall be
installed in accordance with the manufacturer's installation
instructions.
SECTION
1006
EXTERIOR AIR SUPPLY
1006.1
Exterior
air.
Factory-built or masonry fireplaces
covered in this chapter shall be equipped with an exterior air supply to ensure
proper fuel combustion unless the room is mechanically ventilated and
controlled so that the indoor pressure is neutral or positive.
1006.1.1
Factory-built fireplaces.
Exterior combustion air ducts for factory-built
fireplaces shall be a listed component of the fireplace and shall be installed
in accordance with the fireplace manufacturer's instructions.
1006.1.2
Masonry fireplaces.
Listed combustion air ducts for masonry fireplaces shall be
installed in accordance with the terms of their listing and the manufacturer's
instructions.
1006.2
Exterior
air intake.
The exterior air intake shall
be capable of supplying all combustion air from the exterior of the dwelling or
from spaces within the dwelling ventilated with outdoor air such as
nonmechanically ventilated crawl or attic spaces. The exterior air intake shall
not be located within the garage or basement of the dwelling. The exterior air
intake, for other than listed factory-built fireplaces, shall not be located at
an elevation higher than the firebox. The exterior air intake shall be covered
with a corrosion-resistant screen of1/4-inch ( 6.4
mm) mesh.
1006.3
Clearance.
Unlisted
combustion air ducts shall be installed with a minimum 1-inch (25 mm) clearance
to combustibles for all parts of the duct within 5 feet (1524 mm) of the duct
outlet.
1006.4
Passageway.
The
combustion air passageway shall be not less than 6 square inches (3870
mm2) and not more than 55 square inches ( 0.035
m2), except that combustion air systems for listed
fireplaces shall be constructed in accordance with the fireplace manufacturer's
instructions.
1006.5
Outlet.
The
exterior air outlet shall be located in the back or side of the firebox chamber
or shall be located outside of the firebox, at the level of the hearth and not
greater than 24 inches (610 mm) from the firebox opening. The outlet shall be
closable and designed to prevent burning material from dropping into concealed
combustible spaces.
Replaces: 4101:8-10-01