Current through all regulations passed and filed through September 16, 2024
(A)
General. A well
permitted under Chapters 1501:9-1 to 1501:9-12 of the Administrative Code shall
be constructed in a manner that is approved by the chief as specified by these
rules, the terms and conditions of the approved permit, plans submitted in the
approved permit, and the standards established in section
1509.17 of the Revised Code. The
casing and cementing plans in the approved permit are understood to be
estimates based upon the best available geologic information prior to drilling.
The division shall evaluate compliance with this rule for the as-built well.
Where this rule does not detail specific methods to meet these standards, the
owner shall use sound design and industry practices that effectively achieve
the standards established in section
1509.17 of the Revised
Code.
(B)
Field standards. The chief may establish alternative
well construction standards that are well-specific, field-specific, or
play-specific by permit condition, to ensure protection of public health or
safety or the environment.
(C)
Drilling
fluids.
(1)
All intervals drilled prior to reaching the USDW protective depth shall be
drilled with air, fresh water, a freshwater based drilling fluid, or a
combination of the above. Only additives suitable for drilling through potable
water supplies may be used while drilling these intervals.
(2)
Based on
regional knowledge of groundwater resources, well control, or safety factors,
the chief may by permit condition require the use of a freshwater based
drilling fluid and specify its characteristics while the owner is drilling any
interval prior to reaching the USDW protective depth.
(3)
Below cemented
surface casing, other drilling fluids may be utilized consistent with sound
design and effective industry practice.
(D)
Casing
standards.
(1)
All casing installed in a well shall be steel alloy casing that has been
manufactured and tested consistent with standards established by the American
petroleum institute (API) in "5 CT Specification for Casing and Tubing" or ASTM
international (ASTM) in "A500/A500M Standard Specification for Cold-Formed
Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes" and
has a minimum internal yield pressure rating designed to withstand at least 1.2
times the maximum pressure to which the casing may be subjected during
drilling, production or stimulation operations.
(a)
The minimum
internal yield pressure rating shall be based upon engineering calculations
listed in API "TR 5C-3 Technical Report on Equations and Calculations for
Casing, Tubing and Line Pipe used as Casing and Tubing, and Performance
Properties Tables for Casing and Tubing."
(b)
Reconditioned
casing that is permanently set in a well shall be hydrostatically pressure
tested with an applied pressure at least 1.2 times the maximum internal
pressure to which the casing may be subjected, based upon known or anticipated
subsurface pressure, or pressure that may be applied during stimulation,
whichever is greater, and assuming no external pressure. The casing shall be
marked to verify the test status. The owner shall provide a copy of the test
results to the inspector before the casing is installed in the well.
(c)
Where
subsurface reservoir pressure is unknown and cannot be reasonably anticipated,
the owner shall assume a pressure gradient of 0.45 pounds per square inch per
foot in a fully evacuated hole, under shut-in conditions.
(d)
All hydrostatic
pressure tests shall be conducted pursuant to API "5 CT Specification for
Casing and Tubing" or other method(s) approved by the chief.
(2)
Reconditioned casing shall not be set in a well unless it has passed an
approved hydrostatic pressure and drift test or has otherwise been approved by
the inspector. The inspector shall reject casing that is excessively pitted,
patched, bent, corroded, or crimped, or if threads are severely worn or
damaged.
(3)
In order to verify casing integrity and proper cement
displacement, the owner shall pressure test each cemented casing string greater
than two hundred feet long in accordance with the test method of either
paragraph (D)(3)(a) or (D)(3)(b) of this rule.
(a)
Immediately upon
landing the latch-down plug, the owner shall increase displacement pressure by
at least five hundred pounds per square inch and hold pressure for five
minutes. If pressure declines by ten per cent or more, casing integrity and
cement placement shall be further evaluated and appropriate corrective action
shall be taken to verify casing integrity and cement displacement. If the float
apparatus does not hold, the owner shall pump the volume that flowed back, and
shut in until the cement has sufficiently set.
(b)
Prior to
drilling the cement plug, the owner shall test any permanently cemented casing
strings, at a minimum pump pressure in pounds per square inch calculated by
multiplying the length of the casing string by 0.2, but not less than three
hundred pounds per square inch. The test pressure may not decline by more than
ten per cent during the thirty-minute test period.
(i)
If, at the end
of thirty minutes of such testing, the pressure shows a drop greater than ten
per cent, the owner shall not resume further operations until the condition is
corrected. A pressure test demonstrating a pressure drop equal to or less than
ten per cent after thirty minutes is evidence that the condition has been
corrected.
(ii)
Casing integrity may be verified in conjunction with
blowout preventer testing without a test plug using either the test pressure
described in paragraph (D)(3)(b) of this rule, or the pressure required to test
the blowout preventer, whichever is greater.
(E)
Casing shoe tests. The chief may require the owner to
conduct a casing shoe test after drilling below the surface casing and/or the
intermediate casing seat if the pressure gradient of the permitted hydrocarbon
reservoir exceeds 0.5 pounds per square inch per foot, or in areas where
fracture gradients are unknown.
(F)
Surface water
infiltration. Before drilling below the first casing string, the owner shall
either crown the location around the wellbore to divert fluids to a flow ditch,
or construct a liquid-tight cellar at least three feet in diameter to prevent
surface infiltration of fluids adjacent to the wellbore. If a reserve pit is
used to contain cuttings and drilling fluids, the flow ditch from the cellar or
crown to the reserve pit shall also be liquid tight.
(G)
Mouse and rat
holes. If a mouse and/or rat hole is used, it shall be constructed of liquid
tight steel pipe with a welded basal plate or bull plug. The annulus shall be
sealed with clay or cement in a manner that effectively prevents fluids from
entering the annular space.
(H)
Wellbore
diameters.
(1)
The diameter of each section of the wellbore in which casing will be set and
cemented shall be at least one inch greater than the outside diameter of casing
collar to be installed, unless otherwise approved by the chief.
(2)
The
wellbore diameter shall be consistent with manufacturer's recommendations for
all float equipment, centralizers, packers, cement baskets, and all other
equipment run into the wellbore on casing.
(I)
Wellbore
conditioning.
(1)
Prior to cementing, the wellbore shall be conditioned
to kill gas flow, foster adequate cement displacement, and ensure a high
quality bond between cement and the wellbore. If circulation cannot be
established or maintained, the inspector shall require testing to evaluate
cement displacement. If tests indicate cement displacement or quality is
inadequate to meet the standards, the owner shall not resume drilling activity
until corrective action has achieved compliance with the standards.
(2)
If
oil-based drilling mud is used, the wellbore shall be conditioned with a mud
flush and the spacer volume should be designed for a minimum of ten minutes of
contact time prior to cementing production casing in the horizontal segment of
a wellbore.
(3)
Where underground mine voids, solution voids, or other
geologic features render circulation infeasible, the owner shall install a
cement basket or other approved device as close as possible above the top of
the void or thief zone. Mine strings shall be cemented above and below the mine
void in accordance with paragraph (M) of this rule.
(J)
Cement
standards.
(1)
All cement placed into the wellbore shall be Portland cement that is
manufactured to meet the standards of API "10 A Specification for Cements and
Materials for Well Cementing" or ASTM "C150/C150M Standard Specification for
Portland Cement."
(2)
Cemented conductor, mine, and surface casing strings
shall remain static until all cement has reached a compressive strength of at
least five hundred pounds per square inch before drilling the plug, or
initiating a test.
(3)
The tail cement for all intermediate and production
casings and liners shall remain static until the cement has reached a
compressive strength of at least five hundred pounds per square inch before
drilling out the plug or initiating a test. Tail cement shall have a
seventy-two-hour compressive strength of at least one thousand two hundred
pounds per square inch. Lead cements with volume extenders may be used to seal
these strings, but in no case shall the cement have a compressive strength of
less than one hundred pounds per square inch at the time of drill out nor less
than two hundred fifty pounds per square inch twenty-four hours after being
placed.
(4)
The density of the cement slurry shall be based upon a
laboratory free fluid separation test demonstrating an average fluid loss no
more than three milliliters per two hundred fifty milliliters of cement tested
in accordance with API "RP 10 B-2 Recommended Practice for Testing Well
Cements." Slurry should be mixed and pumped at a rate that ensures consistent
slurry density.
(5)
The chief may require, by permit condition, a specific
cement mixture to be used in any well or any area if evidence of local
conditions indicate a specific cement is necessary.
(6)
The owner shall
ensure that the cement mix water quality and chemistry is proper for the cement
slurry design. An authorized representative of the owner shall be on site
observing the cement mixing equipment for the entire duration of the cement
mixing and placement to ensure that cement slurry design parameters are
followed.
(7)
Sulfate resistant cement shall be used whenever
necessary to protect the casing string and prevent the migration of hydrogen
sulfide. When the owner is drilling in a township where hydrogen sulfide occurs
commonly in specific intervals, the chief shall require as a permit condition
that the owner use sulfate resistant cement.
(8)
Compressive
strength test requirements.
(a)
Cement mixtures for which published performance data
are not available shall be tested by the owner or service company and approved
by the chief prior to usage. Tests shall be made on representative samples of
the basic mixture of cement and additives used, using distilled water or
potable tap water for preparing the slurry. The tests shall be conducted using
the equipment and procedures established in API "RP 10 B-2 Recommended Practice
for Testing Well Cements." Test data showing competency of a proposed cement
mixture to meet the above requirements shall be furnished to the inspector
prior to the cementing operation. To determine that the minimum compressive
strength has been obtained, the owner shall use the typical performance data
for the particular cement mixture used in the well at the following
temperatures and at atmospheric pressure:
(i)
For conductor,
mine string, and surface casing cement, the test temperature shall be sixty
degrees Fahrenheit;
(ii)
For intermediate and production casing cement, the
test temperature shall be within ten degrees Fahrenheit of the formation
equilibrium temperature of the cemented interval.
(K)
Centralizer standards.
(1)
All bowspring
centralizers shall meet the standards of API "10 D, Specification for
Bow-Spring Casing Centralizers."
(2)
All rigid
centralizers shall meet the standards of API "10 TR 4 Considerations Regarding
Selection of Centralizers for Primary Cementing Operations."
(3)
Casing shall be
centralized in each segment of the wellbore to provide sufficient casing
standoff and foster effective circulation of cement to isolate critical zones
including aquifers, flow zones, voids, lost circulation zones, and hydrocarbon
production zones.
(L)
Notification.
The owner shall notify the inspector at least twenty-four hours prior to
setting any casing or liner string and before commencing any casing cementing
operation pursuant to this rule to enable the inspector to participate in the
pre-job safety and procedures meeting, independently test mix water, evaluate
casing condition, and observe and document the execution of the cementing
operation.
(M)
Casing strings.
(1)
Drive pipe.
Drive pipe may be driven through unconsolidated materials and need not be
cemented if there is no annular space.
(2)
Mine
string.
(a)
Casing through an active underground mining operation.
(i)
If a well is
drilled within the geographic limits of an active underground mining operation,
the owner shall construct the well in a manner that protects personnel working
in the mine, and, if possible, shall locate the well so as to penetrate a
pillar, a barrier, or the unmined perimeter of the seam.
(ii)
If a well is
drilled within the limits of an active underground mining operation that may
penetrate the excavations of a mine and groundwater has been encountered below
the base of the conductor casing, the hole shall be reduced fifteen feet above
the roof of the mine. This string of casing shall be cemented to surface to
shut off all groundwater. Drilling shall continue to a point at least thirty
but no more than fifty feet below the floor of the mine and another string of
casing shall be set and cemented.
(b)
Casing through
any underground mine void. After drilling through any underground mine void or
rubble zone, casing shall be set at least thirty feet but no more than fifty
feet below the base of the mine void or rubble zone and cemented at this point.
The owner shall design the casing and cementing plans considering the maximum
number of casing strings that may be necessary to isolate mine voids prior to
setting and cementing surface casing.
(c)
A mine string
shall not serve as the only water protection casing. Where a mine string
isolates one or more water-bearing zones, either surface or intermediate casing
shall be cemented to surface inside the mine string.
(d)
Each mine string
shall be equipped with a guide shoe or other appropriate device to prevent
deformation of the bottom of the casing.
(e)
Cementing the
mine string.
(i)
If a mine void or rubble zone is encountered, the
owner shall equip the mine string with a cement basket or other approved device
as close to the top of the void as practical.
(ii)
The interval
from the casing seat to the base of the coal seam shall be cemented.
(iii)
Cement shall be placed on top of the basket or other approved device by pour
string or pumping from surface.
(3)
Conductor
casing.
(a)
Conductor casing shall be set where necessary to:
(i)
Stabilize
unconsolidated sediments;
(ii)
Isolate shallow
aquifers that provide or are capable of providing groundwater for water wells
and springs in the vicinity of the well;
(iii)
Isolate
groundwater before penetrating the working of an active underground mine;
or
(iv)
Provide a base for equipment to divert shallow,
naturally occurring natural gas.
(b)
Conductor casing
shall be cemented to surface if there is an annular space.
(c)
If circulated
cement drops or fails to circulate, cement shall be emplaced from surface by a
method approved by the inspector.
(4)
Surface
casing.
(a)
An
owner shall set and cement sufficient surface casing at least fifty feet below
the base of the deepest USDW, or at least fifty feet into competent bedrock,
whichever is deeper, and as specified by the permit, unless otherwise approved
by the chief. Surface casing shall be cemented before drilling though
hydrocarbon bearing flow zones or zones which contain concentrations of total
dissolved solids exceeding ten thousand milligrams per liter unless otherwise
approved by the chief. For the purposes of this paragraph, hydrocarbon bearing
flow zones shall include all formations that have historically, are currently,
or are anticipated to be commercially productive.
(b)
Sufficient
cement shall be used to fill the annular space outside the casing from the seat
to the ground surface or to the bottom of the cellar.
(c)
If cement is not
circulated to the ground surface or the bottom of the cellar and the top of
cement cannot be measured from surface, the owner shall perform tests as
approved by the inspector. The owner shall notify the inspector prior to
performing the tests. After the nature of the well construction deficiency is
determined, the owner shall contact the inspector and obtain approval for the
procedures to be used to perform any required additional cementing operations.
Surface casing shall not be perforated for the purpose of remedial cementing
unless intermediate casing is set and cemented to surface, or otherwise
authorized by the chief.
(d)
If remedial options fail and the chief determines that
USDWs are not adequately isolated or protected, the chief may issue an
administrative order suspending further drilling operations. If the chief
determines additional remedial measures will not isolate and protect the USDW,
the chief shall issue an administrative order requiring the well to be
plugged.
(e)
For surface holes drilled through glacial drift
deposits that exceed one hundred feet in thickness, a guide shoe shall be run
on the surface casing.
(f)
In areas where bedrock USDWs cannot be mapped, except
in areas subject to paragraph (M)(4)(g) of this rule, surface casing shall be
set and cemented at the depth stated in paragraph (M)(4)(f)(i) or (M)(4)(f)(ii)
of this rule, whichever is deeper and as determined by permit condition, or, as
an alternative method for protecting groundwater resources, at the depth stated
in paragraph (M)(4)(f)(iii) of this rule:
(i)
At least three
hundred feet deep; or
(ii)
At least one hundred feet below the deepest local
perennial stream base; or
(iii)
At least fifty
feet below the base of the lowest spring or deepest water well developed for
any legitimate purpose, based upon an inventory of water supplies within a five
hundred foot radius of the proposed oil and gas well. If there are no springs
or water wells within the five hundred foot radius, conductor casing shall be
set and cemented at a minimum depth of one hundred feet. After conductor casing
is set through the deepest useable water zone and cemented to surface, the
owner shall set and cement to surface a surface casing string through water
zones that may include brackish or brine bearing zones. This casing string
shall be set and cemented to surface before the owner drills into potential
flow zones that can reasonably be expected to contain hydrocarbons in
commercial quantities.
(g)
In areas where
bedrock USDWs cannot be mapped and where groundwater resources can be developed
in valley-fill aquifers, surface casing shall be cemented at least one hundred
feet below the base of the valley-fill aquifer for any well within one thousand
feet of the one hundred year floodplain..
(5)
Alternative
surface casing requirements. An alternative method of protecting USDWs may be
approved upon written application to the chief. The owner shall state the
reason for the alternative USDW protection method and outline the alternative
method for casing and cementing through the deepest USDW. Alternative methods
for setting more than specified amounts of surface casing for well control
purposes may be requested on a field-specific or area-specific basis.
Alternative methods for setting less than specified amounts of surface casing
shall be authorized on an individual well basis only. The chief may approve,
modify, or reject the proposed alternative method. The chief shall reject the
proposed method by order if the owner has not demonstrated that the alternative
casing plan will meet the standards of section
1509.17 of the Revised Code and
this rule. The owner may file an appeal with the oil and gas commission
pursuant to section 1509.36 of the Revised Code. An
owner shall obtain the chief's written approval of any alternative method
before commencing operations.
(6)
Intermediate
casing.
(a)
Intermediate casing may be set at the discretion of the owner to isolate flow
zones, lost circulation zones, or other geologic hazards, unless otherwise
required by this rule or the approved permit.
(b)
The owner shall
set and cement intermediate casing in a competent formation in the following
situations:
(i)
If groundwater containing total dissolved solids of less
than ten thousand milligrams per liter is encountered below the base of
cemented surface casing;
(ii)
Through a gas
storage reservoir when drilling to strata beneath a gas storage reservoir
within the storage protective boundary;
(iii)
When drilling
to permitted hydrocarbon zones deeper than the silurian clinton sandstone east
of the updip pinchout; such casing shall be set through the Mississippian berea
sandstone, or one thousand feet, whichever is greater;
(iv)
For wells
drilled horizontally, in the Marcellus shale, or deeper, such casing shall be
set through the Mississippian berea sandstone or one thousand feet, whichever
is greater; or
(v)
In other situations as determined by the chief.
(c)
For each intermediate string of casing that is
permanently set in the wellbore, tail cement shall extend from the seat to a
point at least five hundred true vertical feet above the casing seat, or to a
point at least two hundred feet above the seat of the next larger diameter
casing string.
(d)
If the intermediate wellbore penetrates one or more
flow zones, cement shall be placed at least five hundred feet above the
uppermost flow zone. The cement used to control annular gas migration from flow
zones shall be designed consistent with recommended methods in API "65-2
Isolating Potential Flow Zones during Construction." The cement shall reach a
compressive strength of five hundred pounds per square inch before drill out.
Annular pressure shall be measured prior to drill out to verify isolation of
the flow zone.
(e)
If the cement placement indicators including fluid
returns, lift pressure, or annular pressure indicate inadequate isolation of
any flow zone, the owner shall obtain approval of the inspector for the
proposed plan for determining top of cement and/or performing additional
cementing operations.
(f)
Liners may be set and cemented as intermediate casing
provided that the cemented liner has a minimum of two hundred feet of cemented
lap within the next larger casing, and the liner top is pressure tested to a
level equal to or higher than the maximum anticipated pressure to be
encountered in the interval to be drilled below the liner. The test pressure
may not decline by more than ten per cent during the thirty minute test period.
If at the end of a thirty minute pressure test, the pressure has dropped by
more than ten per cent, the owner shall not resume operations until the
condition is corrected and verified by a thirty minute pressure test.
(7)
Production casing and liners.
(a)
Cemented
completions.
(i)
The production casing shall be cemented with
sufficient cement to fill the annular space to a point at least five hundred
true vertical feet above the seat in an open-hole vertical completion or the
uppermost perforation in a cemented vertical completion, or one thousand feet
above the kickoff point of a horizontal well. If any flow zone is present,
including strata that may contain hydrocarbons in commercial quantities or a
hydrogen sulfide-bearing flow zone, the casing shall be cemented in a manner
that effectively isolates such strata with at least five hundred feet of cement
above the zone. The cement slurry shall be designed to control annular gas
migration consistent with recommended methods in API "65-2 Isolating Potential
Flow Zones during Construction."
(ii)
When cementing
the production string of a well that will be stimulated by hydraulic
fracturing, and the uppermost perforation is less than five hundred feet below
the base of the deepest USDW, sufficient cement shall be used to fill the
annular space outside the casing from the seat to the ground surface or to the
bottom of the cellar. If cement is not circulated to the ground surface or the
bottom of the cellar, the owner shall notify the inspector and perform tests
approved by the inspector. After the top of cement outside the casing is
determined, the owner or his authorized representative shall contact the
inspector and obtain approval for the procedures to be used to perform any
required additional cementing operations.
(iii)
Liners may be
set and cemented as production casing, provided that the cemented liner has a
minimum of two hundred true vertical depth feet of cemented lap within the next
larger casing, and the liner top is pressure tested to a level that is at least
five hundred pounds per square inch higher than the maximum anticipated
pressure to be encountered by the wellbore during completion and production
operations. The test pressure may not decline by more than ten per cent during
the thirty minute test period. If at the end of a thirty minute pressure test,
the pressure has dropped by more than ten per cent, the owner shall not resume
operations until the condition is corrected and verified by a thirty minute
pressure test. Liners may only be set and cemented as production casing in
horizontal shale gas wells if approved by the chief.
(iv)
If operations
indicate inadequate cement coverage or isolation of the hydrocarbon bearing
zones, the owner shall obtain approval of the inspector for procedures to
determine the top of cement and/or perform corrective actions.
(b)
Packer completions. Packer or other non-cemented completions may be used in
place of cemented completions. If intermediate casing is run with this type of
completion, cementing shall meet the requirements of paragraph (M)(7) of this
rule. If intermediate casing is not run, a multi-stage cementing tool shall be
run above the top external packer and cemented to fill the annular space
outside the casing to the surface or to a point at least five hundred feet
above the packer or casing seat. The chief may approve alternative completion
proposals. Any approved alternative shall meet the well construction standards
of section 1509.17 of the Revised Code and
these rules.
(N)
Annular
pressure.
(1)
Wellhead assemblies shall be used to maintain surface control of the well. Each
component of the wellhead shall have a working pressure rating equal to or
greater than the highest anticipated operating pressure to which the particular
component might be exposed during the course of drilling, testing, completing,
stimulating, or producing the well.
(2)
The valve on the
surface-production casing annulus or surface-intermediate casing annulus shall
be accessible and equipped with a pressure gauge to allow continual monitoring
of mechanical integrity. The valve shall also be equipped with a properly
functioning pressure relief valve set at or below the hydrostatic pressure at
the surface casing seat assuming a pressure gradient of 0.433 pounds per square
inch times the height of the groundwater column. If the hydrostatic head at the
casing seat is unknown, the surface-production casing annulus is assumed to be
over-pressurized when annular pressure measured at surface exceeds 0.303
multiplied by the length of the surface casing. If the inspector approves
perforation of surface casing and intermediate casing is not installed and
cemented, the allowable annular pressure measured at surface in pounds per
square inch will be established by multiplying the depth of the uppermost
perforation by 0.303.
(3)
If any time after installation of the wellhead
assembly, the sustained annular pressure exceeds the prescribed pressure or
releases the pressure relief valve, the owner shall immediately notify the
inspector.
(4)
The inspector shall approve tests or logging
procedures to evaluate the cause of over-pressurized conditions and approve a
plan for corrective action. If remedial cementing, replacement of defective
casing, or implementation of other mechanical barriers or operational solutions
cannot eliminate over-pressurized conditions, the owner shall plug the
well.
(5)
During stimulation or workover operations, all annuli
shall be pressure-monitored. Stimulation or workover operations shall be
immediately suspended for any inexplicable pressure deviation above those
anticipated increases caused by pressure or thermal transfer. In the event that
stimulation fluids circulate, or annular pressures deviate from anticipated,
the owner shall immediately notify the inspector and acquire approval for
remediation of casing or cement. If the chief determines that the stimulation
of the well has resulted in irreparable damage to the well, the chief shall
order that the well be plugged and abandoned within thirty days of issuance of
the order.
(O)
Well construction records.
(1)
Within sixty
days after drilling to total depth, the owner shall file a legible copy of all
cement job logs with the chief furnishing complete data documenting the
cementing of all cemented casing strings, on a form approved by the chief and
signed by the owner of the well or his authorized agent having personal
knowledge of the facts, and representatives of the cementing company performing
the cementing job, attesting to compliance with the cementing requirements of
this rule.
(2)
Each job log shall include the following
information:
(a)
Date cemented;
(b)
Name of the
cementing contractor;
(c)
Mix water temperature and pH;
(d)
Whether or not
the wellbore circulated prior to cementing;
(e)
Hole diameter in
inches, casing outer diameter in inches, casing length in feet, float equipment
depth in feet, basket depth in feet, and centralizer depth in vertical segments
of the wellbore in feet;
(f)
Number of centralizers placed in the horizontal
segment of a wellbore;
(g)
Cement type, additives by percent of unit volume,
volume of cement in sacks, cement yield per sack, average slurry density in
pounds per gallon, slurry volume in barrels, and displacement volume in
barrels;
(h)
Pumping rates in barrels per minute, displacement
pressure in pounds per square inch, and final circulating pressure prior to
landing the plug in pounds per square inch;
(i)
The time the
latch-down or wiper plug landed;
(j)
Casing test
pressure in pounds per square inch and final test pressure in pounds per square
inch;
(k)
Whether or not cement circulated to surface; and
(l)
Volume of cement slurry circulated to surface in barrels.
Effective:
8/1/2012
R.C.
119.032 review dates:
05/29/2017
Promulgated
Under: 119.03
Statutory
Authority: 1509.03,
1509.06,
1509.17,
1509.23
Rule
Amplifies: 1509.02,
1509.03,
1509.05,
1509.06,
1509.10,
1509.12,
1509.15,
1509.17,
1509.18,
1509.23