Current through all regulations passed and filed through September 16, 2024
[Comment: For dates and availability of non-regulatory
government publications, publications of recognized organizations and
associations, federal rules, and federal statutory provisions referenced in
this rule, see paragraph (JJ) of rule
3745-21-01 of the Administrative
Code titled "referenced materials."]
(A)
Rule applicability.
(1) Except as otherwise
provided in paragraph (A)(2) of this rule, this rule shall apply to any reactor
or distillation unit in a process unit that meets both of the following
criteria:
(a) The process unit is located in
Ashtabula, Butler, Clermont, Cuyahoga, Geauga, Hamilton, Lake, Lorain, Medina,
Portage, Summit, or Warren county.
(b) The
process unit produces a SOCMI chemical.
(2) Excluded from this rule are the following:
(a) Any reactor or distillation unit that is
a batch operation.
(b) Any reactor
or distillation unit that is regulated by paragraph (CC) or (EE) of rule
3745-21-09 of the Administrative
Code.
(c) Any reactor or
distillation unit included within an "early reduction program," as specified in
40 CFR part 63, and published in 57 Federal Register 61970 (December 29, 1992),
evidenced by a timely enforceable commitment approved by USEPA.
(d) Any reactor regulated by subpart III or
subpart RRR of 40 CFR part 60 .
(e)
Any distillation unit regulated by subpart NNN of 40 CFR part
60.
(3) For the purposes
of paragraph (A)(2) of this rule, a reactor or distillation unit shall be
considered regulated by a paragraph, rule or subpart if
the reactor or
distillation unit is subject to the limits of that paragraph, rule, or
subpart. A reactor or distillation unit is not considered regulated by a
paragraph, rule, or subpart if the reactor or distillation unit is not subject to the
limits of that paragraph, rule, or subpart. For example, if the reactor or
distillation unit is covered by an exemption in the paragraph, rule, or
subpart, or the applicability criteria of the paragraph or subpart are not met,
then the source is not subject to that paragraph, rule, or
subpart.
(B) Definitions.
The definitions applicable to this rule are contained in
paragraphs (B) and (V) of rule
3745-21-01 of the Administrative
Code.
(C) Overall
requirements for reactors and distillation units.
(1) Except where exempted under paragraph
(C)(2) of this rule, the owner or operator of a reactor or distillation unit
subject to this rule shall comply with paragraphs (D) to (L) of this rule.
(2) Exempted from paragraph (C)(1) of this rule
is any reactor or distillation unit in a process unit with a total design
capacity for all chemicals produced within that unit of less than one thousand
one hundred tons per year. However, such reactor or distillation unit remains
subject to the recordkeeping and reporting requirements contained in paragraphs
(J)(1)(f) and (L)(1) of this rule.
(D) Determination of group status and halogen
status for process vents of reactors and distillation units.
(1) (Group status) The owner or operator of a
reactor or distillation unit shall determine the group status (i.e., group 1,
group 2A, or group 2B) for each process vent based on flow rate, VOC
concentration, and TRE index value in accordance with paragraphs (D)(3) to
(D)(5) of this rule and the procedures contained in paragraph (E) of this rule.
Group 1 process vents require control for VOC, and group 2A and group 2B
process vents do not. Group 1 process vents require monitoring of control
devices, except for boilers or process heaters specified under paragraphs
(F)(1)(b) and (F)(1)(c) of this rule, and require monitoring of bypass lines.
Group 2A process vents require monitoring of the associated recovery systems,
and group 2B process vents do not require any monitoring.
(2) (Halogen status) The owner or operator of
a group 1 process vent which is controlled (or to be controlled) by a
combustion device shall determine the halogen status in accordance with the
procedures specified in paragraph (E)(7) of this rule.
Group 1
process vents that are halogenated process vents being discharged to a
combustion device require halogen reduction control (either a pre-combustion or
post-combustion).
(3) (Group 1) A
process vent shall be group 1 if it meets at least one of the following
specifications:
(a) The owner or operator
designates the process vent as group 1.
(b) At representative operating conditions
expected to yield the lowest TRE index value for the process vent, the TRE
index value is less than or equal to 1.0, the flow rate is equal to or greater
than 0.30 scfm, and the VOC concentration is equal to or greater than five
hundred ppmv.
(4) (Group
2A) A process vent shall be group 2A if it is from a recovery system and if, at
representative operating conditions expected to yield the lowest TRE index
value for the process vent, the TRE index value is greater than 1.0 and less
than or equal to 4.0, the flow rate is equal to or greater than 0.30 scfm, and
the VOC concentration is equal to or greater than five hundred ppmv.
(5) (Group 2B) A process vent shall be group
2B if it meets any one of the following specifications:
(a) The process vent has a flow rate less
than 0.30 scfm.
(b) The process
vent has a VOC concentration less than five hundred ppmv.
(c) The process vent is not from a recovery
system and, at representative operating conditions expected to yield the lowest
TRE index value for the process vent, the TRE index value is greater than
1.0.
(d) The process vent is from a
recovery system and, at representative operating conditions expected to yield
the lowest TRE index value for the process vent, the TRE index value is greater
than 4.0.
(6) Process
changes for group 2A and group 2B process vents.
Whenever process changes are made that could reasonably be
expected to change a group 2A or group 2B process vent to a group 1 process
vent, the owner or operator shall redetermine the flow rate, VOC concentration,
or TRE index value, according to paragraph (D)(6)(a), (D)(6)(b), or (D)(6)(c)
of this rule as specified for each process vent as necessary to determine
whether the process vent is group 1, group 2A, or group 2B. The owner or
operator shall perform the group status determination as soon as practical
after the process change and within sixty days after the process change.
Examples of process changes include, but are not limited to, changes in
production capacity, production rate, feedstock type, or catalyst type, or
whenever there is replacement, removal, or addition of recovery equipment. For
purposes of paragraph (D)(6) of this rule, process changes do not include
process upsets, unintentional, temporary process changes, and changes that are
within the range on which the original TRE index value calculation was
based.
(a) (Group 2B process vent
based on flow rate) The flow rate shall be redetermined by using the
measurement procedure in paragraph (E)(9) of this rule or by using an
engineering assessment of the effects of the change.
(b) (Group 2B process based on VOC
concentration) The VOC concentration shall be redetermined by using the
measurement procedure in paragraph (E)(10) of this rule or by using an
engineering assessment of the effects of the change.
(c) (Group 2B process vent based on TRE index
value or group 2A process vent) The TRE index value shall be redetermined
(recalculated) based on measurements of flow rate, net heating value, VOC
emission rate, and halogen status as specified in paragraphs (E)(9), (E)(11),
(E)(12), and (E)(13) of this rule, or based on an engineering assessment of the
effects of the change.
(E) Procedures for process vent
determinations.
(1) (General) The provisions
under paragraph (E) of this rule provide procedures for the determination of
process vent parameters that are used to determine the group status and halogen
status for a process vent.
(2)
Location within a process vent for determination of group status and halogen
status and for sampling.
(a) For the purpose
of determining group status of a process vent based on VOC concentration, flow
rate, or TRE index value, the location shall be representative of the process
vent stream after the last recovery device (if any recovery devices are
present) but prior to the inlet of any control device that is present, and
prior to release to the atmosphere. The process vent parameters for TRE index
value are flow rate, net heating value, VOC emission rate, and halogen
status.
(b) The location of the
sampling site for measurement of process vent parameters (flow rate, VOC
concentration, VOC emission rate, net heating value, and mass emission rate for
halogen atoms) shall be selected in accordance with paragraph (E)(2)(a) of this
rule and paragraph (C)(3)(f) of rule
3745-21-10 of the Administrative
Code. No traverse site selection method is needed for process vents smaller
than four inches ( 0.10 meter) in nominal inside diameter.
(3) The flow rate of a process vent shall be
determined by engineering assessment or by the measurement procedure of
paragraph (E)(9) of this rule.
(4)
The VOC concentration of a process vent shall be determined by engineering
assessment or by the measurement procedure of paragraph (E)(10) of this
rule.
(5) The net heating value of
a process vent shall be determined by engineering assessment or by the
measurement procedure of paragraph (E)(11) of this rule.
(6) The VOC and TOC emission rate of a
process vent shall be determined by engineering assessment or by the
measurement procedure of paragraph (E)(12) of this rule.
(7) The halogen status of a process vent
shall be determined by process knowledge that no halogen or hydrogen halides
are present in the process vent, by engineering assessment, or by the
measurement procedure of paragraph (E)(13) of this rule. If the mass emission
rate of halogen atoms for a process vent is equal to or greater than 0.99 pound
per hour, the process vent shall be classified as halogenated.
(8) Procedure for TRE index value.
The TRE index value of the process vent shall be determined as
follows:
(a) TRE index value for a process vent shall
be calculated by the following equation:
Click to
view image
where:
TRE = TRE index value.
Q = Process vent flow rate, standard cubic meters per minute,
at a standard temperature of 20 degrees Celsius, as determined under paragraph
(E)(3) of this rule by engineering assessment or measurement procedure.
H = Process vent net heating value, megajoules per standard
cubic meter, as determined under paragraph (E)(5) of this rule by engineering
assessment or measurement procedure.
EVOC = Process vent emission rate of
VOC, kilograms per hour, as determined under paragraph (E)(6) of this rule by
engineering assessment or measurement procedure.
ETOC = Process vent emission rate of
TOC, kilograms per hour, as determined under paragraph (E)(6) of this rule by
engineering assessment or measurement procedure.
a, b, c, and d = coefficients presented in table A of this
rule.
Table A: Coefficients for total
resource effectiveness for nonhalogenated and halogenated process vent
streams
Type of Process Vent
Stream |
Control Device Basis
a |
Values of
Coefficients |
a |
b |
c |
d |
Nonhalogenated |
Flare |
2.129 |
0.183 |
- 0.005 |
0.359 |
|
Thermal incinerator with zero
per cent heat recovery |
3.075 |
0.021 |
- 0.037 |
0.018 |
Thermal incinerator with
seventy per cent heat recovery |
3.803 |
0.032 |
- 0.042 |
0.007 |
Halogenated |
Thermal incinerator and
scrubber |
5.470 |
0.181 |
- 0.040 |
0.004 |
Click to
view image
(b)
For a nonhalogenated process vent stream, the owner or operator shall use the
applicable coefficients in table A to calculate the TRE index values based on a
flare, a thermal incinerator with zero heat recovery, and a thermal incinerator
with seventy per cent heat recovery, and shall select the lowest TRE index
value. For a halogenated process vent stream, the owner or operator shall use
the applicable coefficients in table A to calculate the TRE index value based
on a thermal incinerator and scrubber.
(c) If the TRE index value, as determined in
accordance with paragraphs (E)(8)(a) and (E)(8)(b) of this rule, is less than
or equal to 4.0, and such TRE index value is calculated using engineering
assessment for process vent flow rate, process vent net heating value, process
vent VOC emission rate, or process vent halogen status, then the owner or
operator shall either perform the measurement procedures specified in
paragraphs (E)(9), (E)(11), (E)(12), and (E)(13) of this rule for the
determination of the process vent's group status or designate the process vent
as a group 1 process vent.
(9) (Measurement procedure for flow rate) The
process vent volumetric flow rate in standard cubic meters per minute shall be
measured at a sampling site selected as specified in paragraph (E)(2)(b) of
this rule and by the appropriate method specified in paragraph (C)(3)(f) of
rule 3745-21-10 of the Administrative
Code. If the process vent stream passes through a final steam jet ejector and
is not condensed, the volumetric flow rate shall be corrected to 2.3 per cent
moisture.
(10) Measurement
procedure for VOC concentration.
(a) The
sampling site shall be selected as specified in paragraph (E)(2)(b) of this
rule.
(b) The methods and
procedures under paragraph (C) of rule
3745-21-10 of the Administrative
Code shall to be employed wherein USEPA method 18 or USEPA method 25A shall be
employed for VOC concentration.
(c)
If USEPA method 18 is employed, the following procedures shall be used:
(i) The minimum sampling time for each run
shall be one hour in which either an integrated sample or four grab samples
shall be taken. If grab sampling is used, then the samples shall be taken at
approximately equal intervals in time, such as fifteen-minute intervals during
the run.
(ii) The VOC concentration
(C) is the sum of the concentrations of the individual components and shall be
computed for each run by the following equation:
Click to
view image
where:
C = Concentration of VOC, dry basis, ppmv.
x = Number of samples in the sample run.
n = Number of components in the sample.
Cji = Concentration of sample component
j of the sample i, dry basis, ppmv.
(d) If USEPA method 25A is employed, the
following procedures shall be used:
(i) USEPA
method 25A shall be used only if a single organic compound of VOC is greater
than fifty per cent of the total VOC, by volume, in the process vent.
(ii) The process vent composition may be
determined by either process knowledge or test data collected using an
appropriate USEPA method. Examples of information that could constitute process
knowledge include calculations based on material balances, process
stoichiometry, or previous test results provided the results are still relevant
to the current process vent conditions.
(iii) The organic compound used as the
calibration gas for USEPA method 25A shall be the single organic compound of
VOC present at greater than fifty per cent of the total VOC by
volume.
(iv) The span value for
USEPA method 25A shall be equal to five hundred ppmv.
(v) Use of USEPA method 25A is acceptable if
the response from the high-level calibration gas is at least twenty times the
standard deviation of the response from the zero calibration gas when the
instrument is zeroed on the most sensitive scale.
(vi) The owner or operator shall demonstrate
that the total organic concentration measured by USEPA method 25A is below two
hundred fifty ppmv in order for the VOC concentration to be considered below
five hundred ppmv.
(11) (Measurement procedure for net heating
value) The net heating value of a vent stream shall be measured and calculated
in accordance with
40
CFR 63.115(d)(2)(ii) and
40
CFR 63.115(d)(2)
(iii).
(12) (Measurement procedure for TOC and VOC
emission rates) The TOC and VOC emission rates of a process vent shall be
determined in accordance with paragraph (C) of rule
3745-21-10 of the Administrative
Code and the following:
(a) The sampling site
shall be selected as specified in paragraph (E)(2)(b) of this rule.
(b) The minimum sampling time for each run
shall be one hour in which either an integrated sample or a minimum of four
grab samples shall be taken. If grab sampling is used, then the samples shall
be taken at approximately equal intervals in time such as fifteen-minute
intervals during the run.
(c) The
mass rates of TOC and VOC for each sample shall be calculated in accordance
with paragraph (C)(4) of rule
3745-21-10 of the Administrative
Code wherein all organic compounds measured by USEPA method 18 are used in the
calculation of the mass rate of TOC and only those organic compounds that are
VOC are used in the calculation of mass rate of VOC. The mass rates of TOC and
VOC for each run shall be the average of the mass rates of TOC and VOC of each
sample within that run.
(13) (Measurement procedure for mass emission
rate of halogen atoms) The mass emission rate of halogen atoms for a process
vent shall be measured based upon a sampling site selected as specified in
paragraph (E)(2)(b) of this rule, flow rate measured by the appropriate method
specified in paragraph (C)(3)(f) of rule
3745-21-10 of the Administrative
Code, and the halogen-related measurements and calculations specified in
40
CFR 63.115(d)(2)(v)(A)(3)
and
40
CFR
63.115(d)(2)(v)(B).
(F) Control and operational
requirements for process vents.
(1) For any
group 1 process vent, the owner or operator shall comply with
paragraph (F)(1)(a),
(F)(1)(b), (F)(1)(c), (F)(1)(d), (F)(1)(e), (F)(1)(f), or (F)(1)(h) of this
rule. If the group 1 process vent is a halogenated process vent that is
discharged to a combustion device, the owner or operator shall also comply with
paragraph (F)(1)(g) of
this rule.
(a) Discharge the group 1 process
vent to a flare that is designed and operated to meet
paragraph
(DD)(10)(d) of rule
3745-21-09 of the Administrative
Code.
(b) Discharge the group 1
process vent into the flame zone of a boiler or process heater with a heat
input capacity equal to or greater than one hundred fifty million Btu per
hour.
(c) Discharge the group 1
process vent to a boiler or process heater as the primary fuel or with the
primary fuel.
(d) Discharge the
group 1 process vent to a control device (boiler, process heater, incinerator
or recapture device) or combination of control devices that is designed and
operated to reduce VOC emissions from the group 1 process vent by at least
ninety-eight per cent or emit VOC at a concentration less than twenty ppmv, dry
basis, whichever is less stringent. For a combustion device, the concentration
of VOC shall be corrected to three per cent oxygen.
(e) For the group 1 process vent, achieve and
maintain a TRE index value greater than 1.0 at the outlet of the final recovery
device, or prior to release from the process vent to atmosphere if no recovery
device is present. If the TRE index value is greater than 1.0, the process vent
shall meet the requirements for a group 2A or group 2B process vent specified
in paragraph (F)(2) or (F)(3) of this rule, whichever is applicable.
(f) (Existing combustion device) Discharge
the group 1 process vent to a previously installed combustion device, provided
all of the following conditions are met:
(i)
The combustion device was installed prior to either of
the following:
(a)
May 27, 2005 if the facility is
located in Butler, Clermont, Hamilton, or Warren county.
(b)
August 25,
2008 if the facility is located in Ashtabula, Cuyahoga, Geauga, Lake,
Lorain, Medina, Portage, or Summit county.
(ii) The combustion device is not capable of
reliably reducing VOC emissions from the process vent in order to meet
paragraph (F)(1)(d) of
this rule.
(iii) The combustion
control shall reduce VOC emissions from the group 1 process vent by at least
ninety per cent by weight.
(iv) If
the combustion device is replaced with new control equipment for which
construction commenced on or after May 27, 2005 for facilities
located in Butler, Clermont, Hamilton, or Warren county or August 25, 2008 for
facilities located in Ashtabula, Cuyahoga, Geauga, Lake, Lorain, Medina,
Portage, or Summit county, the use of paragraph (F)(1)(f) of this rule
shall terminate for the group 1 process vent.
(g) A group 1 process vent that is a
halogenated process vent and that is discharged to a combustion device shall be
controlled with a halogen reduction device that meets paragraph (F)(1)(g)(i) or
(F)(1)(g)(ii) of this rule. However, if the combustion device is a flare, the
group 1 process vent shall be controlled with a halogen reduction device that
meets paragraph (F)(1)(g)(ii) of this rule.
(i) (Halogen reduction device following
combustion) A scrubber or other halogen reduction device that follows
combustion shall meet either of the following:
(a) Except as provided in paragraph
(F)(1)(g)(i)(b) of this rule, the scrubber or other halogen reduction device
shall reduce overall emissions of hydrogen halides and halogens by ninety-nine
per cent or shall reduce the outlet mass of total hydrogen halides and halogens
to less than 0.99 pound per hour, whichever is less stringent.
(b) If a scrubber or other halogen reduction
device was installed prior to May 27, 2005 for facilities located
in Butler, Clermont, Hamilton, or Warren county or August 25, 2008 for
facilities located in Ashtabula, Cuyahoga, Geauga, Lake, Lorain, Medina,
Portage, or Summit county, the scrubber or other halogen reduction device shall
reduce overall emissions of hydrogen halides and halogens by ninety-five per
cent or shall reduce the outlet mass of total hydrogen halides and halogens to
less than 0.99 pound per hour, whichever is less stringent.
(ii) (Halogen reduction
device prior to combustion) A halogen reduction device, such as a scrubber, or
other technique shall reduce the process vent's mass emission rate of halogen
atoms to less than 0.99 pound per hour prior to the combustion
device.
(h) (Off-site
control or onsite control not owned or operated by the owner or operator of the
source) Transfer the gas stream from group 1 process vent for disposal to an
onsite control device (or other compliance equipment) not owned or operated by
the owner or operator of the source (reactor or distillation unit) generating
the gas stream, or to an off-site control device or other compliance equipment,
provided the following conditions are met:
(i)
The owner or operator transferring the gas stream shall do the following:
(a) Comply with the provisions specified in
paragraph (H)(6) of this rule for each gas stream prior to transfer.
(b) Notify the transferee that the gas stream
contains VOC that are to be treated in accordance with the provisions of this
rule. The notice shall be submitted to the transferee initially and whenever
there is a change in the required control.
(ii) The owner or operator may not transfer
the gas stream unless the transferee has submitted to the director a written
certification that the transferee will manage and treat any gas stream
transferred under paragraph (F)(1)(h) of this rule and received from a source
(reactor or distillation unit) subject to this rule in accordance with
this rule. The
certifying entity may revoke the written certification by sending a written
statement to the director and the owner or operator giving at least ninety days
notice that the certifying entity is rescinding acceptance of responsibility
for compliance with the regulatory provisions of this rule. Upon expiration of
the notice period, the owner or operator may not transfer the gas stream to the
transferee. Records retained by the transferee shall be retained in accordance
with paragraph (J)(1) of this rule.
(iii) By providing this written certification
to the director, the certifying entity accepts responsibility for compliance
with the regulatory provisions listed in paragraph (F)(1)(h)(ii) of this rule
with respect to any transfer covered by the written certification. Failure to
abide by any of those provisions with respect to such transfers may result in
enforcement action by the director against the certifying entity.
(iv) Written certifications and revocation
statements to the director from the transferees of such gas streams shall be
signed by a responsible official of the certifying entity and provide the name
and address of the certifying entity. Such written certifications are not
transferable by the transferee.
(2) For any group 2A process vent, the owner
or operator shall maintain a TRE index value greater than 1.0
(3) For any group 2B process vent, the owner
or operator shall maintain a flow rate less than 0.30 scfm, or a VOC
concentration less than five hundred ppmv, or a TRE index value greater than
1.0 if the gas stream is not from a recovery system, or a TRE index value
greater than 4.0 if the gas stream is from a recovery system, whichever is the
basis for the group 2B status for that process vent.
(G) Compliance dates.
(1) Except where otherwise specified within
this rule, any owner or operator of a reactor or distillation unit that is
subject to this rule shall comply with this rule by no later than the following dates:
(a) For any reactor or distillation unit
located in Butler, Clermont, Hamilton, or Warren county for which installation
commenced before May 27, 2005, the compliance date of the reactor or
distillation unit is May 27, 2006.
(b) For any reactor or distillation unit
located in Butler, Clermont, Hamilton, or Warren county for which installation
commenced on or after May 27, 2005, the compliance date of the reactor or
distillation unit is the date of initial startup of the reactor or distillation
unit.
(c) For any reactor or
distillation unit located in Ashtabula, Cuyahoga, Geauga, Lake, Lorain, Medina,
Portage, or Summit county for which installation commenced before
August 25, 2008, the compliance date of the reactor or
distillation unit is August 25,
2009.
(d) For any reactor or
distillation unit located in Ashtabula, Cuyahoga, Geauga, Lake, Lorain, Medina,
Portage, or Summit county for which installation commenced on or after
August 25, 2008, the compliance date of the reactor or
distillation unit is the date of initial startup of the reactor or distillation
unit.
(2) In the event a
reactor or distillation unit has a group 1 process vent which is subject to
paragraph (F)(1)(f) of this rule and the group 1 process vent is later
discharged to a new control device, the compliance date of the process vent
pertaining to an applicable requirement under paragraph (F)(1) of this rule is
the date of first startup of the discharge of the process vent to the new
control device. Until that date of first startup, the group 1 process vent
shall continue to comply with paragraph (F)(1)(f) of this rule.
(3) If there is a change in group status due
to a process change, the owner or operator shall meet
one of the following:
(a) (Group status change to group 1) Where
the process change causes the group status to change to group 1, the owner or
operator shall comply with the group 1 process vent requirements in paragraph
(F)(1) of this rule upon initial startup after the change and thereafter unless
the owner or operator demonstrates to the director that achieving compliance
will take longer than making the process change. If this demonstration is made
to the director's satisfaction, the owner or operator shall comply as
expeditiously as practical, but in no event later than one year after the
process vent becomes a group 1 process vent, and shall comply with the
following procedures to establish a compliance date:
(i) The owner or operator shall submit to the
director for approval a compliance schedule, along with a justification for the
schedule.
(ii) The compliance
schedule shall be submitted with an application for a permit, or an application
for a modification of a permit, or by other means provided by theappropriate
Ohio EPA district office or local air agency.
(iii) The director shall approve the
compliance schedule or request changes within ninety calendar days of receipt
of the compliance schedule and justification for the schedule.
(b) (Group status change
to group 2A) Where the process change causes the process vent group status to
change to group 2A, the owner or operator shall comply with
paragraph (F)(2) of
this rule upon completion of the group status determination of the process
vent.
(c) (Group status change to
group 2B) Where the process change causes the process vent group status to
change to group 2B or causes the basis of a group 2B status to change, the
owner or operator shall comply with paragraph (F)(3) of this rule as soon as practical after the
process change.
(4) The
owner or operator of any reactor or distillation unit that has a group 1
process vent discharged to a flare that is designed and operated to meet
paragraph (F)(1)(a) of this rule, or discharged to a control device or
combination of control devices that is designed and operated to meet paragraph
(F)(1)(d) of this rule shall demonstrate compliance by conducting a compliance
test of the control or recovery devices in accordance with paragraph (I)
of this rule within ninety days after the compliance date.
(5) The owner or operator of any reactor or
distillation unit that has a group 1 process vent operated to meet paragraph
(F)(1)(e) of this rule or a group 2A process vent operated to meet paragraph
(F)(2) of this rule shall demonstrate compliance by conducting a TRE
determination test in accordance with paragraph (I) of this rule by the
compliance date.
(6) Additional
testing of the process vent, control device, or recovery device of a reactor or
distillation unit in accordance with paragraph (I) of this rule may be required
by the director to ensure continued compliance.
(H) Monitoring for group 1 and group 2A process
vents.
(1) For any flare used by a group 1
process vent to comply with paragraph (F)(1)(a) of this rule, the owner or
operator shall install, calibrate, maintain, and operate according to
manufacturer's specifications, a monitoring device (including but not limited
to a thermocouple, ultra-violet beam sensor, or infrared sensor) capable of
continuously detecting the presence of a flame.
(2) For any combustion device (boiler,
process heater, incinerator) used by a group 1 process vent to comply with
paragraph (F)(1)(d) or (F)(1)(g) of this rule, the owner or operator shall
install, calibrate, maintain, and operate according to manufacturer's
specifications, a temperature monitoring device equipped with a continuous
recorder. The temperature monitoring device shall be located as follows:
(a) Where a thermal incinerator is used, the
temperature monitoring device shall be located in the firebox or in the
ductwork immediately downstream of the firebox in a position before any
substantial heat exchange occurs.
(b) Where a catalytic incinerator is used,
one of the following:
(i)
Temperature
monitoring devices shall be located in the gas stream immediately before
(upstream) and after (downstream) the catalyst bed.
(ii)
If an owner or
operator elects to implement an inspection and maintenance plan for the
catalytic incinerator that meets paragraph (H)(9) of this rule, the temperature
monitoring device shall be located upstream of the catalyst bed
only.
(c) Where a
boiler or process heater is used, the temperature monitoring device shall be
located in the firebox. This requirement does not apply to process vent streams
that are introduced with the primary fuel or are used as the primary
fuel.
(3) For any
recapture device used by a group 1 process vent to comply with paragraph
(F)(1)(d) of this rule and for any final recovery device within a recovery
system used by a group 2A process vent to comply with paragraph (F)(2) of this
rule the owner or operator shall install, calibrate, maintain and operate
according to manufacturer's specifications, the following monitoring devices:
(a) Where an absorber is used,
the following:
(i) A temperature monitoring device equipped
with a continuous recorder shall be employed to monitor the exit temperature of
the absorbing liquid.
(ii) A
specific gravity monitoring device equipped with a continuous recorder shall be
employed to monitor the exit specific gravity of the absorbing
liquid.
(b) Where a
condenser is used, a temperature monitoring device equipped with a continuous
recorder shall be employed to monitor the exit (product side)
temperature.
(c) Where a carbon
adsorber is used, the following:
(i) An integrating regeneration stream flow
monitoring device, having an accuracy of plus or minus ten per cent or better,
shall be employed for recording the total regeneration stream mass or
volumetric flow for each regeneration cycle.
(ii) A carbon bed temperature monitoring
device shall be employed for recording the carbon bed temperature after each
regeneration and within fifteen minutes of completing any cooling
cycle.
(d) Where a
recapture or final recovery device other than an absorber, condenser, or carbon
adsorber is used, or as an alternative to the monitoring device specified in
paragraphs (H)(2)(a) to (H)(2)(c) of this rule, an organic monitoring device
equipped with a continuous recorder shall be employed for monitoring the
concentration level or reading at the outlet of the recapture or final recovery
device.
(4) For any
halogen reduction device used by a halogenated group 1 process vent to comply
with paragraph (F)(1)(g) of this rule, the owner or operator shall install,
calibrate, maintain and operate according to manufacturer's specifications,
monitoring devices as follows:
(a) Where a
scrubber is used, the following monitoring devices shall be employed:
(i) A pH monitoring device equipped with a
continuous recorder shall be employed to monitor the pH of the scrubber
effluent.
(ii) A flow meter
equipped with a continuous recorder shall be employed to monitor the scrubber
influent for liquid flow.
(iii) A
flow meter equipped with a continuous recorder shall be employed to monitor the
gas stream flow, unless an alternative method for gas stream flow
is submitted to the director, as follows:
(a) The owner or operator may determine gas
stream flow using the design blower capacity, with appropriate adjustments for
pressure drop.
(b) If the scrubber
is subject to an Ohio EPA or USEPA regulation prior to
May 27, 2005 if the facility is located in Butler, Clermont, Hamilton, or
Warren county, or August 25, 2008 if the facility is
located in Ashtabula, Cuyahoga, Geauga, Lake, Lorain, Medina, Portage, or
Summit county, the owner or operator may determine gas stream flow by the
method that had been utilized to comply with such regulation. A determination
that was conducted prior to the compliance date of such regulation may be
utilized to comply with this rule if the determination is still representative.
(c) The owner or operator may prepare and
implement a gas stream flow determination plan that documents an appropriate
method that will be used to determine the gas stream flow. The plan shall
require determination of gas stream flow by a method that will at least provide
a value for either a representative or the highest gas stream flow anticipated
in the scrubber during representative operating conditions other than startups,
shutdowns, or malfunctions. The plan shall include a description of the
methodology to be followed and an explanation of how the selected methodology
will reliably determine the gas stream flow and a description of the records
that will be maintained to document the determination of gas stream
flow.
(b) Where
a halogen reduction device other than a scrubber is used, the procedures in
paragraph (H)(8) of this rule shall be followed to establish monitoring devices
and parameters.
(5)
(Alternative parameter monitoring) An owner or operator of a process vent may
request approval to employ monitoring devices and monitoring parameters other
than those listed in paragraphs (H)(1) to (H)(4) of this rule. The request
shall be submitted according to the procedures specified in paragraph (H)(8) of
this rule. Approval shall be requested if the owner or operator uses a
combustion, recovery, or recapture device other than those listed in paragraphs
(H)(1) to (H)(4) of this rule or uses one of the combustion or recovery or
recapture devices listed in paragraphs (H)(1) to (H)(4) of this rule, but seeks
to monitor a parameter other than those specified in paragraphs (H)(1) to
(H)(4) of this rule.
(6) For any
bypass line that could divert a group 1 process vent directly to the
atmosphere, the owner or operator shall comply with either of the following:
(a) The owner or operator shall install,
calibrate, maintain, and operate, according to manufacturer's specifications, a
flow indicator that takes a reading at least once every fifteen minutes. The
flow indicator shall be installed at the entrance to any bypass line that could
divert the gas stream to the atmosphere.
(b) The owner or operator shall secure the
bypass line valve in the non-diverting position with a car-seal or a
lock-and-key type configuration. The owner or operator shall perform a visual
inspection of the seal or closure mechanism at least once every month to ensure
that the valve is maintained in the non-diverting position and the gas stream
is not diverted through the bypass line.
Equipment such as low leg drains, high
point bleeds, analyzer vents, open-ended valves or lines, and pressure relief
valves needed for safety purposes are not subject to this
paragraph.
(7) For each parameter monitored under
paragraphs (H)(2) to (H)(5) of this rule, the owner or operator shall determine
a range that indicates proper operation of the control or recovery device. The
ranges shall be determined in accordance with the following:
(a)
If a compliance test is conducted pursuant to paragraph (I) of this rule, the
range shall be based on the parameter values measured during the compliance
test that demonstrated compliance and may be supplemented by engineering
assessments or manufacturer's recommendations. Compliance testing
is not required to be conducted over the entire range of permitted parameter
values.
(b) If a TRE determination
test is conducted pursuant to paragraph (I) of this rule, the range shall be
based on the parameter values measured during the TRE determination test and
may be supplemented by engineering assessments or
manufacturer's recommendations. TRE determination testing or vent stream
measurements are not required to be conducted over the entire range of
permitted parameter values.
(c) If
a compliance test or a TRE determination test has not been conducted, the range
may be based solely on engineering assessments or
manufacturer's recommendations.
In order to establish the range, the
information specified under paragraph (K)(2)(c) of this rule shall be submitted
as part of the initial compliance status report required under paragraph (K)(2)
of this rule.
(8) Approval of other monitoring devices and
parameters.
(a) The owner or operator who has
been directed by any paragraph of this rule to establish monitoring devices and
parameters or request approval to employ monitoring devices and parameters
other than required by this rule shall submit within an application for a
permit or modification of a permit, or by other means provided by the
appropriate Ohio EPA or local air agency, the
following information:
(i) A description of
the parameter to be monitored to ensure the process,
control technology, or pollution prevention measure is operated in conformance
with its design and achieves the specified emission limit, percent reduction,
or nominal efficiency, and an explanation of the criteria used to select the
parameter.
(ii) A description of the methods and
procedures that will be used to demonstrate that the parameter indicates proper
operation of the control device or recovery device being monitored, the
schedule for this demonstration, and a statement that the owner or operator
will establish a range for the monitored parameter as part of the initial
compliance status report required in paragraph (K)(2) of this rule.
(iii) The frequency and content of
monitoring, recording, and reporting if monitoring and recording is not
continuous, or if reports of daily average values when the monitored parameter
value is outside the range established in the operating permit or initial
compliance report will not be included in semiannual reports as specified in
paragraph (K)(2) of this rule. The rationale for the proposed monitoring,
recording, and reporting system shall be included.
(b) If the monitoring device and parameter
are approved by the director, the monitoring device and parameter, including
associated records and semiannual reporting, shall be specified in the terms
and conditions of a permit or order issued by the director.
(9)
For an owner or
operator that elects, in accordance with paragraph (H)(2)(b)(ii) of this rule,
to monitor the upstream temperature only of the catalytic incinerator, an
inspection and maintenance plan shall be developed, maintained on-site, and
made readily available upon the request of the appropriate Ohio EPA district
office or local air agency. At a minumum, the plan shall include the
following:
(a)
Annual sampling and analysis of the catalyst activity (i.e., conversion
efficiency) following the manufacturer's or catalyst supplier's recommended
procedures.
(b)
Monthly inspection of the oxidizer system including
the burner assembly and fuel supply lines for problems.
(c)
Annual internal
and monthly external visual inspection of the catalyst bed to check for
channeling, abrasion, and settling. If problems are found, corrective action
consistent with the manufacturer's recommendations shall be implemented and a
new performance test to determine destruction efficiency in accordance with
paragraph (C) of rule
3745-21-10 of the Administrative
Code shall be conducted.
(I) Compliance tests and TRE determination
tests for group 1 and group 2A process vents.
(1) Where a flare is used to comply with
paragraph (F)(1)(a) of this rule, the owner or operator shall conduct
compliance tests as follows:
(a) Determine
visible emissions from the flare in accordance with paragraph (DD)(10)(d)(i) of
rule 3745-21-09 of the Administrative
Code.
(b) Determine the net heating
value of the gas being combusted in accordance with paragraph (P)(2) of rule
3745-21-10 of the Administrative
Code.
(c) Determine the actual exit
velocity of the flare in accordance with paragraph (P)(3) of rule
3745-21-10 of the Administrative
Code
(2) No initial
compliance test is required for a boiler or process heater used to comply with
paragraph (F)(1)(b) or (F)(1)(c) of this rule.
(3) Except as provided in paragraph (I)(8) of
this rule, any owner or operator using a control device (or combination of
control devices) to comply with the VOC reduction or VOC concentration
requirement in paragraph (F)(1)(d) of this rule or the VOC reduction
requirement in paragraph (F)(1)(f) of this rule, shall conduct an initial
compliance test as follows:
(a) For
determination of compliance with the ninety or ninety-eight per cent reduction
of VOC requirement, sampling sites shall be located at the outlet to atmosphere
of any control device and at the inlet of the control device (or combination of
control devices) as follows:
(i) The control
device inlet sampling site shall be located after the final recovery device (if
any).
(ii) If a vent stream is
introduced with the combustion air or as a secondary fuel into a boiler or
process heater with a design capacity less than one hundred fifty million Btu
per hour, selection of the location of the inlet sampling sites shall ensure
the measurement of VOC concentrations in all vent streams and primary and
secondary fuels introduced into the boiler or process
heater.
(b) For
determination of compliance with the twenty ppmv VOC limit, the sampling site
shall be located at the outlet of any control device.
(c) The VOC concentration and mass rate of
VOC for each sampling site shall be determined in accordance with the test
methods in paragraph (C) of rule
3745-21-09 of the Administrative
Code as follows:
(i) VOC concentration shall
be based on USEPA method 18.
(ii)
The minimum sampling time for each run shall be one hour in which either an
integrated sample or a minimum of four grab samples shall be taken. If grab
sampling is used, then the samples shall be taken at approximately equal
intervals in time such as fifteen minute intervals during the run.
(iii) The mass rate of VOC for each sample
shall be calculated in accordance with paragraph (C)(4) of rule
3745-21-10 of the Administrative
Code. The mass rate of VOC for each run shall be the average of the mass rate
of VOC of each sample within that run.
(d) The per cent reduction of VOC shall be
the per cent reduction in the mass rate of VOC between the outlet of the last
recovery device and the outlet to atmosphere from all control devices
combined.
(e) If a combustion
device is the control device used to comply with the twenty ppmv VOC limit, the
concentration of VOC shall be corrected to three per cent oxygen for each run
as follows:
(i) The emission rate correction
factor or excess air, integrated sampling and analysis procedures of USEPA
method 3B shall be used to determine the oxygen concentration
(%O2d). The samples shall be taken during the same time
that the VOC samples are taken.
(ii)
The concentration corrected to three per cent oxygen (Cc) shall be computed
using the following equation:
Click to
view image
where:
Cc = Concentration of VOC corrected to
three per cent oxygen, dry basis, ppmv.
Cm = Concentration of VOC measured, dry
basis, ppmv.
%02d = Concentration of oxygen, dry
basis, per cent by volume.
(4) Any owner or operator using a combustion
device followed by a scrubber or other halogen reduction device to comply with
paragraph (F)(1)(g)(i) of this rule shall conduct an initial compliance test to
determine compliance with the per cent reduction (control efficiency)
requirement or outlet mass limit for total hydrogen halides and halogens as
follows:
(a) For determining compliance with
the per
cent reduction requirement, sampling sites shall be located at the inlet
and outlet of the scrubber or other halogen reduction device used to reduce
halogen emissions.
(b) For
determining compliance with outlet mass emission limit, the sampling site shall
be located at the outlet of the scrubber or other halogen reduction device and
prior to any releases to the atmosphere.
(c) Except as provided in paragraph (I)(4)(f)
of this rule, USEPA method 26 or USEPA method 26A shall be used to determine
the concentration, in milligrams per dry standard cubic meter, of total
hydrogen halides and halogens that may be present in the gas stream at each
sampling site. The mass emissions of each hydrogen halide and halogen compound
shall be calculated from the measured concentrations and the gas stream flow
rate.
(d) To demonstrate compliance
with the per cent reduction requirement, the owner or
operator shall do the following:
(i)
Sum the
mass emissions for any hydrogen halides and halogens present at the inlet of
the scrubber or other halogen reduction device .
(ii)
Sum the mass
emissions for any hydrogen halides and halogens present at the outlet of the
scrubber or other halogen reduction device .
(iii)
Determine
the per cent reduction by comparison of the summed inlet and outlet
measurements.
(e) To
demonstrate compliance with the outlet mass emission limit, the owner or operator
shall sum the mass emissions for any hydrogen halides and halogens at the
outlet of the scrubber or other halogen reduction device express the emissions
as a mass emission rate in pounds per hour. The resultant mass emission rate of
total hydrogen halides and halogens shall be less than 0.99 pound per
hour.
(f) The
owner or operator may use any other method to demonstrate compliance if the
method or data has been validated according to the applicable procedures of
USEPA method 301.
(5) An
owner or operator using a scrubber or other halogen reduction device to reduce
the vent stream halogen atom mass emission rate to less than 0.99 pound per
hour prior to a combustion device to comply with paragraph (F)(1)(g)(ii) of
this rule shall determine the halogen atom mass emission rate prior to the
combustion device according to the measurement procedure in paragraph (E)(13)
of this rule.
(6) Except as
provided in paragraph (I)(9) of this rule, any owner or operator using a
recovery system, process change, or other means to achieve and maintain a TRE
index value greater than 1.0 for a process vent and to comply with paragraph
(F)(1)(e) of this rule, shall conduct TRE determination tests to determine the
TRE index value of the process vent based on measurements for flow rate, net
heating value, VOC emission rate, and mass emission rate of halogen atoms (if
needed for halogen status) as specified in the measurement procedures of
paragraphs (E)(9), and (E)(11)
to (E)(13) of this rule.
(7) Except as provided in paragraph (I)(9) of
this rule, any owner or operator using a recovery system to maintain a TRE
index value greater than 1.0 for a process vent and comply with paragraph
(F)(2) of this rule, shall conduct TRE determination tests to determine the TRE
index value of the process vent based on measurements conducted for flow rate,
net heating value, VOC emission rate, and mass emission rate of halogen atoms
(if needed for halogen status) as specified in the measurement procedures of
paragraphs (E)(9), and (E)(11)
to (E)(13) of this rule.
(8) An initial compliance test is not
required for the following:
(a) A control
device for which a test was conducted for determining compliance with a
regulation promulgated by the Ohio EPA or USEPA and the test was conducted
using the same methods specified in this rule and either no process changes
have been made since the test, or the owner or operator can demonstrate to the
satisfaction of the director that the results of the test, with or without
adjustments, reliably demonstrate compliance despite process changes.
(b) A boiler or process heater burning
hazardous waste for which the owner or operator has
done either of the following:
(i)
Been
issued a final permit under 40 CFR part 270 and complies with
40 CFR part 266,
subpart H.
(ii)
Certified compliance with the
interim status requirements of 40 CFR part 266, subpart
H.
(c) A hazardous waste incinerator for which
the owner or operator has been issued a final permit under 40 CFR part 270 and
complies with 40 CFR
part 264,
subpart O, or has certified compliance with the interim status requirements of
40 CFR part 265, subpart O.
(9) An initial TRE determination test is not
required for a recovery device for which a test was conducted for determining
compliance with a regulation promulgated by the Ohio EPA or USEPA and the test
was conducted using the same methods specified in this rule and either no
process changes have been made since the test, or the owner or operator can
demonstrate to the satisfaction of the director that the results of the test,
with or without adjustments, reliably demonstrate compliance despite process
changes.
(J)
Recordkeeping.
(1) (General) All records
specified under this paragraph shall be retained by the owner or operator for a
period of not less than five years and shall be made available to the director
or any authorized representative of the director for review during normal
business hours. The following types of records are to be maintained by the
owner or operator:
(a) Group status
determination records for process vents.
(b) Monitoring records for group 1 and group
2A process vents.
(c) Compliance
demonstration records for group 1 process vents.
(d) Compliance demonstration records for
group 2A process vents.
(e)
Compliance demonstration records for group 2B process vents.
(f) Records pertaining to the one thousand
one hundred tons per year exemption.
(2) Group status determination records for
process vents.
The owner or operator of a reactor or distillation unit subject
to this rule shall maintain records used to determine the group status of each
process vent. The following types of records are to be maintained:
(a) (TRE index value records) The owner or
operator shall maintain records of measurements, engineering assessments, and
calculations performed to determine the TRE index value of the process vent
according to the procedures of paragraph (E)(8) of this rule, including those
records associated with halogen vent stream determination. Documentation of
engineering assessments shall include all data, assumptions, and procedures
used for the engineering assessments. For any process vent not classified as
group 2B based on flow rate or VOC concentration records specified in
paragraphs (J)(2)(b) and (J)(2)(c) of this rule, TRE index value records are
needed to document the basis for classifying a process vent as group 1, group
2A, or group 2B.
(b) (Flow rate
records) Each owner or operator who elects to demonstrate that a process vent
is group 2B based on a flow rate less than 0.30 scfm shall record the flow rate
as measured using the measurement procedure specified in paragraph (E)(9) of
this rule or as determined through engineering assessment.
(c) (VOC concentration records) Each owner or
operator who elects to demonstrate that a process vent is group 2B based on a
VOC concentration less than the five hundred ppmv shall record the VOC
concentration as measured using the measurement procedure specified in
paragraphs (E)(10) of this rule or as determined through engineering
assessment.
(d) (Process change
records) The owner or operator shall keep up-to-date, readily accessible
records on process changes, as defined in paragraph (D)(6) of this rule, for
process vents as follows:
(i) If the process
vent is a group 2B process vent on the basis of the flow rate being less than
0.30 scfm, then the owner or operator shall keep records of any process changes
that increase the process vent flow rate and any redetermination of the flow
rate pursuant to paragraph (D)(6)(a) of this rule.
(ii) If the process vent is a group 2B
process vent on the basis of the VOC concentration being less than five hundred
ppmv, then the owner or operator shall keep records of any process changes that
increase the VOC concentration of the process vent and any redetermination of
the concentration pursuant to paragraph (D)(6)(b) of this rule.
(iii) If the process vent is a group 2B
process vent on the basis of the TRE index value being greater than 4.0 for a
vent stream from a recovery system, then the owner or operator shall keep
records of any process changes and any redetermination (recalculation) of the
TRE index value pursuant to paragraph (D)(6)(c) of this rule.
(iv) If the process vent is a group 2B
process vent on the basis of the TRE index value being greater than 1.0 for a
vent stream not from a recovery system, then the owner or operator shall keep
records of any process changes and any redetermination (recalculation) of the
TRE index value pursuant to paragraph (D)(6)(c) of this rule.
(v) If the process vent is a group 2A process
vent (i.e., the TRE index value is greater than 1.0 and less than or equal to
4.0 for a vent stream not from a recovery system), then the owner or operator
shall keep records of any process changes and any redetermination
(recalculation) of the TRE index value pursuant to paragraph (D)(6)(c) of this
rule.
(3)
Monitoring records for group 1 and group 2A process vents.
For any group 1 or group 2A process vent subject to paragraph
(H) of this rule, the owner or operator shall maintain monitoring records as
follows:
(a) For any flare used by a
group 1 process vent to comply with paragraph (F)(1)(a) of this rule, the owner
or operator shall maintain the following records for the monitoring device used
to continuously detect the presence of a pilot flame:
(i) Hourly records of whether the monitor was
continuously operating and whether a pilot flame was continuously present
during each hour.
(ii) A record on
the presence of a pilot flame over the full period of the compliance
test.
(iii) A record of the times
and duration of all periods when the pilot flame is absent or the monitoring
device is not operating.
(b) For any combustion device (boiler,
process heater, or incinerator) used by a group 1 process vent to comply with
paragraph (F)(1)(d) or (F)(1)(f) of this rule, the owner or operator shall
maintain the following records for the temperature monitoring device:
(i) Where the combustion device is a thermal
incinerator, boiler, or process heater:
(a)
Continuous records of firebox temperature.
(b) A record of the firebox temperature
averaged over the full period of the compliance test.
(c) A record of daily average firebox
temperature for each operating day.
(d) Records of the times and durations of all
periods excluded from the daily average as specified in paragraph (J)(3)(f) of
this rule and any other periods during process or control operation when the
monitoring device is not working.
(ii) Where the combustion device is a
catalytic incinerator and the owner or operator elects
to comply with paragraph (H)(2)(b)(i) of this rule:
(a) Continuous records of temperature
upstream and downstream of catalyst bed.
(b) A
record of the upstream temperature, downstream temperature, and temperature
difference across the catalyst bed averaged over the full period of the
compliance test.
(c) A record of
the daily average of the upstream temperature and the temperature difference
across the catalyst bed for each operating day.
(d) Records of the times and durations of all
periods excluded from the daily average as specified in paragraph (J)(3)(f) of
this rule and any other periods during process or control operation when the
monitoring device is not working.
(iii)
Where the
combustion device is a catalytic incinerator and the owner or operator elects
to comply with paragraphs (H)(2)(b)(ii) and (H)(9) of this rule:
(a)
Continuous
records of temperature upstream of the catalyst bed.
(b)
A record of the
upstream temperature averaged over the full period of the compliance
test.
(c)
A record of the daily average of the upstream
temperature for each operating day.
(d)
Records of the
times and durations of all periods excluded from the daily average as specified
in paragraph (J)(3)(f) of this rule and any other periods during process or
control operation when the monitoring device is not working.
(e)
Records, and a
description of the results of each inspection and catalyst activity
analysis.resulting from the inspection and maintenance plan for the catalytic
incinerator as specified in paragraph (H)(9) of this
rule.
(c)
For any halogen reduction device used by a halogenated group 1 process vent to
comply with paragraph (F)(1)(g)(i) of this rule, the owner or operator shall
maintain the following monitoring records:
(i) Where a scrubber is employed for a
halogenated vent stream following combustion:
(a) Continuous records of pH of scrubber
effluent.
(b) A record of pH of the
scrubber effluent averaged over the full period of the compliance
test.
(c) A record of the daily
average pH of the scrubber effluent for each operating day.
(d) Continuous records of scrubber liquid
flow rate.
(e) A record of the
scrubber liquid/gas ratio averaged over the full period of the compliance
test.
(f) A record of the daily
average scrubber liquid/gas ratio for each operating day.
(g) Records of the times and durations of all
periods excluded from the daily average as specified in paragraph (J)(3)(f) of
this rule and any other periods during process or control operation when either
monitoring device is not working.
(ii) Where a halogen reduction device other
than a scrubber is employed for a halogenated vent stream following combustion,
the owner or operator shall maintain the monitoring records identified pursuant
to paragraph (H)(8) of this rule.
(d) For any recapture device used by a group
1 process vent to comply with paragraph (F)(1)(d) of this rule and any final
recovery device within a recovery system used by a group 2A process vent to
comply with paragraph (F)(2) of this rule, the owner or operator shall maintain
the following monitoring records, as applicable:
(i) Where an absorber is the recapture or
final recovery device:
(a) Continuous records
of the exit temperature of the absorbing liquid.
(b) A record of the exit temperature of the
absorbing liquid averaged over the full period of the compliance test (if group
1) or averaged over the full period of the TRE index value determination (if
group 2A).
(c) A record of the
daily average exit temperature of the absorbing liquid for each operating
day.
(d) Continuous records of the
exit specific gravity.
(e) A record
of the exit specific gravity averaged over the full period of the compliance
test (if group 1) or averaged over the full period of the TRE index value
determination (if group 2A).
(f) A
record of the daily average exit specific gravity for each operating
day.
(g) Records of the times and
durations of all periods excluded from the daily average as specified in
paragraph (J)(3)(f) of this rule and any other periods during process or
control operation when either monitoring device is not
working.
(ii) Where a
condenser is the recapture device or final recovery device:
(a) Continuous records of the exit (product
side) temperature.
(b) A record of
the exit temperature averaged over the full period of the compliance test (if
group 1) or averaged over the full period of the TRE index value determination
(if group 2A).
(c) A record of the
daily average exit temperature for each operating day.
(d) Records of the times and durations of all
periods excluded from the daily average as specified in paragraph (J)(3)(f) of
this rule and any other periods during process or control operation when the
monitoring device is not working.
(iii) Where a carbon adsorber is the
recapture device or final recovery device:
(a)
A record of the total regenerative stream mass or volumetric flow for each
carbon bed regeneration cycle.
(b) A
record of the total regenerative stream mass or volumetric flow for each carbon
bed regeneration cycle during the full period of the compliance test (if group
1) or during the full period of the TRE index value determination (if group
2A).
(c) A record of the
temperature of the carbon bed after each regeneration cycle [and within fifteen
minutes of completing any cooling cycle.]
(d) A record of the temperature of the carbon
bed after each regeneration cycle [and within fifteen minutes of completing any
cooling cycle] during the full period of the compliance test
(if group 1) or during the full period of the TRE index value determination (if
group 2A).
(e) Records of the times
and durations of all periods during process or control operation when either
monitoring device is not working.
(iv) Where an organic monitoring device is
employed for monitoring the concentration level or reading at the outlet of a
recapture or final recovery device other than an absorber, condenser, or carbon
adsorber, or where an organic monitoring device is employed as an alternative
to the otherwise specified monitoring device for an absorber, condenser, or
carbon adsorber, the owner or operator shall maintain the following monitoring
records:
(a) Continuous records of the
concentration level or reading of the outlet of the recapture or final recovery
device.
(b) A record of the
concentration level or reading of the outlet of the recapture or final recovery
device averaged over the full period of the compliance test (if group 1) or
during the full period of the TRE index value determination (if group
2A).
(c) A record of the daily
average concentration level or reading for each operating day.
(d) Records of the times and durations of all
periods excluded from the daily average as specified in paragraph (J)(3)(f) of
this rule and any other periods during process or control operation when the
monitoring device is not working.
(e) For any bypass line that could divert a
group 1 process vent directly to the atmosphere, the owner or operator shall
maintain the monitoring records as follows:
(i) Where a flow indicator is employed for a
bypass line:
(a) Hourly records of whether the
flow indicator was operating and whether a diversion of the vent stream to the
atmosphere was detected at any time during the hour.
(b) Records of the times and durations of all
periods when the flow indicator is not operating or the vent stream is diverted
to the atmosphere.
(ii)
Where a car-seal or a lock-and-key type configuration is employed to secure the
bypass line valve in the non-diverting position:
(a) A record indicating that a monthly visual
inspection of the seal or closure mechanism has been done.
(b) Records of the times and durations of all
periods when the seal mechanism is broken, the bypass line valve position has
changed, the serial number of the broken car-seal has changed, or when the key
to unlock the bypass line valve has been checked
out.
(f) The
daily average value of a monitored parameter shall be calculated as the average
of all values recorded during the operating day by the continuous recorder,
except for monitoring data recorded during the following periods:
(i) Monitoring system breakdowns, repairs,
calibration checks, and zero (low-level) and high-level adjustments.
(ii) Start-ups.
(iii) Shutdowns.
(iv) Malfunctions.
(v) Periods of non-operation of the reactor
or distillation unit, resulting in cessation of the emissions to which the
monitoring applies.
(4) Compliance demonstration records for
group 1 process vents.
Any owner or operator of a group 1 process vent shall keep an
up-to-date, readily accessible record of the data specified in paragraphs
(J)(4)(a) to (J)(4)(e) of this rule, as applicable, to demonstrate compliance
with paragraph (F) of this rule.
(a)
When using a flare to comply with paragraph (F)(1)(a) of this rule, the owner
or operator shall maintain records on the following:
(i) Flare design (i.e., steam-assisted,
air-assisted, or non-assisted).
(ii) The
results of all visible emission readings, heat content determinations (and
associated concentration measurements), and exit velocity determinations (and
associated flow rate measurements) for a compliance test conducted pursuant to
paragraph (I)(1) of this rule.
(iii)
All periods during the compliance test when the pilot flame is
absent.
(b) When using a
boiler or process heater to comply with paragraph (F)(1)(b) of this rule, the
owner or operator shall maintain records on the heat input capacity of the
boiler or process heater and a description of the location at which the vent
stream is introduced into the boiler or process heater.
(c) When using a boiler or process heater to
comply with paragraph (F)(1)(c) of this rule, the owner or operator shall
maintain records on the location at which the vent stream is introduced into
the boiler or process heater.
(d)
When using a control device (boiler, process heater, incinerator, or recapture
device) to comply with paragraph (F)(1)(d) of this rule, the owner or operator
shall maintain records of the following:
(i)
The results of compliance tests conducted pursuant to paragraph (I)(3) of this
rule.
(ii) The results of parameter
monitoring during the compliance test, including results of continuous
parameter monitoring averaged over the full period of the compliance
test.
(iii) For a boiler or process
heater, a description of the location at which the vent stream is introduced
into the boiler or process heater for the compliance test. For a boiler or
process heater, a description of the location at which the vent stream is
introduced into the boiler or process heater for the compliance
test.
(e) When using a
recovery system, process change, or other means to achieve and maintain a TRE
index value greater than 1.0 and to comply with paragraph (F)(1)(e) of this
rule, the owner or operator shall maintain records of the TRE determination
tests conducted pursuant to paragraph (I)(7) of this rule.
(f) When using a combustion device to comply
with paragraph (F)(1)(f) of this rule, the owner or operator shall maintain
records of the following:
(i) The date of
installation of the combustion device.
(ii) Documentation on why the combustion
device is not capable of reliably reducing VOC emissions from the process vent
in order to meet the requirement of paragraph (F)(1)(d) of this rule, including
the results of any VOC emissions testing.
(iii) Information on the combustion device
pertaining to design specifications, good engineering practices, and any
requirements under applicable laws, as defined under paragraph (I) of rule
3745-31-01 of the Administrative
Code.
(iv) The results of
compliance tests conducted pursuant to paragraph (I)(3) of this rule.
(v) The results of parameter monitoring
averaged over the full period of the compliance test.
(g) When using a scrubber or other halogen
reduction device following a combustion device to control a halogenated vent
stream to comply with paragraph (F)(1)(g)(i) of this rule, the owner or
operator shall maintain records of the following:
(i) The results of compliance tests conducted
pursuant to paragraph (I)(4) of this rule.
(ii) The results of parameter monitoring
averaged over the full period of the compliance test.
(h) When transferring a group 1 process vent
for disposal to comply with paragraph (F)(1)(h) of this rule, the owner or
operator shall maintain records on the name and location of the transferee and
the identification of the group 1 process vent.
(5) Compliance demonstration records for
group 2A process vents.
Any owner or operator of a group 2A process vent shall keep an
up-to-date, readily accessible record of the data specified in paragraphs
(J)(5)(a) to (J)(5)(b) of this rule to demonstrate compliance with paragraph
(F)(2) of this rule.
(a) The results
of the TRE determination test (i.e., measurements of vent stream flow rate and
vent stream concentrations used in the TRE index value determination, all
measured while the vent stream is normally routed and constituted).
(b) The calculations to determine the TRE
index value.
(c) The results of
parameter monitoring for the final recovery device (absorber, condensers,
carbon adsorber, or other recovery device) during the TRE determination test,
including results of continuous parameter monitoring averaged over the full
period of the TRE determination test.
(6) Compliance demonstration records for
group 2B process vents.
Any owner or operator of a group 2B process vent shall keep an
up-to-date, readily accessible record of the data specified in paragraph
(J)(6)(a), (J)(6)(b), or (J)(6)(c) of this rule, whichever is applicable, to
demonstrate compliance with paragraph (F)(3) of this rule.
(a) Any owner or operator who elects to
demonstrate that a process vent is a group 2B process vent based on a flow rate
being less than 0.30 scfm shall maintain a record of the vent stream flow rate
as determined in accordance with paragraph (E)(3) of this rule, including
documentation of any engineering assessments, measurements, and
calculations.
(b) Any owner or
operator who elects to demonstrate that a process vent is a group 2B process
vent based on a VOC concentration being less than five hundred ppmv shall
maintain a record of the vent stream VOC concentration as determined in
accordance with paragraph (E)(4) of this rule, including documentation of any
engineering assessments, measurements, and calculations.
(c) Any owner or operator who elects to
demonstrate that a process vent not from a recovery system is a group 2B
process vent based on the TRE index value being greater than 1.0 shall maintain
records of the following:
(i) A description
and identification of the process operation or device preceding the process
vent.
(ii) The TRE index value as
determined in accordance with paragraph (E)(8) of this rule, including
documentation of any engineering assessments, measurements, and
calculations.
(d) Any
owner or operator who elects to demonstrate that a process vent from a recovery
system is a group 2B process vent based on the TRE index value being greater
than 4.0 shall maintain records of the following:
(i) A description and identification of the
final recovery device preceding the process vent.
(ii) The TRE index value as determined in
accordance with paragraph (E)(8) of this rule, including documentation of any
engineering assessments, measurements, and
calculations.
(7) Records pertaining to the one thousand
one hundred tons per year exemption.
The owner or operator of a reactor or distillation unit subject
to this rule and qualifying for the exemption under paragraph (C)(2) of this
rule regarding a process unit with a total design capacity for all chemicals
produced within that unit of less than one thousand one hundred tons per year,
shall keep up-to-date records detailing the design production capacity of the
process unit, including any change in equipment or process operation that
affects the total design production capacity.
(K) Reporting .
(1)
(General) The provisions under paragraph (K) of this rule describe the contents
of reports and identify the reporting dates for the following reports:
(a) Initial compliance status
report.
(b) Semiannual compliance
status reports.
(c) Process change
reports for group 2A and group 2B process vents.
(2) Initial compliance status report.
Each owner or operator of a reactor or distillation unit
subject to this rule shall submit an initial compliance status report within
sixty calendar days after the compliance dates specified in paragraph (G) of
this rule as follows:
(a) The initial
compliance status report shall include the results of any process vent group
determinations, compliance tests, TRE determination tests, inspections, values
of monitored parameters established during compliance tests and TRE
determination tests, and any other information used to demonstrate compliance
and recorded pursuant to paragraphs (J)(4) to (J)(6) of this rule.
(b) For compliance tests, TRE determination
tests, and any group determinations based on measurements, the initial
compliance status report shall include one complete test report for each test
method used for a particular kind of process vent. For additional tests and
measurements performed for the same kind of process vent using the same test
method, the test results or measurement results shall be submitted, but a
complete test report is not required.
(c) A complete test report shall include a
brief process description, sampling site description, description of sampling
and analysis procedures and any modifications to standard procedures, quality
assurance procedures, record of operating conditions during the test, record of
preparation of standards, record of calibrations, raw data sheets for field
sampling, raw data sheets for field and laboratory analyses, documentation of
calculations, and any other information required by the test method.
(d) For each monitored parameter for which a
range is required to be established under paragraph (H)(7) of this rule
(pertains to group 1 and group 2A process vents), the compliance status report
shall include the following information:
(i)
The specific range of the monitored parameter
for each control device and final recovery device.
(ii) The rationale for the specific range for
each parameter for each control device and final recovery device, including any
data and calculations used to develop the range and a description of why the
range indicates proper operation of the control device or final recovery
device.
(3)
Semiannual compliance status reports.
The owner or operator of a reactor or distillation unit subject
to this rule shall submit semiannual compliance status reports containing the
information in paragraphs (K)(3)(a)
to (K)(3)(c) of this rule. The
semiannual compliance status reports shall be submitted no later than sixty
calendar days after the end of each six-month period to the appropriate Ohio
EPA district office or local air agency. The first
report shall be submitted no later than eight months after the date the initial
compliance status report is due and shall cover the six-month period beginning
on the date the initial compliance status report is due.
(a) Semiannual reports on parameter
monitoring for group 1 process vents.
For a group 1 process vent, the semiannual compliance status
reports shall include the following recorded information:
(i) Reports of daily average values of
monitored parameters for all operating days when the daily average values
recorded under paragraph (J)(3) of this rule were outside the ranges
established in the initial compliance status report or permit issued by the
director.
(ii) Reports of the times
and durations of all periods recorded under paragraph (J)(3) of this rule when
the monitoring device is not working or monitoring data is not collected during
process operation generating the process vent stream or during operation of the
control or recovery device.
(iii)
Reports of the times and durations of all periods recorded under paragraph
(J)(3)(e)(i)(b) of this rule when the vent stream is diverted to the atmosphere
through a bypass line.
(iv) Reports
of the duration of all periods recorded under paragraph (J)(3)(e)(ii)(b) of
this rule when the seal mechanism is broken, the bypass line valve position has
changed, the serial number of the broken car-seal has changed, or the key to
unlock the bypass line valve has been checked out.
(v) Reports of the times and durations of all
periods recorded under paragraph (J)(3)(a)(iii) of this rule in which all pilot
flames of a flare were absent.
(vi)
Reports of all carbon bed regeneration cycles during which the parameters
recorded under paragraphs (J)(3)(d)(iii)(a) and (J)(3)(d)(iii)(c) of this rule
were outside the ranges established in the initial compliance status report or
permit issued by the director.
(vii) Reports on monitoring devices and
parameters approved by the director pursuant to paragraph (H)(8) of this
rule.
(b) Semiannual
reports on parameter monitoring for group 2A process vents.
For a group 2A process vent, the semiannual compliance status
reports shall include the following recorded information:
(i) Reports of daily average values of
monitored parameters for all operating days when the daily average values
recorded under paragraph (J)(3) of this rule were outside the ranges
established in the initial compliance status report or permit issued by the
director.
(ii) Reports of all
carbon bed regeneration cycles during which the parameters recorded under
paragraphs (J)(3)(d)(iii)(a) and (J)(3)(d)(iii)(c) of this rule were outside
the ranges established in the initial compliance status report or permit issued
by the director.
(iii) Reports on
monitoring devices and parameters approved by the director pursuant to
paragraph (H)(8) of this rule.
(c) Semiannual reports on subsequent
compliance tests for group 1 process vents or subsequent TRE determination
tests for group 2A process vents.
If any subsequent compliance tests or subsequent TRE
determination tests are conducted during the semiannual reporting period after
the initial compliance status report has been submitted, the semiannual
compliance status report shall include the data recorded pursuant to paragraphs
(J)(4) and (J)(5) of this rule.
(4) Process change reports for group 2A and
group 2B process vents.
Whenever a process change, as defined in paragraph (D)(6) of
this rule, is made that causes the process vent group status to change, the
owner or operator shall submit a report to the appropriate Ohio
EPA district office or local air agency within sixty
calendar days after the process change. The report shall include the following,
whichever is applicable:
(a) For a
group 2A or group 2B process vent that becomes a group 1 process vent, the
report shall include all of the following:
(i) A description of the process
change.
(ii) The results of the
redetermination of the flow rate, VOC concentration, and TRE index value
required under paragraph (D)(6) of this rule and recorded under paragraph
(J)(2)(d) of this rule.
(iii) A
statement that the owner or operator will comply with
paragraph (F)(1) of
this rule for group 1 process vents by the date specified in paragraph
(G)(3)(a) of this rule.
(b) For a group 2B process vent that becomes
a group 2A process vent, the report shall include all of the following:
(i) A description of the process
change.
(ii) The results of the
determination or redetermination of the TRE index value required under
paragraph (D)(6) of this rule and recorded under paragraph (J)(2)(d) of this
rule.
(iii) A statement that the
owner or operator will comply with paragraph (F)(2) of this rule for group 2A process vents by the
date specified in paragraph (G)(3)(b) of this rule.
(c) For a group 2A process vent that becomes
a group 2B process, the report shall include all of the following:
(i) A description of the process
change.
(ii) The results of the
determination or redetermination of the TRE index value required under
paragraph (D)(6) of this rule and recorded under paragraph (J)(2)(d) of this
rule.
(iii) A statement that the
owner or operator will comply with of paragraph (F)(3) of this rule for group 2B process
vents by the date specified in paragraph (G)(3)(c) of this
rule.
(d) For a group 2B
process vent under a specific basis that becomes a group 2A process vent under
a different basis, the report shall include all of the following:
(i) A description of the process
change.
(ii) The results of the
redetermination of the basis for the group 2 process vent under paragraph
(D)(6) of this rule and recorded under paragraph (J)(2)(d) of this
rule.
(iii) A statement that the
owner or operator will comply with paragraph (F)(3) of this rule for group 2B process vents by the
date specified in paragraph (G)(3)(c) of this rule.
(e) The owner or operator is not required to
submit a report of a process change if one of the following conditions are met:
(i) The process
change does not meet the definition of a process change in paragraph (D)(6) of
this rule.
(ii) The
vent stream flow rate is redetermined for a group 2B process vent that is based
on flow rate according to paragraph (D)(6)(a) of this rule and the redetermined
value is less than 0.30 scfm.
(iii)
The VOC concentration is redetermined for a group 2B process vent that is based
on flow rate according to paragraph (D)(6)(b) of this rule and the redetermined
value is less than five hundred ppmv.
(iv) The TRE index value is redetermined for
a group 2B process vent that is based on the TRE index value according to
paragraph (D)(6)(c) of this rule and the redetermined value is greater than 1.0
for a process vent not from a recovery system or greater than 4.0 for a process
vent from a recovery system
.
(v)
The TRE index value is redetermined for a group 2A process vent according to
paragraph (D)(6)(c) of this rule and the redetermined TRE index value for a
process vent from a recovery system is greater than 1.0 and less than or equal
to 4.0.
(L)
Applicability
notification and permit application.
(1) The
ownerr or operator of a reactor or distillation unit that is subject to this
rule, is located in Butler, Clermont, Hamilton, or Warren county, and has an
initial startup date before May 27, 2005 shall notify the appropriate Ohio
EPA district office or local air agency in writing
that the reactor or distillation operation is subject to this rule. The
notification, which shall be submitted not later than July 26, 2005, shall
provide the information specified in paragraph (L)(5) of this rule.
(2) The owner or operator of a reactor or
distillation unit that is subject to this rule, is located in Butler, Clermont,
Hamilton, or Warren county, and has an initial startup date on or after May 27,
2005 shall notify the appropriate Ohio EPA district office or
local air agency in writing that the reactor or distillation unit is subject to
this rule. The notification, which shall be submitted not later than either the
date of initial startup of the reactor or distillation unit or July 26, 2005
(whichever is later), shall provide the information specified in paragraph
(L)(5) of this rule. The application for a permit-to-install under rule
3745-31-02 of the Administrative
Code may be used to fulfill the notification requirements of this
paragraph.
(3) The owner or
operator of a reactor or distillation unit that is subject to this rule, is
located in Ashtabula, Cuyahoga, Geauga, Lake, Lorain, Medina, Portage, or
Summit county, and has an initial startup date before
August 25, 2008 shall notify the appropriate Ohio
EPA district office or local air agency in writing
that the reactor or distillation operation is subject to this rule. The
notification, which shall be submitted not later than
October 24, 2008, shall provide the
information specified in paragraph (L)(5) of this rule.
(4) The owner or operator of a reactor or
distillation unit that is subject to this rule, is located in Ashtabula,
Cuyahoga, Geauga, Lake, Lorain, Medina, Portage, or Summit county, and has an
initial startup date on or after August 25, 2008 shall notify
the appropriate Ohio EPA district office or local air
agency in writing that the reactor or distillation unit is subject to this
rule. The notification, which shall be submitted not later than either the date
of initial startup of the reactor or distillation unit or
October 24, 2008 (whichever is
later), shall provide the information specified in paragraph (L)(5) of this
rule. The application for a permit-to-install under rule
3745-31-02 of the Administrative
Code may be used to fulfill the notification requirements of this
paragraph.
(5) The notification
required in paragraphs (L)(1) to (L)(4) of this rule shall include the
following information:
(a) Name and address of
the owner or operator.
(b)
Address (i.e., physical location) of the facility.
(c) Equipment description and Ohio EPA
application number (if assigned) of the reactor or distillation unit.
(d) Identification of the applicable
requirements, the means of compliance, and the compliance date for the reactor
or distillation unit under this rule
(e)
An application for an operating permit or an application for
a modification to an operating permit in accordance with Chapter 3745-77 of the
Administrative Code (for sources subject to the Title V permit program) or an
application for a permit-to-install and operate or an application for a
modification to a permit-to-install and operate in accordance with Chapter
3745-31 of the Administrative Code (for sources not subject to the Title V
permit program) for each subject process that meets one of the following:
(i)
The process does not
possess an effective operating permit or permit-to-install and
operate.
(ii)
The process possesses an
effective operating permit or permit-to-install and operate and the owner or
operator cannot certify in writing to the director that such subject process is
in compliance with this rule. An application for an operating permit or
permit-to-install and operate is not required provided the subject process is
operating under an effective permit and certifies compliance. Such
certification shall include all compliance certification requirements under
paragraph (K)(2) of this rule.
[Comment: Applications for sources not
subject to Chapter 3745-77 of the Administrative Code, requiring submittal
prior to June 30, 2008, were submitted in accordance with Chapter 3745-35 of
the Administrative
Code.]
Effective: 10/15/2015
Five Year
Review (FYR) Dates: 07/13/2015 and
07/13/2020
Promulgated
Under: 119.03
Statutory Authority: 3704.03(E)
Rule
Amplifies: 3704.03(A), 3704.03(E)
Prior Effective Dates: 5/27/2005,
8/25/2008