Ohio Administrative Code
Title 3745 - Ohio Environmental Protection Agency
Chapter 3745-266 - Disposal Standards
Section 3745-266-105 - Standards to control particulate matter
Current through all regulations passed and filed through December 16, 2024
(A) A boiler or industrial furnace burning hazardous waste may not emit particulate matter in excess of one hundred eighty milligrams per dry standard cubic meter (0.08 grains per dry standard cubic foot) after correction to a stack gas concentration of seven per cent oxygen, using procedures prescribed in 40 CFR Part 60, appendix A, methods 1 to 5, and the appendix to rule 3745-266-103 of the Administrative Code.
(B) An owner or operator in compliance with paragraph (B) of rule 3745-266-109 of the Administrative Code for the low risk waste exemption is exempt from the particulate matter standard.
(C) Oxygen correction.
Pc = Pm x 14 / (E - Y)
where:
Pc is the corrected concentration of the pollutant in the stack gas.
Pm is the measured concentration of the pollutant in the stack gas.
E is the oxygen concentration on a dry basis in the combustion air fed to the device.
Y is the measured oxygen concentration on a dry basis in the stack.
(D) For the purposes of permit enforcement, compliance with the operating requirements specified in the permit (under rule 3745-266-102 of the Administrative Code) are regarded as compliance with this rule. However, evidence that compliance with those permit conditions is insufficient to ensure compliance with this rule may be information justifying modification of a permit under rule 3745-50-51 of the Administrative Code.
[Comment: For dates of non-regulatory government publications, publications of recognized organizations and associations, federal rules, and federal statutory provisions referenced in this rule, see rule 3745-50-11 of the Administrative Code titled "Incorporated by reference."]