Ohio Administrative Code
Title 1301:7 - Division of State Fire Marshal
Chapter 1301:7-7 - Ohio Fire Code
Section 1301:7-7-57 - Flammable and combustible liquids
Current through all regulations passed and filed through September 16, 2024
(A) Section 5701 General
Exceptions:
When mixed with lower flash-point liquids, Class II or III liquids are capable of assuming the characteristics of the lower flash-point liquids. Under such conditions, the appropriate provisions of this rule for the actual flash point of the mixed liquid shall apply.
When heated above their flash points, Class II and III liquids assume the characteristics of Class I liquids. Under such conditions, the appropriate provisions of this rule for flammable liquids shall apply.
(B) Section 5702 Definitions
"Alcohol-based hand rub."
"Bulk plant or terminal."
"Bulk transfer."
"Combustible liquid."
"Class II."
"Class IIIA."
"Class IIIB."
"Fire point."
"Flammable liquid."
"Class IA."
"Class IB."
"Class IC."
"Flash point."
"Fuel limit switch."
"Liquid storage room."
"Liquid storage warehouse."
"Mobile fueling."
"Process transfer."
"Refinery."
"Remote emergency shutoff device."
"Remote solvent reservoir."
"Solvent distillation unit."
"Tank, primary."
(C) Section 5703 General requirements
The extent of the classified area is allowed to be reduced, or eliminated, where sufficient technical justification is provided to the fire code official that a concentration in the area in excess of 25 per cent of the lower flammable limit (LFL) cannot be generated.
Table 5703.1.1
Class I electrical equipment locationsa
Location |
Group D Division |
Extent of classified area |
Underground tank fill opening |
1 2 |
Pits, boxes or spaces below grade level, any part of which is within the Division 1 or 2 classified area. Up to 18 inches above grade level within a horizontal radius of 10 feet from a loose-fill connection and within a horizontal radius of 5 feet from a tight-fill connection. |
Vent-discharging upward |
1 2 |
Within 3 feet of open end of vent, extending in all directions. Area between 3 feet and 5 feet of open end of vent, extending in all directions. |
Drum and container filling Outdoor or indoor with adequate ventilation |
1 2 |
Within 3 feet of vent and fill opening, extending in all directions. Area between 3 feet and 5 feet from vent of fill opening, extending in all directions. Also up to 18 inches above floor or grade level within a horizontal radius of 10 feet from vent or fill opening. |
Pumps, bleeders, withdrawal fittings, meters and similar devices Indoor Outdoor |
2 2 |
Within 5 feet of any edge of such devices, extending in all directions, and up to 3 feet above floor or grade level within 25 feet horizontally from any edge of such devices. Within 3 feet of any edge of such devices, extending in all directions, and up to 18 inches above floor or grade level within 10 feet horizontally from an edge of such devices. |
Pits Without mechanical ventilation With mechanical ventilation Containing valves, fittings or piping, and not within Division 1 or 2 classified area |
1 2 2 |
Entire area within pit if any part is within a Division 1 or 2 classified area. Entire area within pit if any part is within a Division 1 or 2 classified area. Entire pit. |
Drainage ditches, separators, impounding basins Indoor Outdoor |
1 or 2 2 |
Same as pits. Area up to 18 inches above ditch, separator or basin, and up to 18 inches above grade within 15 feet horizontal from any edge. |
Tank vehicle and tank carb Loading through open dome Loading through bottom connections with atmospheric venting |
1 2 1 2 |
Within 3 feet of edge of dome, extending in all directions. Area between 3 feet and 15 feet from edge of dome, extending in all directions. Within 3 feet of point of venting to atmosphere, extending in all directions. Area between 3 feet and 15 feet from point of venting to atmosphere, extending in all directions. Also up to 18 inches above grade within a horizontal radius of 10 feet from point of loading connection. |
Tank vehicle and tank carb- continued Loading through closed dome with atmospheric venting Loading through closed dome with vapor control Bottom loading with vapor control or any bottom unloading |
1 2 2 2 |
Within 3 feet of open end of vent, extending in all directions. Area between 3 feet and 15 feet from open end of vent, extending in all directions, and within 3 feet of edge of dome, extending in all directions. Within 3 feet of point of connection of both fill and vapor lines, extending in all directions. Within 3 feet of point of connection, extending in all directions, and up to 18 inches above grade within a horizontal radius of 10 feet from point of connection. |
Storage and repair garage for tank vehicles |
1 2 |
Pits or spaces below floor level. Area up to 18 inches above floor or grade level for entire storage or repair garage. |
Garages for other than tank vehicles |
Ordinary |
Where there is an opening to these rooms within the extent of an outdoor classified area, the entire room shall be classified the same as the area classification at the point of the opening. |
Outdoor drum storage |
Ordinary |
--- |
Indoor warehousing where there is no flammable liquid transfer |
Ordinary |
Where there is an opening to these rooms within the extent of an indoor classified area, the room shall be classified the same as if the wall, curb or partition did not exist. |
Indoor equipment where flammable vapor/air mixtures could exist under normal operations |
1 2 |
Area within 5 feet of any edge of such equipment, extending in all directions. Area between 5 feet and 8 feet of any edge of such equipment, extending in all directions, and the area up to 3 feet above floor or grade level within 5 feet to 25 feet horizontally from any edge of such equipment. |
Outdoor equipment where flammable vapor/air mixtures could exist under normal operations |
1 2 |
Area within 3 feet of any edge of such equipment, extending in all directions. Area between 3 feet and 8 feet of any edge of such equipment extending in all directions, and the area up to 3 feet above floor or grade level within 3 feet to 10 feet horizontally from any edge of such equipment. |
Tank-above ground Shell, ends or roof and dike area Vent Floating roof |
1 2 1 2 1 |
Area inside dike where dike height is greater than the distance from the tank to the dike for more than 50 per cent of the tank circumference. Area within 10 feet from shell, ends or roof of tank. Area inside dikes to level of top of dike. Area within 5 feet of open end of vent, extending in all directions. Area between 5 feet and 10 feet from open end of vent, extending in all directions. Area above the roof and within the shell. |
Office and restrooms |
Ordinary |
Where there is an opening to these rooms within the extent of an indoor classified location, the room shall be classified the same as if the wall, curb or partition did not exist. |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Locations as classified in NFPA 70 as listed in rule 1301:7-7-80 of the Administrative Code.
b. When classifying the extent of area, consideration shall be given to the fact that tank cars or tank vehicles can be spotted at varying points. Therefore, the extremities of the loading or unloading positions shall be used.
c. The release of Class I liquids can generate vapors to the extent that the entire building, and possibly a zone surrounding it, are considered a Class I, Division 2 location.
Exception: Solvent distillation units in accordance with paragraph (E)(4)( 5705.4) of this rule.
Table 5703.6.2
Piping standards
Piping use |
Standard |
Power piping |
ASME B 31.1as listed in rule 1301:7-7-80 of the Administrative Code |
Process piping |
ASME B 31.3as listed in rule 1301:7-7-80 of the Administrative Code |
Pipeline transportation systems for liquid hydrocarbons and other liquids |
ASME B 31.4as listed in rule 1301:7-7-80 of the Administrative Code |
Building services piping |
ASME B 31.9as listed in rule 1301:7-7-80 of the Administrative Code |
In all cases, nonmetallic piping shall be used in accordance with section 27.4.6 of NFPA 30 as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Vapor-recovery piping is allowed to be tested using an inert gas.
In lieu of the minimum 4-foot (1219 mm) straight run length, approved flexible joints are allowed to be used under dispensers and suction pumps, at submerged pumps and tanks, and where vents extend above ground.
Nonmetallic joints shall be approved and shall be installed in accordance with the manufacturer's instructions.
Pipe joints that are dependent on the friction characteristics or resiliency of combustible materials for liquid tightness of piping shall not be used in buildings. Piping shall be secured to prevent disengagement at the fitting.
(D) Section 5704 Storage
Exceptions:
Exception: Listed, lockable engine mounted tanks that are connected to stationary pieces of equipment shall not be required to be enclosed in vaults or to have fencing if all of the following apply:
Tanks that have previously contained Class I liquids shall not be loaded with Class II or Class III liquids until such tanks and all piping, pumps, hoses and meters connected thereto have been completely drained and flushed.
Exceptions:
Exception: Areas designated as smoking and hot work areas, and areas where hot work permits have been issued in accordance with this code.
Weeds, combustible materials and waste Class I, II or IIIA liquids shall not be accumulated in an unsafe manner at a storage site.
Exception: Where determined by the fire code official that the use of such devices can result in damage to the tank.
Vent-line flame arresters shall be installed in accordance with their listing or API 2000 as listed in rule 1301:7-7-80 of the Administrative Code and maintained in accordance with section 21.8.6 of NFPA 30 or API 2000 as listed in rule 1301:7-7-80 of the Administrative Code. In-line flame arresters in piping systems shall be installed and maintained in accordance with their listing or API 2028 as listed in rule 1301:7-7-80 of the Administrative Code. Pressure-vacuum vents shall be installed in accordance with section 21.4.3 of NFPA 30 or API 2000 as listed in rule 1301:7-7-80 of the Administrative Code and maintained in accordance with section 21.8.6 of NFPA 30 or API 2000 as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Vent pipe outlets on tanks storing Class IIIB liquid inside buildings and connected to fuel-burning equipment shall be located such that the vapors are released to a safe location outside of buildings.
Exceptions:
Filling and emptying connections to indoor tanks containing Class IIIB liquids and connected to fuel-burning equipment shall be located at a finished ground level location outside of buildings. Such openings shall be provided with a liquid-tight cap that shall be closed when not in use. A sign in accordance with paragraph(C)(6)( 5003.6) of rule 1301:7-7-50 of the Administrative Code that displays the following warning shall be permanently attached at the filling location:
"TRANSFERRING FUEL OTHER THAN CLASS IIIB COMBUSTIBLE LIQUID TO THIS TANK CONNECTION IS A VIOLATION OF THE FIRE CODE AND IS STRICTLY PROHIBITED"
An approved means or method in accordance with paragraph(D)(2)(i)(vi)(e)(5704.2.9.6.5) of this rule shall be provided to prevent the overfilling of Class IIIB liquid storage tanks connected to fuel-burning equipment inside buildings.
Exception: Outside above-ground tanks with a capacity of 1,320 gallons (5000 L) or less.
Exception: Where approved by the fire code official, below-grade vaults are allowed to be constructed on site, provided that the design is in accordance with the building code as listed in rule 1301:7-7-80 of the Administrative Code and that special inspections are conducted to verify structural strength and compliance of the installation with the approved design in accordance with section 1707 of the building code as listed in rule 1301:7-7-80 of the Administrative Code. Installation plans for below-grade vaults that are constructed on site shall be prepared by, and the design shall bear the stamp of, a registered design professional. Consideration shall be given to soil and hydrostatic loading on the floors, walls and lid; anticipated seismic forces; uplifting by groundwater or flooding; and to loads imposed from above such as traffic and equipment loading on the vault lid.
The top of an at-grade or below-grade vault shall be designed to relieve safely or contain the force of an explosion occurring inside the vault. The top and floor of the vault and the tank foundation shall be designed to withstand the anticipated loading, including loading from vehicular traffic, where applicable. The walls and floor of a vault installed below grade shall be designed to withstand anticipated soil and hydrostatic loading.
Vaults shall be designed to be wind and earthquake resistant, in accordance with the building code as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Storage of foam-producing materials off the premises is allowed as follows:
Exceptions:
Exception: Crude oil storage tanks in production fields with no other exposures adjacent to the storage tank.
Exceptions:
Exceptions:
Exception: Liquids with boilover characteristics and unstable liquids in accordance with paragraphs(D)(2)(i)(v)(a)(iv)(5704.2.9.5. 1.4) and (D)(2)(i)(v)(a)(v)(5704.2.9.5. 1.5 ) of this rule.
Exception: Tanks used for storing Class IIIB liquids are allowed to be spaced 3 feet (914 mm) apart unless within a diked area or drainage path for a tank storing Class I or II liquids.
The separation between tanks containing unstable liquids shall be not less than one-half the sum of their diameters.
Dikes, diversion curbs, grading or other method approved by the fire code official shall be provided to prevent the accumulation of Class I, II or IIIA liquids under adjacent LP-gas containers. Where flammable or combustible liquid storage tanks are within a diked area, the LP-gas containers shall be outside the diked area and not less than 10 feet (3048 mm) away from the centerline of the wall of the diked area.
Exceptions:
Exception: Where climatic conditions are such that the sign may be obscured by ice or snow, or weathered beyond readability or otherwise impaired, said procedures and chart shall be located in the office window, lock box or other area accessible to the person filling the tank.
Exceptions:
Exceptions:
Exception: Those underground tank systems that are out of service for more than one year where an extension of the one year out of service period has been granted by the state fire marshal. Any request for an extension of the out of service period shall be submitted in writing prior to the end of the one year out of service period, or extension thereof to the state fire marshal. All such written requests for extension must contain the following information:
Exception: In-place fire protection (foam) system lines.
Exceptions:
Exception.:
Exception: Piping is allowed to be abandoned in place where the fire code official determines that removal is not practical. Abandoned piping shall be capped and safeguarded as required by the fire code official.
Exception: Piping associated with bulk plants, terminal facilities and refineries.
Exceptions:
Exception: Shelves in storage cabinets or on laboratory furniture specifically designed for such use.
For Group M occupancy wholesale and retail sales uses, indoor storage of flammable and combustible liquids shall not exceed the maximum allowable quantities per control area indicated in Table 5704.3.4.1 of this rule.
Storage of hazardous production material flammable and combustible liquids in Group H-5 occupancies shall be in accordance with rule 1301:7-7-50 of the Administrative Code.
Table 5704.3.4.1
Maximum allowable quantity per control area of flammable and combustible liquids in wholesale and retail sales occupanciesa
Type of liquid |
Maximum allowable quantity per control area (gallons) |
||
Sprinkleredb in accordance with footnote densities and arrangements |
Sprinklered in accordance with Tables 5704.3.6.3(4) to 5704.3.6.3(8) and Table 5704. 3.7.5.1 of this rule |
Nonsprinklered |
|
Class IA |
60 |
60 |
30 |
Class IB, IC, II and IIIA |
7,500c |
15,000c |
1,600 |
Class IIIB |
Unlimited |
Unlimited |
13,200 |
For SI: 1 foot = 304.8 mm, 1 square foot = 0.00929 m2, 1 gallon = 3.785 L, 1 gallon per minute per square foot = 40.75 L/min/m2.
a. Control areas shall be separated from each other by not less than a 1-hour fire barrier wall.
b. To be considered as sprinklered, a building shall be equipped throughout with an approved automatic sprinkler system with a design providing minimum densities as follows:
1. For uncartoned commodities on shelves 6 feet or less in height where the ceiling height does not exceed 18 feet, quantities are those allowed with a minimum sprinkler design density of Ordinary Hazard Group 2.
2. For cartoned, palletized or racked commodities where storage is 4 feet 6 inches or less in height and where the ceiling height does not exceed 18 feet, quantities are those allowed with a minimum sprinkler design density of 0.21 gallon per minute per square foot over the most remote 1,500-square-foot area.
c. Where wholesale and retail sales or storage areas exceed 50,000 square feet in area, the maximum allowable quantities are allowed to be increased by 2 per cent for each 1,000 square feet of area in excess of 50,000 square feet, up to not more than 100 per cent of the table amounts. A control area separation is not required. The cumulative amounts, including amounts attained by having an additional control area, shall not exceed 30,000 gallons.
Exception: In sprinklered buildings, an aggregate quantity of 120 gallons (454 L) of water-miscible Class IB and Class IC liquids is allowed in nonmetallic containers, each having a capacity of 16 ounces ( 0.473 L) or less.
Exception: Metal containers not exceeding 55 gallons (208 L) are allowed to store up to 240 gallons (908 L) of the maximum allowable quantity per control area of Class IB and IC liquids in a control area. The building shall be equipped throughout with an automatic sprinkler system in accordance with Table 5704.3.4.1 of this rule. The containers shall be provided with plastic caps without cap seals and shall be stored upright. Containers shall not be stacked or stored in racks and shall not be located in areas accessible to the public.
Combustible commodities shall not be stored above flammable and combustible liquids.
Table 5704.3.6.3(1)
Maximum storage height in control area
Type of liquid |
Nonsprinklered area (feet) |
Sprinklered areaa (feet) |
Sprinklered with in-rack protectiona,b (feet) |
Flammable liquids: Class IA Class IB Class IC |
4 4 4 |
4 8 8 |
4 12 12 |
Combustible liquids: Class II Class IIIA Class IIIB |
6 8 8 |
8 12 12 |
12 16 20 |
For SI: 1 foot = 304.8 mm.
a. In buildings protected by an automatic sprinkler system, the storage height for containers and portable tanks shall not exceed the maximum storage height permitted for the fire protection scheme set forth in NFPA 30 as listed in rule 1301:7-7-80 of the Administrative Code or the maximum storage height demonstrated in a full-scale fire test, whichever is greater. NFPA 30 criteria as listed in rule 1301:7-7-80 of the Administrative Code and fire test results for metallic containers and portable tanks shall not be applied to nonmetallic containers and portable tanks.
b. In-rack protection shall be in accordance with Table 5704.3.6.3(5), 5704.3.6.3(6) or 5704.3.6.3(7) of this rule.
Table 5704.3.6.3(2)
Storage arrangements for palletized or solid-pile storage in liquid storage rooms and warehouses
Class |
Storage level |
Maximum storage height |
Maximum quantity per pile (gallons) |
Maximum quantity per rooma (gallons) |
||||
Drums |
Containersb (feet) |
Portable tanksb (feet) |
Containers |
Portable tanks |
Containers |
Portable tanks |
||
IA |
Ground floor Upper floors Basements |
1 1 0 |
5 5 Not allowed |
Not allowed Not allowed Not allowed |
3,000 2,000 Not allowed |
Not allowed Not allowed Not allowed |
12,000 8,000 Not allowed |
Not allowed Not allowed Not allowed |
IB |
Ground floor Upper floors Basements |
1 1 0 |
6.5 6.5 Not allowed |
7 7 Not allowed |
5,000 3,000 Not allowed |
20,000 10,000 Not allowed |
15,000 20,000 Not allowed |
40,000 12,000 Not allowed |
IC |
Ground floord Upper floors Basements |
1 1 0 |
6.5c 6.5c Not allowed |
7 7 Not allowed |
5,000 3,000 Not allowed |
20,000 10,000 Not allowed |
15,000 12,000 Not allowed |
40,000 20,000 Not allowed |
II |
Ground floord Upper floors Basements |
3 3 1 |
10 10 5 |
14 14 7 |
10,000 10,000 7,500 |
40,000 40,000 20,000 |
25,000 25,000 7,500 |
80,000 80,000 20,000 |
III |
Ground floor Upper floors Basements |
5 5 3 |
20 20 10 |
14 14 7 |
15,000 15,000 10,000 |
60,000 60,000 20,000 |
50,000 50,000 25,000 |
100,000 100,000 40,000 |
For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L.
a. See paragraph (D)(3)(h)(i)(5704.3.8.1) of this rule for unlimited quantities in liquid storage warehouses.
b. In buildings protected by an automatic sprinkler system, the storage height for containers and portable tanks shall not exceed the maximum storage height permitted for the fire protection scheme set forth in NFPA 30 as listed in rule 1301:7-7-80 of the Administrative Code or the maximum storage height demonstrated in a full-scale fire test, whichever is greater. NFPA 30 criteria as listed in rule 1301:7-7-80 of the Administrative Code and fire test results for metallic containers and portable tanks shall not be applied to nonmetallic containers and portable tanks.
c. These height limitations are allowed to be increased to 10 feet for containers having a capacity of 5 gallons or less.
d. For palletized storage of unsaturated polyester resins (UPR) in relieving-style metal containers with 50 per cent or less by weight Class IC or II liquid and no Class IA or IB liquid, height and pile quantity limits shall be permitted to be 10 feet and 15,000 gallons, respectively, provided that such storage is protected by sprinklers in accordance with NFPA 30 as listed in rule 1301:7-7-80 of the Administrative Code and that the UPR storage area is not located in the same containment area or drainage path for other Class I or II liquids.
Table 5704.3.6.3(3)
Storage arrangements for rack storage in liquid storage rooms and warehouses
Class |
Type rack |
Storage level |
Maximum storage height (feet)b |
Maximum quantity per rooma(gallons) |
Containers |
Containers |
|||
IA |
Double row or single row |
Ground floor Upper floors Basements |
25 15 Not allowed |
7,500 4,500 Not allowed |
IB IC |
Double row or single row |
Ground floor Upper floors Basements |
25 15 Not allowed |
15,000 9,000 Not allowed |
II |
Double row or single row |
Ground floor Upper floors Basements |
25 25 15 |
24,000 24,000 9,000 |
III |
Multirow Double row Single row |
Ground floor Upper floors Basements |
40 20 20 |
48,000 48,000 24,000 |
For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L.
a. See paragraph (D)(3)(h)(i)(5704.3.8.1) of this rule for unlimited quantities in liquid storage warehouses.
b. In buildings protected by an automatic sprinkler system, the storage height for containers and portable tanks shall not exceed the maximum storage height permitted for the fire protection scheme set forth in NFPA 30 as listed in rule 1301:7-7-80 of the Administrative Code or the maximum storage height demonstrated in a full-scale fire test, whichever is greater. NFPA 30 criteria as listed in rule 1301:7-7-80 of the Administrative Code and fire test results for metallic containers and portable tanks shall not be applied to nonmetallic containers and portable tanks.
Table 5704.3.6.3(4)
Automatic sprinkler protection for solid-pile and palletized storage of liquids in metal containers and portable tanksa
Storage conditions |
Ceiling sprinkler design and demand |
Minimum hose stream demand (gpm) |
Minimum duration sprinklers and hose streams (hours) |
||||
Density (gpm/ft2) |
Area (square feet) |
Maximum spacing (square feet) |
|||||
Class liquid |
Container size and arrangement |
High temperature sprinklers |
Ordinary temperature sprinklers |
||||
IA |
5 gallons or less, with or without cartons, palletized or solid pileb |
0.30 |
3,000 |
5,000 |
100 |
750 |
2 |
Containers greater than 5 gallons, on end or side, palletized or solid pile |
0.60 |
5,000 |
8,000 |
80 |
750 |
||
IB, IC and II |
5 gallons or less, with or without cartons, palletized or solid pileb |
0.30 |
3,000 |
5,000 |
100 |
500 |
2 |
Containers greater than 5 gallons on pallets or solid pile, one high |
0.25 |
5,000 |
8,000 |
100 |
|||
II |
Containers greater than 5 gallons on pallets or solid pile, more than one high, on end or side |
0.60 |
5,000 |
8,000 |
80 |
750 |
2 |
IB, IC and II |
Portable tanks, one high |
0.30 |
3,000 |
5,000 |
100 |
500 |
2 |
II |
Portable tanks, two high |
0.60 |
5,000 |
8,000 |
80 |
750 |
2 |
III |
5 gallons or less, with or without cartons, palletized or solid pile |
0.25 |
3,000 |
5,000 |
120 |
500 |
1 |
Containers greater than 5 gallons on pallets or solid pile, on end or sides, up to three high |
0.25 |
3,000 |
5,000 |
120 |
500 |
1 |
|
Containers greater than 5 gallons, on pallets or solid pile, on end or sides, up to 18 feet high |
0.35 |
3,000 |
5,000 |
100 |
750 |
2 |
|
Portable tanks, one high |
0.25 |
3,000 |
5,000 |
120 |
500 |
1 |
|
Portable tanks, two high |
0.50 |
3,000 |
5,000 |
80 |
750 |
2 |
For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L, 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m2.
a. The design area contemplates the use of Class II standpipe systems. Where Class I standpipe systems are used, the area of application shall be increased by 30 per cent without revising density.
b. For storage heights above 4 feet or ceiling heights greater than 18 feet, an approved design shall be provided.
Table 5704.3.6.3(5)
Automatic sprinkler protection requirements for rack storage of liquids in metal containers of 5-gallon capacity or less with or without cartons on conventional wood palletsa
Class liquid |
Ceiling sprinkler design and demand |
In-rack sprinkler arrangement and demand |
Minimum hose stream demand (gpm) |
Minimum duration sprinkler and hose stream (hours) |
||||||
Density (gpm/ft2) |
Area (square feet) |
Maximum spacing |
Racks up to 9 feet deep |
Racks more than 9 feet to 12 feet deep |
30 psi (standard orifice) |
Number of sprinklers operating |
||||
High temperature sprinklers |
Ordinary temperature sprinklers |
14 psi (large orifice) |
||||||||
I (maximum 25-foot height) Option 1 |
0.40 |
3,000 |
5,000 |
80 ft2/head |
1. Ordinary temperature, quick-response sprinklers, maximum 8 feet 3 inches horizontal spacing 2. One line sprinklers above each level of storage 3. Locate in longitudinal flue space, staggered vertical 4. Shields required where multilevel |
1. Ordinary temperature, quick-response sprinklers, maximum 8 feet 3 inches horizontal spacing 2. One line sprinklers above each level of storage 3. Locate in transverse flue spaces, staggered vertical and within 20 inches of aisle 4. Shields required where multilevel |
30 psi ( 0.5 -inch orifice) |
1. Eight sprinklers if only one level 2. Six sprinklers each on two levels if only two levels 3. Six sprinklers each on top three levels, if three or more levels 4. Hydraulically most remote |
750 |
2 |
I (maximum 25-foot height)Option 2 |
0.55 |
2,000b |
Not applicable |
100 ft2/head |
1. Ordinary temperature, quick-response sprinklers, maximum 8 feet 3 inches horizontal spacing 2. See 2 above 3. See 3 above 4. See 4 above |
1. Ordinary temperature, quick-response sprinklers, maximum 8 feet 3 inches horizontal spacing orifice) 2. See 2 above 3. See 3 above 4. See 4 above |
14 psi ( 0.53 -inch |
See 1 through 4 above |
500 |
2 |
I and II (maximum 14-foot storage height) (maximum three tiers) |
0.55c |
2,000d |
Not applicable |
100 ft2/head |
Not Applicable None for maximum 6-foot-deep racks |
Not applicable |
Not applicable |
Not applicable |
500 |
2 |
II (maximum 25-foot height) |
0.30 |
3,000 |
5,000 |
100 ft2/head |
1. Ordinary temperature sprinklers 8 feet apart horizontally 2. One line sprinklers between levels at nearest 10-foot vertical intervals 3. Locate in longitudinal flue space, staggered vertical 4. Shields required where multilevel |
1. Ordinary temperature sprinklers 8 feet apart horizontally 2. Two lines between levels at nearest 10-foot vertical intervals 3. Locate in transverse flue spaces, staggered vertical and within 20 inches of aisle 4. Shields required where multilevel |
30 psi |
Hydraulically most remote-six sprinklers at each level, up to a maximum of three levels |
750 |
2 |
III (40-foot height) |
0.25 |
3,000 |
5,000 |
120 ft2/head |
Same as for Class II liquids |
Same as for Class II liquids |
30 psi |
Same as for Class II liquids |
500 |
2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch = 6.895 kPa, 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m2.
a. The design area contemplates the use of Class II standpipe systems. Where Class I standpipe systems are used, the area of application shall be increased by 30 per cent without revising density.
b. Using listed or approved extra-large orifices, high-temperature quick-response or standard element sprinklers under a maximum 30-foot ceiling with minimum 7.5 -foot aisles.
c. For friction lid cans and other metal containers equipped with plastic nozzles or caps, the density shall be increased to 0.65 gpm per square foot using listed or approved extra-large orifice, high-temperature quick-response sprinklers.
d. Using listed or approved extra-large orifice, high-temperature quick-response or standard element sprinklers under a maximum 18-foot ceiling with minimum 7.5 -foot aisles and metal containers.
Table 5704.3.6.3(6)
Automatic sprinkler protection requirements for rack storage of liquids in metal containers greater than 5 gallon capacitya
Class liquid |
Ceiling sprinkler design and demand |
In-rack sprinkler arrangement and demand |
Minimum hose stream demand (gpm) |
Minimum duration sprinkler and hose stream (hours) |
||||||
Density (gpm/ft2) |
Area (square feet) |
Maximum spacing |
On-side storage racks up to 9-foot deep racks |
On-end storage (on pallets) up to 9-foot deep racks |
Minimum nozzle pressure |
Number of sprinklers operating |
||||
High temperature sprinklers |
Ordinary temperature sprinklers |
|||||||||
IA (maximum 25-foot height) |
0.60 |
3,000 |
5,000 |
80 ft2/head |
1. Ordinary temperature sprinklers 8 feet apart horizontally 2. One line sprinklers above each tier of storage 3. Locate in longitudinal flue space, staggered vertical 4. Shields required where multilevel |
1. Ordinary temperature sprinklers 8 feet apart horizontally 2. One line sprinklers above each tier of storage 3. Locate in longitudinal flue space, staggered vertical 4. Shields required where multilevel |
30 psi |
Hydraulically most remote-six sprinklers at each level |
1,000 |
2 |
IB, IC and II (maximum 25-foot height) |
0.60 |
3,000 |
5,000 |
100 ft2/head |
1. See 1 above 2. One line sprinklers every three tiers of storage 3. See 3 above 4. See 4 above |
1. See 1 above 2. See 2 above 3. See 3 above 4. See 4 above |
30 psi |
Hydraulically most remote-six sprinklers at each level |
750 |
2 |
III (maximum 40-foot height) |
0.25 |
3,000 |
5,000 |
120 ft2/head |
1. See 1 above 2. One line sprinklers every sixth level (maximum) 3. See 3 above 4. See 4 above |
1. See 1 above 2. One line sprinklers every third level (maximum) 3. See 3 above 4. See 4 above |
15 psi |
Hydraulically most remote-six sprinklers at each level |
500 |
1 |
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch = 6.895 kPa, 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m2.
a. The design assumes the use of Class II standpipe systems. Where a Class I standpipe system is used, the area of application shall be increased by 30 per cent without revising density.
Table 5704.3.6.3(7)
Automatic AFFF water protection requirements for rack storage of liquids in metal containers greater than 5-gallon capacitya,b
Class liquid |
Ceiling sprinkler design and demand |
In-rack sprinkler arrangement and demandc |
Duration AFFF supply (minimum) |
Duration water supply (hours) |
|||||
Density (gpm/ft2) |
Area (square feet) |
On-end storage of drums on pallets, up to 25 feet |
Minimum nozzle pressure (psi) |
Number of sprinklers operating |
Hose stream demandd (gpm) |
||||
High-temperature sprinklers |
Ordinary temperature sprinklers |
||||||||
IA, IB, IC and II |
0.30 |
1,500 |
2,500 |
1. Ordinary temperature sprinkler up to 10 feet apart horizontally 2. One line sprinklers above each level of storage 3. Locate in longitudinal flue space, staggered vertically 4. Shields required for multilevel |
30 |
Three sprinklers per level |
500 |
15 |
2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch = 6.895 kPa, 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m2.
a. System shall be closed-head wet system with approved devices for proportioning aqueous film-forming foam.
b. Except as modified herein, in-rack sprinklers shall be installed in accordance with NFPA 13 as listed in rule 1301:7-7-80 of the Administrative Code.
c. The height of storage shall not exceed 25 feet.
d. Hose stream demand includes 11/2-inch inside hose connections, where required.
Table 5704.3.6.3(8)
Automatic sprinkler protection requirements for Class I liquid storage in metal containers of 1-gallon capacity or less with uncartoned or case-cut shelf display up to 6.5 feet, and palletized storage above in a double row rack arraya
Storage height |
Ceiling sprinkler design and demand |
In-rack sprinkler arrangement and demand |
Minimum hose stream demand (gpm) |
Minimum duration sprinklers and hose stream (hours) |
||||||
Density (gpm/ft2) |
Area (square feet) |
Maximum spacing |
Racks up to 9 feet deep |
Racks 9 to 12 feet |
Minimum nozzle pressure |
Number of sprinklers operating |
||||
High temperature |
Ordinary temperature |
|||||||||
Maximum 20-foot storage height |
0.60 |
2,000b |
Not applicable |
100 ft2/head |
1. Ordinary temperature, quick response sprinklers, maximum 8 feet 3 inches horizontal spacing 2. One line of sprinklers at the 6-foot level and the 11.5 -foot level of storage 3. Locate in longitudinal flue space, staggered vertical 4. Shields required where multilevel |
Not applicable |
30 psi (standard orifice) or 14 psi (large orifice) |
1. Six sprinklers each on two levels 2. Hydraulically most remote 12 sprinklers |
500 |
2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch = 6.895 kPa, 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m2.
a. This table shall not apply to racks with solid shelves.
b. Using extra-large orifice sprinklers under a ceiling 30 feet or less in height. Minimum aisle width is 7.5 feet.
Additional aisles shall be provided for access to doors, required windows and ventilation openings, standpipe connections, mechanical equipment and switches. Such aisles shall be not less than 3 feet (914 mm) in width, unless greater widths are required for separation of piles or racks, in which case the greater width shall be provided.
Requirements for portable tank design shall be in accordance with chapters 9 and 12 of NFPA 30 as listed in rule 1301:7-7-80 of the Administrative Code. Shelving, racks, dunnage, scuffboards, floor overlay and similar installations shall be of noncombustible construction or of wood not less than a 1-inch (25 mm) nominal thickness. Adequate material-handling equipment shall be available to handle tanks safely at upper tier levels.
Automatic foam-water systems and automatic aqueous film-forming foam (AFFF) water sprinkler systems shall not be used except where approved.
Protection criteria developed from the fire modeling or full-scale fire testing conducted at a testing laboratory listed in rule 1301:7-7-01 of the Administrative Code are allowed in lieu of the protection as shown in Tables 5704.3.6.3(2) to 5704.3.6.3(7) and Table 5704.3.7.5.1 of this rule where approved.
Table 5704.3.7.5.1
Automatic AFFF-water protection requirements for solid-pile and palletized storage of liquids in metal containers of 5-gallon capacity or lessa,b
Package type |
Class liquid |
Ceiling sprinkler design and demand |
Storage height (feet) |
Hose demand (gpm)c |
Duration AFFF supply (minimum) |
Duration water supply (hours) |
||||
Density (gpm/ft2) |
Area (square feet) |
Temperature rating |
Maximum spacing |
Orifice size (inch) |
||||||
Cartoned |
IB, IC, II and III |
0.40 |
2,000 |
286ºF |
100 ft2/head |
0.531 |
11 |
500 |
15 |
2 |
Uncartoned |
IB, IC, II and III |
0.30 |
2,000 |
286ºF |
100 ft2/head |
0.5 or 0.531 |
12 |
500 |
15 |
2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m2,ºC. = [(ºF)-32]/ 1.8.
a. System shall be a closed-head wet system with approved devices for proportioning aqueous film-forming foam.
b. Maximum ceiling height of 30 feet.
c. Hose stream demand includes 11/2-inch inside hose connections, where required.
Not less than one portable fire extinguisher having a rating of not less than 20-B shall be located outside of, but not more than 10 feet (3048 mm) from, the door opening into a liquid storage room.
Automatic foam water systems and automatic AFFF water sprinkler systems shall not be used except where approved.
Protection criteria developed from fire modeling or full-scale fire testing conducted at a testing laboratory listed in rule 1301:7-7-01 of the Administrative Code are allowed in lieu of the protection as shown in Tables 5704.3.6.3(2) to 5704.3.6.3(7) and Table 5704.3.7.5.1 of this rule where approved.
Table 5704.4.2
Outdoor liquid storage in closed containers and portable tanks
Class of liquid |
Closed container storage-maximum per pile |
Portable tank storage-maximum per pile |
Minimum distance between piles or racks (feet) |
Minimum distance to lot line of property that can be built uponc,d (feet) |
Minimum distance to public street, public alley or public wayd (feet) |
||
Quantitya,b (gallons) |
Height (feet) |
Quantitya,b (gallons) |
Height (feet) |
||||
IA |
1,100 |
10 |
2,200 |
7 |
5 |
50 |
10 |
IB |
2,200 |
12 |
4,400 |
14 |
5 |
50 |
10 |
IC |
4,400 |
12 |
8,800 |
14 |
5 |
50 |
10 |
II |
8,800 |
12 |
17,600 |
14 |
5 |
25 |
5 |
III |
22,000 |
18 |
44,000 |
14 |
5 |
10 |
5 |
For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L.
a. For mixed class storage, see paragraph (D)(4)(b)(5704.4.2) of this rule.
b. For storage in racks, the quantity limits per pile do not apply, but the rack arrangement shall be limited to not more than 50 feet in length and two rows or 9 feet in depth.
c. If protection by a public fire department or private fire brigade capable of providing cooling water streams is not available, the distance shall be doubled.
d. When the total quantity stored does not exceed 50 per cent of the maximum allowed per pile, the distances are allowed to be reduced 50 per cent, but not less than 3 feet.
The quantity of liquids stored adjacent to a building protected in accordance with paragraph (D)(4)(b)(iv)(b)(5704.4.2.4) of this rule is allowed to exceed 1,100 gallons (4163 L), provided that the maximum quantity per pile does not exceed 1,100 gallons (4163 L) and each pile is separated by a 10-foot-minimum 3048 mm) clear space along the common wall.
Where the quantity stored exceeds 1,100 gallons (4163 L) adjacent to a building complying with paragraph (D)(4)(b)(iv)(a)(5704.4.2.4) of this rule, or the provisions of paragraph (D)(4)(b)(iv)(a)(5704.4.2.4) of the rule cannot be met, a minimum distance in accordance with Table 5704.4.2 of this rule column 7 ("Minimum distance to lot line of property that can be built upon") shall be maintained between buildings and the nearest closed container or portable tank.
Exception: Closed containers stored on containment pallets in accordance with paragraph (D)(2)(c)(5004.2.3) of rule 1301:7-7-50 of the Administrative Code and closed containers stored in cabinets and lockers with integral spill containment.
(E) Section 5705 Dispensing, use, mixing and handling
Exception: Containers of organic coatings having no fire point and which are opened for pigmentation are not required to comply with this paragraph.
Exception: Air transfer of Class II and Class III liquids at temperatures below their flash points.
Exception: Liquids in original shipping containers not exceeding 5.3 -gallon (20 L) capacity.
Exception: Where such devices are impractical, approved automatic or manually controlled fire-extinguishing devices shall be provided.
Exception: Operation in single-family dwellings.
Exception: Where the exterior wall facing the adjoining lot line is a blank wall having a fire-resistance rating of not less than 4 hours, the fire code official is authorized to modify the distances. The distance shall be not less than that set forth in the building code as listed in rule 1301:7-7-80 of the Administrative Code, and where Class IA or unstable liquids are involved, explosion control shall be provided in accordance with paragraph (K)(911) of rule 1301:7-7-09 of the Administrative Code.
Table 5705.3.4(1)
Separation of processing vessels from lot lines
Processing vessels with emergency relief venting |
Locationa |
|
Stable liquids |
Unstable liquids |
|
Not in excess of 2.5 psig |
Table 5705.3.4(2) of this rule |
2.5 times Table 5705.3.4(2) of this rule |
Over 2.5 psig |
1.5 times Table 5705.3.4(2) of this rule |
4 times Table 5705.3.4(2) of this rule |
For SI: 1 pound per square inch gauge = 6.895 kPa.
a. Where protection of exposures by a public fire department or private fire brigade capable of providing cooling water streams on structures is not provided, distances shall be doubled.
Table 5705.3.4(2)
Reference table for use with Table 5705.3.4(1) of this rule
Tank capacity (gallons) |
Minimum distance from lot line of a lot which is or can be built upon, including the opposite side of a public way (feet) |
Minimum distance from nearest side of any public way or from nearest important building on the same property (feet) |
275 or less |
5 |
5 |
276 to 750 |
10 |
5 |
751 to 12,000 |
15 |
5 |
12,001 to 30,000 |
20 |
5 |
30,001 to 50,000 |
30 |
10 |
50,001 to 100,000 |
50 |
15 |
100,001 to 500,000 |
80 |
25 |
500,001 to 1,000,000 |
100 |
35 |
1,000,001 to 2,000,000 |
135 |
45 |
2,000,001 to 3,000,000 |
165 |
55 |
3,000,001 or more |
175 |
60 |
For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L.
Exception: Cleaning with Class I, II and IIIA liquids shall be in accordance with paragraph (E)(3)(f)(5705.3.6) of this rule.
Use of hazardous production material flammable and combustible liquids in Group H-5 occupancies shall be in accordance with rule 1301:7-7-50 of the Administrative Code.
Exception: Cleaning with Class I, II or IIIA liquids shall be in accordance with paragraph (E)(3)(f)(5705.3.6) of this rule.
Exceptions:
Exception: Materials used in commercial and industrial process-related cleaning operations in accordance with other provisions of this code and not involving facilities maintenance cleaning operations.
Where required by paragraph (E)(3)(e)(iii)(5705.3.5.3) or (E)(3)(f)(i)(5705.3.6.1) of this rule, rooms or buildings used for use, dispensing or mixing of flammable and combustible liquids in quantities exceeding the maximum allowable quantity per control area shall be in accordance with paragraphs (E)(3)(g)(i)(5705.3.7.1) to (E)(3)(g)(vi)(c)(5705.3.7.6.3) of this rule.
Exception: Where natural ventilation can be shown to be effective for the materials used, dispensed or mixed.
Dispensing of flammable and combustible liquids at motor fuel-dispensing facilities shall be in accordance with rule 1301:7-7-23 of the Administrative Code.
Exceptions:
Table 5705.3.8.2
Maximum allowable quantities for dispensing of flammable and combustible liquids in outdoor control areasa, b
Class of liquid |
Quantity (gallons) |
Flammable Class IA Class IB Class IC Combination Class IA, IB and IC |
10 15 20 30c |
Combustible Class II Class IIIA Class IIIB |
30 80 3,300 |
For SI: 1 gallon = 3.785 L.
a. For definition of "Outdoor Control Area," see paragraph (B) of rule 1301:7-7-2 of the Administrative Code.
b. The fire code official is authorized to impose special conditions regarding locations, types of containers, dispensing units, fire control measures and other factors involving fire safety.
c. Containing not more than the maximum allowable quantity per control area of each individual class.
Exception: In refineries and distilleries.
Exceptions:
Exception: Appliances listed for the distillation of unstable (reactive) solvents.
Exception: Facilities may install and use automatically activated alcohol based handrub dispensing devices only in compliance with paragraph (E)(5)( 5705.5) of this rule and as follows:
(F) Section 5706 Special operations
Exception: Storage and use of fuel oil and containers connected with oil-burning equipment regulated by paragraph (C)(603) of rule 1301:7-7-06 of the Administrative Code and the mechanical code as listed in rule 1301:7-7-80 of the Administrative Code.
Discharge devices shall be of a type that do not develop an internal pressure on the container. Pumping devices or approved self-closing faucets used for dispensing liquids shall not leak and shall be well-maintained. Individual containers shall not be interconnected and shall be kept closed when not in use.
Containers stored outside of buildings shall be in accordance with paragraph (D)(5704) of this rule and the building code as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Permanent above-ground tanks of greater capacity which meet the requirements of paragraph (D)(2)( 5704.2) of this rule.
Emergency vents shall be in accordance with paragraph (D)(2)(g)(iv)(5704.2.7.4) of this rule. Emergency vents shall be arranged to discharge in a manner that prevents localized overheating or flame impingement on any part of the tank in the event that vapors from such vents are ignited.
The gravity discharge outlet shall be provided with an approved hose equipped with a self-closing valve at the discharge end of a type that can be padlocked to its hanger.
Exception: Marine motor fuel-dispensing facilities in accordance with rule 1301:7-7-23 of the Administrative Code.
Exception: The dispensing of diesel fuel at a terminal or bulk plant into a motor vehicle that is transporting petroleum products or equipment essential to the operation of the terminal or bulk plant, provided that the motor vehicle is owned or leased by or operated under a contract with a person who has been issued a motor fuel dealers license under section 5735.02 of the Revised Code. For such dispensing, the provisions of this rule governing capacity limitations shall not apply.
Protection shall consist of metallic bond wire permanently electrically connected to the fill stem. The fill pipe assembly shall form a continuous electrically conductive path downstream from the point of bonding. The free end of such bond wire shall be provided with a clamp or equivalent device for convenient attachment to a metallic part in electrical contact with the cargo tank of the tank vehicle or tank car. For tank vehicles, protection shall consist of a flexible bond wire of adequate strength for the intended service and the electrical resistance shall not exceed 1 megohm. For tank cars, bonding shall be provided where the resistance of a tank car to ground through the rails is 25 ohms or greater.
Such bonding connection shall be fastened to the vehicle, car or tank before dome covers are raised and shall remain in place until filling is complete and all dome covers have been closed and secured.
Exceptions:
Filling through open domes into the tanks of tank vehicles or tank cars that contain vapor-air mixtures within the flammable range, or where the liquid being filled can form such a mixture, shall be by means of a downspout which extends to near the bottom of the tank.
When top loading a tank vehicle with vapor control, flow control shall be in accordance with paragraph (F)(5)(a)(x)(5706.5.1.10) of this rule. Self-closing valves shall not be tied or locked in the open position.
Exception: Tank vehicles are allowed under weather protection canopies and canopies of automobile motor vehicle fuel-dispensing stations.
Exceptions:
Exception: Where unloading is performed with a pump deriving its power from the tank vehicle motor.
Devices shall relieve to other portions of the system or to another approved location.
Exception: When unloading is performed with a pump deriving its power from the tank vehicle motor.
Exceptions:
Exception: In cases of accident, breakdown or other emergencies, tank vehicles are allowed to be parked and left unattended at any location while the operator is obtaining assistance.
Exceptions:
During unloading of the tank vehicle, the portable fire extinguisher shall be out of the carrying device on the vehicle and shall be 15 feet (4572 mm) or more from the unloading valves.
Exceptions:
Exception: For tanks, venting shall comply with paragraph (D)(2)(g)(iii)(5704.2.7.3) of this rule.
Replaces: 1301:7-7-57