Section 3750-75-03 - Criteria for the construction of an emergency response lock box unit
Current through all regulations passed and filed through March 18, 2024
[Comment: For dates of non-regulatory government publications, publications of recognized organizations and associations, federal rules, and federal statutory provisions referenced in this rule, see the "Incorporation by Reference" section at the end rule 3750-1-01.]
(A) All emergency response lock box units shall be constructed to meet the following minimum criteria:
Note: Materials tested in accordance with ASTM E136 Standard Test Method for Behavior of Materials in a Verticle Tube Furnace at 750 degrees C and conforming to the criteria contained in section 7 of NFPA 101, the Life Safety Code, shall be considered noncombustible.
(B) The construction of key boxes is not regulated under Chapter 3750-75 of the Administrative Code.