Current through all regulations passed and filed through September 16, 2024
(A)
Section 5501
General
(1)
5501.1 Scope. Storage, use and handling of cryogenic fluids
shall comply with this rule and NFPA 55 as listed in rule
1301:7-7-80
of the Administrative Code. Cryogenic fluids classified as hazardous materials
shall also comply with the general requirements of rule
1301:7-7-50
of the Administrative Code. Partially full containers containing residual
cryogenic fluids shall be considered as full for the purposes of the controls
required.
Exceptions:
1.
Fluids used as
refrigerants in refrigeration systems (see paragraph (F)(606) of rule
1301:7-7-06
of the Administrative Code.)
2.
Liquefied natural
gas (LNG), which shall comply with NFPA 59A as listed in rule
1301:7-7-80
of the Administrative Code.
Oxidizing cryogenic fluids, including
oxygen, shall comply with rule
1301:7-7-63
of the Administrative Code, as applicable.
Flammable cryogenic fluids, including
hydrogen, methane and carbon monoxide, shall comply with rules
1301:7-7-23
and
1301:7-7-58
of the Administrative Code, as applicable.
Inert cryogenic fluids, including
argon, helium and nitrogen, shall comply with ANSI/CGA P-18 as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
5501.2 Permits.
Permits shall be required as set forth in rule
1301:7-7-01
of the Administrative Code.
(B)
Section 5502
Definitions
(1)
5502.1 Definitions. The following terms are defined in rule
1301:7-7-02 of the
Administrative Code.
"Cryogenic container."
"Cryogenic fluid."
"Cryogenic vessel."
"Flammable cryogenic
fluid."
"Low-pressure
tank."
(C)
Section 5503 General requirements
(1)
5503.1
Containers. Containers employed for storage or use of cryogenic fluids shall
comply with paragraphs (C)(1)(a)(550311) to (C)(1)(c)(ii)(5503 1.3.2) of this
rule and rule
1301:7-7-50
of the Administrative Code.
(a)
5503.1.1 Nonstandard containers. Containers, equipment
and devices that are not in compliance with recognized standards for design and
construction shall be approved upon presentation of satisfactory evidence that
they are designed and constructed for safe operation.
(i)
5503.1.1.1 Data
submitted for approval. The following data shall be submitted to the fire code
official with reference to the deviation from the recognized standard with the
application for approval.
(a)
Type and use of container, equipment or
device.
(b)
Material to be stored, used or
transported.
(c)
Description showing dimensions and materials used in
construction.
(d)
Design pressure, maximum operating pressure and test
pressure.
(e)
Type, size and setting of pressure relief
devices.
(f)
Other data requested by the fire code
official.
(b)
5503.1.2 Concrete
containers. Concrete containers shall be built in accordance with the building
code as listed in rule
1301:7-7-80
of the Administrative Code. Barrier materials and membranes used in connection
with concrete, but not functioning structurally, shall be compatible with the
materials contained.
(c)
5503.1.3 Foundations and supports. Containers shall be
provided with substantial concrete or masonry foundations, or structural steel
supports on firm concrete or masonry foundations. Containers shall be supported
to prevent the concentration of excessive loads on the supporting portion of
the shell. Foundations for horizontal containers shall be constructed to
accommodate expansion and contraction of the container. Foundations shall be
provided to support the weight of vaporizers or heat exchangers.
(i)
5503.1.3.1
Temperature effects. Where container foundations or supports are subject to
exposure to temperatures below -130°F (-90°C), the foundations or supports
shall be constructed of materials to withstand the low-temperature effects of
cryogenic fluid spillage.
(ii)
5503.1.3.2
Corrosion protection. Portions of containers in contact with foundations or
saddles shall be painted to protect against corrosion.
(2)
5503.2 Pressure relief devices. Pressure relief devices
shall be provided in accordance with paragraphs (C)(2)(a)(5503.2.1) to
(C)(2)(g)(5503.2.7) of this rule to protect containers and systems containing
cryogenic fluids from rupture in the event of overpressure. Pressure relief
devices shall be designed in accordance with CGA S- 1.1, CGA S- 1.2 and CGA S-
1.3 as listed in rule
1301:7-7-80
of the Administrative Code.
(a)
5503.2.1 Containers. Containers shall be provided with
pressure relief devices.
(b)
5503.2.2 Vessels or equipment other than containers.
Heat exchangers, vaporizers, insulation casings surrounding containers, vessels
and coaxial piping systems in which liquefied cryogenic fluids could be trapped
because of leakage from the primary container shall be provided with a pressure
relief device.
(c)
5503.2.3 Sizing. Pressure relief devices shall be sized
in accordance with the specifications to which the container was fabricated.
The relief device shall have sufficient capacity to prevent the maximum design
pressure of the container or system from being exceeded.
(d)
5503.2.4
Accessibility. Pressure relief devices shall be located such that they are
provided with ready access for inspection and repair.
(e)
5503.2.5
Arrangement. Pressure relief devices shall be arranged to discharge
unobstructed to the open air in such a manner as to prevent impingement of
escaping gas on personnel, containers, equipment and adjacent structures or to
enter enclosed spaces.
Exception: DOTn-specified containers
with an internal volume of 2 cubic feet ( 0.057 m3)
or less.
(f)
5503.2.6 Shutoffs between pressure relief devices and
containers. Shutoff valves shall not be installed between pressure relief
devices and containers.
Exceptions:
1.
A shutoff valve is
allowed on containers equipped with multiple pressure relief device
installations where the arrangement of the valves provides the full required
flow through the minimum number of required relief devices at all
times.
2.
A locking-type shutoff valve is allowed to be used
upstream of the pressure relief device for service-related work performed by
the supplier when in accordance with the requirements of the ASME Boiler and
Pressure Vessel Code as listed in rule
1301:7-7-80
of the Administrative Code.
(g)
5503.2.7
Temperature limits. Pressure relief devices shall not be subjected to cryogenic
fluid temperatures except when operating.
(3)
5503.3 Pressure
relief vent piping. Pressure relief vent-piping systems shall be constructed
and arranged so as to remain functional and direct the flow of gas to a safe
location in accordance with paragraphs (C)(3)(a)(5503.3.1) and
(C)(3)(b)(5503.3.2) of this rule.
(a)
5503.3.1 Sizing. Pressure relief device vent piping
shall have a cross- sectional area not less than that of the pressure relief
device vent opening and shall be arranged so as not to restrict the flow of
escaping gas.
(b)
5503.3.2 Arrangement. Pressure relief device vent
piping and drains in vent lines shall be arranged so that escaping gas will
discharge unobstructed to the open air and not impinge on personnel,
containers, equipment and adjacent structures or enter enclosed spaces.
Pressure relief device vent lines shall be installed in such a manner to
exclude or remove moisture and condensation and prevent malfunction of the
pressure relief device because of freezing or ice
accumulation.
(4)
5503.4 Marking. Cryogenic containers and systems shall
be marked in accordance with paragraphs (C)(4)(a)(5503.4.1) to
(C)(4)(f)(5503.4.6) of this rule.
(a)
5503.4.1 Identification signs. Visible hazard
identification signs in accordance with NFPA 704 as listed in rule
1301:7-7-80
of the Administrative Code shall be provided at entrances to buildings or areas
in which cryogenic fluids are stored, handled or used.
(b)
5503.4.2
Identification of contents. Stationary and portable containers shall be marked
with the name of the gas contained. Stationary above-ground containers shall be
placarded in accordance with paragraphs (C)(5)( 5003.5) and (C)(6)( 5003.6)
of rule
1301:7-7-50
of the Administrative Code. Portable containers shall be identified in
accordance with CGA C-7 as listed in rule
1301:7-7-80
of the Administrative Code.
(c)
5503.4.3
Identification of containers. Stationary containers shall be identified with
the manufacturing specification and maximum allowable working pressure with a
permanent nameplate. The nameplate shall be installed on the container in an
accessible location. The nameplate shall be marked in accordance with the ASME
Boiler and Pressure Vessel Code or DOTn 49 CFR Parts 100-185 as listed in rule
1301:7-7-80
of the Administrative Code.
(d)
5503.4.4
Identification of container connections. Container inlet and outlet
connections, liquid-level limit controls, valves and pressure gauges shall be
identified in accordance with one of the following:
(i)
Marked with a
permanent tag or label identifying the function.
(ii)
Identified by a
schematic drawing that portrays the function and designates whether connected
to the vapor or liquid space of the container.
Where a schematic drawing is provided,
it shall be attached to the container and maintained in a legible
condition.
(e)
5503.4.5
Identification of piping systems. Piping systems shall be identified in
accordance with ASME A 13.1 as listed in rule
1301:7-7-80
of the Administrative Code.
(f)
5503.4.6
Identification of emergency shutoff valves. Emergency shutoff valves shall be
identified and the location shall be clearly visible and indicated by means of
a sign.
(5)
5503.5 Security. Cryogenic containers and systems shall
be secured against accidental dislodgment and against access by unauthorized
personnel in accordance with paragraphs (C)(5)(a)(5503.5.1) to
(C)(5)(d)(5503.5.4) of this rule.
(a)
5503.5.1 Security of areas. Containers and systems
shall be secured against unauthorized entry and safeguarded in an approved
manner.
(b)
5503.5.2 Securing of containers. Stationary containers
shall be secured to foundations in accordance with the building code as listed
in rule
1301:7-7-80
of the Administrative Code. Portable containers subject to shifting or upset
shall be secured. Nesting shall be an acceptable means of securing
containers.
(c)
5503.5.3 Securing of vaporizers. Vaporizers, heat
exchangers and similar equipment shall be anchored to a suitable foundation and
its connecting piping shall be sufficiently flexible to provide for the effects
of expansion and contraction due to temperature changes.
(d)
5503.5.4 Physical
protection. Containers, piping, valves, pressure relief devices, regulating
equipment and other appurtenances shall be protected against physical damage
and tampering.
(6)
5503.6 Electrical wiring and equipment. Electrical
wiring and equipment shall comply with NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code and paragraphs (C)(6)(a)(5503.6.1) and
(C)(6)(b)(5503.6.2) of this rule.
(a)
5503.6.1 Location. Containers and systems shall not be
located where they could become part of an electrical circuit.
(b)
5503.6.2
Electrical grounding and bonding. Containers and systems shall not be used for
electrical grounding. Where electrical grounding and bonding is required, the
system shall comply with NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code. The grounding system shall be protected against
corrosion, including corrosion caused by stray electric
currents.
(7)
5503.7 Service and repair. Service, repair,
modification or removal of valves, pressure relief devices or other container
appurtenances shall comply with paragraphs (C)(7)(a)(5503.7.1) and
(C)(7)(b)(5503.7.2) of this rule and the ASME Boiler and Pressure Vessel Code,
Section VIII or DOTn 49 CFR Parts 100-185 as listed in rule
1301:7-7-80
of the Administrative Code.
(a)
5503.7.1 Containers. Containers that have been removed
from service shall be handled in an approved manner.
(b)
5503.7.2 Systems.
Service and repair of systems shall be performed by trained
personnel.
(8)
5503.8 Unauthorized use. Containers shall not be used
for any purpose other than to serve as a vessel for containing the product that
it is designed to contain.
(9)
5503.9 Leaks,
damage and corrosion. Leaking, damaged or corroded containers shall be removed
from service. Leaking, damaged or corroded systems shall be replaced, repaired
or removed in accordance with paragraph (C)(7)( 5503.7) of this
rule.
(10)
5503.10 Lighting. Where
required, lighting, including emergency lighting, shall be provided for fire
appliances and operating facilities such as walkways, control valves and gates
ancillary to stationary containers.
(D)
Section 5504
Storage
(1)
5504.1 General. Storage of containers shall comply with this
paragraph.
(2)
5504.2 Indoor storage. Indoor storage of containers
shall be in accordance with paragraphs (D)(2)(a)(5504.2.1) to
(D)(2)(b)(iii)(5504.2.2.3) of this rule.
(a)
5504.2.1
Stationary containers. Stationary containers shall be installed in accordance
with the provisions applicable to the type of fluid stored and this
paragraph.
(i)
5504.2.1.1 Containers. Stationary containers shall comply
with paragraph (C)(1)(55031) of this rule.
(ii)
5504.2.1.2
Construction of indoor areas. Cryogenic fluids in stationary containers stored
indoors shall be located in buildings, rooms or areas constructed in accordance
with the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(iii)
5504.2.1.3
Ventilation. Storage areas for stationary containers shall be ventilated in
accordance with the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
5504.2.2 Portable
containers. Indoor storage of portable containers shall comply with the
provisions applicable to the type of fluid stored and paragraphs
(D)(2)(b)(i)(5504.2.2.1) to (D)(2)(b)(iii)(5504.2.2.3) of this rule.
(i)
5504.2.2.1
Containers. Portable containers shall comply with paragraph (C)(1)(55031) of
this rule.
(ii)
5504.2.2.2 Construction of indoor areas. Cryogenic
fluids in portable containers stored indoors shall be stored in buildings,
rooms or areas constructed in accordance with the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(iii)
5504.2.2.3
Ventilation. Storage areas shall be ventilated in accordance with the
mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
(3)
5504.3 Outdoor
storage. Outdoor storage of containers shall be in accordance with paragraphs
(D)(3)(a)(5504.3.1) to (D)(3)(a)(ii)(c)(5504.3.1.2.3) of this rule.
(a)
5504.3.1
Separation from hazardous conditions. Cryogenic containers and systems in
outdoor storage shall be separated from materials and conditions that pose
exposure hazards to or from each other in accordance with paragraphs
(D)(3)(a)(i)(5504.3.1.1) to (D)(3)(a)(i)(e)(5504.3.1.1.5) of this rule.
(i)
5504.3.1.1
Stationary containers. Stationary containers shall be separated from exposure
hazards in accordance with the provisions applicable to the type of fluid
contained and the minimum separation distances indicated in Table 5504.3.1.1 of
this rule.
Table 5504.3.1.1 Separation of
stationary containers from exposure hazards
Exposure |
Minimum distance
(feet) |
Buildings, regardless of
construction type |
1 |
Building exits
|
10 |
Wall openings
|
1
|
Air intakes |
10 |
Lot lines |
5 |
Places of public
assembly |
50 |
Nonambulatory patient
areas |
50 |
Combustible materials such as
paper, leaves, weeds, dry grass or debris
|
15 |
Other hazardous
materials |
In accordance with rule
1301:7-7-50
of the Administrative Code
|
(a)
5504.3.1.1.1 Point-of-fill connections. Remote transfer
points and fill connection points shall not be positioned closer to exposures
than the minimum distances required for stationary containers.
(b)
5504.3.1.1.2
Surfaces beneath containers. Containers shall be placed on surfaces that are
compatible with the fluid in the container.
(c)
5504.3.1.1.3
Location. Containers of cryogenic fluids shall not be located within diked
areas containing other hazardous materials.
(d)
5504.3.1.1.4
Areas subject to flooding. Stationary containers located in areas subject to
flooding shall be securely anchored or elevated to prevent the containers from
separating from foundations or supports.
(e)
5504.3.1.1.5
Drainage. The area surrounding stationary
containers shall be provided with a means to prevent
accidental discharge of fluids from endangering personnel, containers,
equipment and adjacent structures or to enter enclosed spaces. The stationary
container shall not be placed where spilled or discharged fluids will be
retained around the container.
Exception: These provisions shall not
apply where it is determined by the fire code official that the container does
not constitute a hazard, after consideration of special features such as
crushed rock utilized as a heat sink, topographical conditions, nature of
occupancy, proximity to structures on the same or adjacent property, and the
capacity and construction of containers and character of fluids to be
stored.
(ii)
5504.3.1.2 Outdoor storage of portable containers.
Outdoor storage of portable containers shall comply with paragraph (C)(5503) of
this rule and paragraphs (D)(3)(a)(ii)(a)(55043.1.2.1) to
(D)(3)(a)(ii)(c)(5504.3.1.2.3) of this rule.
(a)
5504.3.1.2.1
Exposure hazard separation. Portable containers in outdoor storage shall be
separated from exposure hazards in accordance with Table 5504.3.1.2.1 of this
rule.
Table 5504.3.1.2.1 Separation of
portable containers from exposure hazards
Exposure |
Minimum distance
(feet) |
Building
exits |
10 |
Wall openings |
1 |
Air intakes |
10 |
Lot lines |
5 |
Combustible materials such as
paper, leaves, weeds, dry grass or debris
|
15 |
Other hazardous
materials |
In accordance with rule
1301:7-7-50
of the Administrative Code
|
For SI: 1 foot = 304.8
(b)
5504.3.1.2.2 Surfaces beneath containers. The surface
of the area on which stationary containers are placed, including the surface of
the area located below the point where connections are made for the purpose of
filling such containers, shall be compatible with the fluid in the
container.
(c)
5504.3.1.2.3 Drainage. The area surrounding portable
containers shall be provided with a means to
prevent accidental discharge of fluids from endangering adjacent containers,
buildings, equipment or adjoining property.
Exception: These provisions shall not
apply where it is determined by the fire code official that the container does
not constitute a hazard.
(E)
Section 5505 Use
and handling
(1)
5505.1 General. Use and handling of cryogenic fluid
containers and systems shall comply with paragraphs (E)(1)(a)(5505.1.1) to
(E)(5)(b)(5505.5.2) of this rule.
(a)
5505.1.1 Cryogenic fluid systems. Cryogenic fluid
systems shall be suitable for the use intended and designed by persons
competent in such design. Equipment, machinery and processes shall be listed or
approved.
(b)
5505.1.2 Piping systems. Piping, tubing, valves and
joints and fittings conveying cryogenic fluids shall be installed in accordance
with the material-specific provisions of paragraphs (A)(1)(5501 1) and
(E)(1)(b)(i)(5505.1.2.1) to (E)(1)(b)(vi)(5505 1.2 6) of this rule.
(i)
5505.1.2.1 Design
and construction. Piping systems shall be suitable for the use intended through
the full range of pressure and temperature to which they will be subjected.
Piping systems shall be designed and constructed to provide adequate allowance
for expansion, contraction, vibration, settlement and fire
exposure.
(ii)
5505.1.2.2 Joints. Joints on container piping and
tubing shall be threaded, welded, silver brazed or flanged.
(iii)
5505.1.2.3
Valves and accessory equipment. Valves and accessory equipment shall be
suitable for the intended use at the temperatures of the application and shall
be designed and constructed to withstand the maximum pressure at the minimum
temperature to which they will be subjected.
(a)
5505.1.2.3.1
Shutoff valves on containers. Shutoff valves shall be provided on all container
connections except for pressure relief devices. Shutoff valves shall be
provided with access thereto and located as close as practical to the
container.
(b)
5505.1.2.3.2
Shutoff valves on piping. Shutoff valves shall be installed in piping
containing cryogenic fluids where needed to limit the volume of liquid
discharged in the event of piping or equipment failure. Pressure relief valves
shall be installed where liquid is capable of being trapped between shutoff
valves in the piping system (see paragraph (C)(2)( 5503.2) of this
rule).
(iv)
5505.1.2.4 Physical protection and support. Piping
systems shall be supported and protected from physical damage. Piping passing
through walls shall be protected from mechanical damage.
(v)
5505.1.2.5
Corrosion protection. Above-ground piping that is subject to corrosion because
of exposure to corrosive atmospheres, shall be constructed of materials to
resist the corrosive environment or otherwise protect against corrosion.
Below-ground piping shall be protected against corrosion.
(vi)
5505.1.2.6
Testing. Piping systems shall be tested and proven free of leaks after
installation as required by the standards to which they were designed and
constructed. Test pressures shall be not less than 150 per cent of the maximum
allowable working pressure where hydraulic testing is conducted or 110 per cent
where testing is conducted pneumatically.
(2)
5505.2 Indoor
use. Indoor use of cryogenic fluids shall comply with the material- specific
provisions of paragraph (A)(1)(5501 1) of this rule.
(3)
5505.3 Outdoor
use. Outdoor use of cryogenic fluids shall comply with the material specific
provisions of paragraphs (A)(1)(5501 1), (E)(3)(a)(5505 31) and
(E)(3)(b)(5505.3.2) of this rule.
(a)
5505.3.1 Separation. Distances from lot lines,
buildings and exposure hazards shall comply with paragraph (D)(3)( 5504.3) of
this rule and the material specific provisions of paragraph (A)(1)(5501 1) of
this rule.
(b)
5505.3.2 Emergency shutoff valves. Manual or automatic
emergency shutoff valves shall be provided to shut off the cryogenic fluid
supply in case of emergency. An emergency shutoff valve shall be located at the
source of supply and at the point where the system enters the
building.
(4)
5505.4 Filling and dispensing. Filling and dispensing
of cryogenic fluids shall comply with paragraphs (E)(4)(a)( 5505.4. to
(E)(4)(c)(5505 4.3) of this rule.
(a)
5505.4.1 Dispensing areas. Dispensing of cryogenic
fluids with physical or health hazards shall be conducted in approved
locations. Dispensing indoors shall be conducted in areas constructed in
accordance with the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(i)
5505.4.1.1 Ventilation. Indoor areas where cryogenic
fluids are dispensed shall be ventilated in accordance with the requirements of
the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code in a manner that captures any vapor at the point of
generation.
Exception: Cryogenic fluids that can be
demonstrated not to create harmful vapors.
(ii)
5505.4.1.2
Piping systems. Piping systems utilized for filling or dispensing of cryogenic
fluids shall be designed and constructed in accordance with paragraph
(E)(1)(b)(5505 1.2) of this rule.
(b)
5505.4.2 Vehicle
loading and unloading areas. Loading or unloading areas shall be conducted in
an approved manner in accordance with the standards referenced in paragraph
(A)(1)(5501 1) of this rule.
(c)
5505.4.3 Limit
controls. Limit controls shall be provided to prevent overfilling of stationary
containers during filling operations.
(5)
5505.5 Handling.
Handling of cryogenic containers shall comply with paragraphs (E)(5)(a)( 5505.5
1) and (E)(5)(b)(5505.5.2) of this rule.
(a)
5505.5.1 Carts
and trucks. Cryogenic containers shall be moved using an approved method. Where
cryogenic containers are moved by hand cart, hand truck or other mobile device,
such carts, trucks or devices shall be designed for the secure movement of the
container.
Carts and trucks used to transport
cryogenic containers shall be designed to provide a stable base for the
commodities to be transported and shall have a means of restraining containers
to prevent accidental dislodgment.
(b)
5505.5.2 Closed
containers. Pressurized containers shall be transported in a closed condition.
Containers designed for use at atmospheric conditions shall be transported with
appropriate loose fitting covers in place to prevent spillage.
Replaces: 1301:7-7-32.