Ohio Administrative Code
Title 3701 - Department of Health - Administration and Director
Chapter 3701-86 - Registration of Newborn Safety Incubator Locations
Section 3701-86-04 - Installation of a newborn safety incubator access portal and newborn safety incubator
Universal Citation: OH Admin Code 3701-86-04
Current through all regulations passed and filed through September 16, 2024
(A) The access portal door to the newborn safety incubator will be installed by a licensed general contractor registered with the Ohio department of health in accordance with rule 3701-86-02 of the Administrative Code.
(1) The access portal door
will:
(a) Lock automatically upon
closure;
(b) May only be unlocked
from the interior of the building;
(c) Trigger a series of alarms that, at a
minimum, include:
(i) An audible alarm
triggered to a central location within the facility one minute after the
opening of the access portal door; and
(ii) An automatic call to 911 triggered from
the alarm system if the alarm is not turned off from within the facility within
one minute of the commencement of the initial alarm.
(2) The access portal door alarm
will
only be capable of being turned off from within the facility once a response is
made to the newborn safety incubator.
(B) The access portal door alarm will be:
(1) Wired into the existing structure's
electrical or telecommunications system.
(a)
If wired into the structure's existing electrical system:
(i) Be in compliance with the "National
Electric Code" and "National Fire Code/National Fire Protection Agency"
standards, if applicable;
(ii) Be
installed by a licensed electrical contractor registered with the Ohio
department of health in accordance with rule
3701-86-02 of the Administrative
Code; and
(iii) If the facility has
a secondary or back-up power supply, be wired into the secondary or back-up
power supply to ensure continued operation of the alarm system during outages
of the structure's primary power supply.
(b) If wired into the structure's existing
telecommunications network, installed by a telecommunications installation
professional registered with the Ohio department of health in accordance with
rule 3701-86-02 of the Administrative
Code.
(2) Tested
following installation to ensure the activation of the audible, 911, and
disarming components of the system; and
(3) Tested at a minimum of once each quarter
to ensure continued functionality.
(a)
Documentation of the required testing will be
maintained onsite by the location as long as the newborn safety incubator
remains registered at the location; and
(b) Documentation of the required testing
will be
made available to the director upon request.
(C) Each newborn safety incubator will:
(1) Be a medical bassinet in compliance with
21 CFR
880.5145 with the exception of bassinet
wheels, which will be removed for installation in compliance with
paragraph (C)(2) of this rule;
(2)
Have the supporting frame of the medical bassinet physically anchored to a
position that aligns the plastic basket or bed portion of the bassinet with the
wall directly beneath the access portal door and prevents movement of the unit
as a whole; and
(3) Provide a safe
sleep environment. For the purpose of this rule, a safe sleep environment means
the medical bassinet includes:
(a) A firm flat
bassinet mattress;
(b) A bassinet
mattress sheet that fits snugly on a mattress and overlaps the mattress so it
cannot be dislodged by pulling on the corner of the sheet; and
(c) Is free from any bedding, including
pillows, bumpers, and blankets.
Disclaimer: These regulations may not be the most recent version. Ohio may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.