Section 1301:7-7-64 - Pyrophoric materials
Current through all regulations passed and filed through September 16, 2024
(A) Section 6401 General
(B) Section 6402 Definition
"Pyrophoric."
(C) Section 6403 General requirements
(D) Section 6404 Storage
The storage of silane gas and gas mixtures with a silane concentration of 1.37 per cent or more by volume, shall be in accordance with CGA G-13 as listed in rule 1301:7-7-80 of the Administrative Code.
Aisles between storage piles shall be not less than 10 feet (3048 mm) in width.
Individual tanks or containers shall not exceed 500 gallons (1893 L) in capacity.
Exception: Storage in approved hazardous materials storage cabinets constructed in accordance with paragraph (C)(8)(g)(5003.8.7) of rule 1301:7-7-50 of the Administrative Code.
The storage of silane gas, and gas mixtures with a silane concentration of 1.37 per cent or more by volume, shall be in accordance with CGA G-13 as listed in rule 1301:7-7-80 of the Administrative Code.
Table 6404.2.1 Pyrophoric gases-distance from storage to exposuresa
Maximum amount per storage area (cubic feet) |
Minimum distance between storage areas (feet) |
Minimum distance to lot lines of property that can be built upon (feet) |
Minimum distance to public streets, public alleys or public ways (feet) |
Minimum distance to buildings on the same property |
||
Nonrated construction or openings within 25 feet |
Two-hour construction and openings within 25 feet |
Four-hour construction and no openings within 25 feet |
||||
250 |
5 |
25 |
5 |
5 |
0 |
0 |
2,500 |
10 |
50 |
10 |
10 |
5 |
0 |
7,500 |
20 |
100 |
20 |
20 |
10 |
0 |
For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m3.
(E) Section 6405 Use