Ohio Administrative Code
Title 1301:7 - Division of State Fire Marshal
Chapter 1301:7-7 - Ohio Fire Code
Section 1301:7-7-62 - Organic peroxides
Current through all regulations passed and filed through September 16, 2024
(A) Section 6201 General
Unclassified detonable organic peroxides that are capable of detonation in their normal shipping containers under conditions of fire exposure shall be stored in accordance with rule 1301:7-7-56 of the Administrative Code.
(B) Section 6202 Definition
"Organic peroxide."
"Class I."
"Class II."
"Class V."
"Unclassified detonable."
(C) Section 6203 General requirements
(D) Section 6204 Storage
Indoor storage of unclassified detonable organic peroxides that are capable of detonation in their normal shipping containers under conditions of fire exposure shall be stored in accordance with rule 1301:7-7-56 of the Administrative Code.
Table 6204.1.2
Organic peroxides - distance to exposures from detached storage buildings or outdoor storage areas
Organic peroxide class |
Maximum storage quantity (pounds) at minimum separation distance |
|||||
Distance to buildings, lot lines, public streets, public alleys, public ways or means of egress |
Distance between individual detached storage buildings or individual outdoor storage areas |
|||||
50 feet |
100 feet |
150 feet |
20 feet |
75 feet |
100 feet |
|
I |
2,000 |
20,000 |
175,000 |
2,000 |
20,000 |
175,000 |
II |
100,000 |
200,000 |
No limit |
100,000a |
No limit |
No limit |
III |
200,000 |
No limit |
No limit |
200,000a |
No limit |
No limit |
IV |
No limit |
No limit |
No limit |
No limit |
No limit |
No limit |
V |
No limit |
No limit |
No limit |
No limit |
No limit |
No limit |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
a. Where the amount of organic peroxide stored exceeds this amount, the minimum separation shall be 50 feet.
Exception: A smoke detection system shall not be required in detached storage buildings equipped throughout with an approved automatic fire-extinguishing system complying with rule 1301:7-7-09 of the Administrative Code.
Table 6204.1.7
Storage of organic peroxides
Organic peroxide class |
Pile configuration |
Maximum quantity per building |
|||
Maximum width (feet) |
Maximum height (feet) |
Minimum distance to next pile (feet) |
Minimum distance to walls (feet) |
||
I |
6 |
8 |
4a |
4b |
Note c |
II |
10 |
8 |
4a |
4b |
Note c |
III |
10 |
8 |
4a |
4b |
Note c |
IV |
16 |
10 |
3a,d |
4b |
No requirement |
V |
No requirement |
No requirement |
No requirement |
No requirement |
No requirement |
For SI: 1 foot = 304.8 mm.
a. Not less than one main aisle with a minimum width of 8 feet shall divide the storage area.
b. Distance to noncombustible walls is allowed to be reduced to 2 feet.
c. See Table 6204.1.2 of this rule for maximum quantities.
d. The distance shall be not less than one-half the pile height.
(E) Section 6205 Use
Replaces: 1301:7-7-62