Current through all regulations passed and filed through September 16, 2024
(A)
Section 2901
General
(1)
2901.1 Scope. Organic coating manufacturing processes shall
comply with this rule except that this rule shall not apply to processes
manufacturing nonflammable or water-thinned coatings or to operations applying
coating materials.
(2)
2901.2 Permits. Permits shall be required as set forth
in rule
1301:7-7-01
of the Administrative Code.
(3)
2901.3
Maintenance. Structures and their service equipment shall be maintained in
accordance with this code and NFPA 35 as listed in rule
1301:7-7-80
of the Administrative Code.
(B)
Section 2902
Definition
(1)
2902.1 Definition. The following term is defined in rule
1301:7-7-02 of the
Administrative Code.
"Organic coating."
(C)
Section 2903 General precautions
(1)
2903.1 Building
features. Manufacturing of organic coatings shall be done only in buildings
that do not have pits or basements.
(2)
2903.2 Location.
Organic coating manufacturing operations and operations incidental to or
connected with organic coating manufacturing shall not be located in buildings
having other occupancies.
(3)
2903.3 Fire-fighting access. Organic coating
manufacturing operations shall be accessible from not less than one side for
the purpose of fire control. Approved aisles shall be maintained for the
unobstructed movement of personnel and fire suppression
equipment.
(4)
2903.4 Fire protection systems. Fire protection systems
shall be installed, maintained, periodically inspected and tested in accordance
with rule
1301:7-7-09
of the Administrative Code.
(5)
2903.5 Portable
fire extinguishers. Not less than one portable fire extinguisher complying with
paragraph (F)(906) of rule
1301:7-7-09
of the Administrative Code for extra hazard shall be provided in organic
coating areas.
(6)
2903.6 Open flames. Open flames and direct-fired
heating devices shall be prohibited in areas where flammable vapor-air mixtures
exist.
(7)
2903.7 Smoking. Smoking shall be prohibited in
accordance with paragraph (J)(310) of rule
1301:7-7-03
of the Administrative Code.
(8)
2903.8 Power
equipment. Power-operated equipment and industrial trucks shall be of a type
approved for the location.
(9)
2903.9 Tank
maintenance. The cleaning of tanks and vessels that have contained flammable or
combustible liquids shall be performed under the supervision of persons
knowledgeable of the fire and explosion potential.
(a)
2903.9.1 Repairs.
Where necessary to make repairs involving "hot work," the work shall be
authorized by the responsible individual before the work
begins.
(b)
2903.9.2 Empty containers. Empty flammable or
combustible liquid containers shall be removed to a detached, outside location
and, if not cleaned on the premises, the empty containers shall be removed from
the plant as soon as practical.
(10)
2903.10 Drainage. Drainage
facilities shall be provided to direct flammable and combustible liquid leakage
and fire protection water to an approved location away from the building, any
other structure, storage area or adjoining premises.
(11)
2903.11 Alarm system. An
approved fire alarm system shall be provided in accordance with paragraph
(G)(907) of rule
1301:7-7-09
of the Administrative Code.
(D)
Section 2904
Electrical equipment and protection
(1)
2904.1 Wiring and equipment. Electrical wiring and
equipment shall comply with this rule and shall be installed in accordance with
NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
2904.2 Hazardous
locations. Where Class I liquids are exposed to the air, the design of
equipment and ventilation of structures shall be such as to limit the Class I,
Division 1, locations to the following:
1.
Piping
trenches.
2.
The interior of equipment.
3.
The immediate
vicinity of pumps or equipment locations, such as dispensing stations, open
centrifuges, plate and frame filters, opened vacuum filters, change cans and
the surfaces of open equipment. The immediate vicinity shall include a zone
extending from the vapor liberation point 5 feet (1524 mm) horizontally in all
directions and vertically from the floor to a level 3 feet (914 mm) above the
highest point of vapor liberation.
(a)
2904.2.1 Other locations. Locations within the confines
of the manufacturing room where Class I liquids are handled shall be Class I,
Division 2 except locations indicated in paragraph (D)(2)(2904.2) of this
rule.
(b)
2904.2.2 Ordinary equipment. Ordinary electrical
equipment, including switchgear, shall be prohibited except where installed in
a room maintained under positive pressure with respect to the hazardous area.
The air or other media utilized for pressurization shall be obtained from a
source that will not cause any amount or type of flammable vapor to be
introduced into the room.
(3)
2904.3 Bonding.
Equipment including, but not limited to, tanks, machinery and piping shall be
bonded and connected to a ground where an ignitable mixture is capable of being
present.
(a)
2904.3.1 Piping. Electrically isolated sections of metallic
piping or equipment shall be grounded or bonded to the other grounded portions
of the system.
(b)
2904.3.2 Vehicles. Tank vehicles loaded or unloaded
through open connections shall be grounded and bonded to the receiving
system.
(c)
2904.3.3 Containers. Where a flammable mixture is
transferred from one portable container to another, a bond shall be provided
between the two containers, and one shall be grounded.
(4)
2904.4
Ground. Metal framing of buildings shall be grounded with resistance of not
more than 5 ohms.
(E)
Section 2905
Process structures
(1)
2905.1 Design. Process structures shall be designed and
constructed in accordance with the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
2905.2 Fire
apparatus access. Fire apparatus access complying with paragraph (C)(503) of
rule
1301:7-7-05
of the Administrative Code shall be provided for the purpose of fire control to
not less than one side of organic coating manufacturing
operations.
(3)
2905.3 Drainage. Drainage facilities shall be provided
in accordance with paragraph (C)(10)(2903.10) of this rule where
topographical conditions are such that flammable and combustible liquids are
capable of flowing from the organic coating manufacturing operation so as to
constitute a fire hazard to other premises.
(4)
2905.4 Explosion
control. Explosion control shall be provided in areas subject to potential
deflagration hazards as indicated in NFPA 35 as listed in rule
1301:7-7-80
of the Administrative Code. Explosion control shall be provided in accordance
with paragraph (K)(911) of rule
1301:7-7-09
of the Administrative Code.
(5)
2905.5
Ventilation. Enclosed structures in which Class I liquids are processed or
handled shall be ventilated at a rate of not less than 1 cubic foot per minute
per square foot [ 0.00508 m3/
(s. m2)] of solid floor area.
Ventilation shall be accomplished by exhaust fans that take suction at floor
levels and discharge to a safe location outside the structure. Noncontaminated
intake air shall be introduced in such a manner that all portions of solid
floor areas are provided with continuous uniformly distributed air
movement.
(6)
2905.6 Heating. Heating provided in hazardous areas
shall be by indirect means.
Ignition sources such as open flames or
electrical heating elements, except as provided for in paragraph (D)(2904) of
this rule, shall not be permitted within the structure.
(F)
Section 2906 Process mills and kettles
(1)
2906.1 Mills.
Mills, operating with close clearances, which process flammable and
heat-sensitive materials, such as nitrocellulose, shall be located in a
detached building or in a noncombustible structure without other occupancies.
The amount of nitrocellulose or other flammable material brought into the area
shall not be more than the amount required for a batch.
(2)
2906.2 Mixers.
Mixers shall be of the enclosed type or, where of the open type, shall be
provided with properly fitted covers. Where flow is by gravity, a shutoff valve
shall be installed as close as practical to the mixer, and a control valve
shall be provided near the end of the fill pipe.
(3)
2906.3 Open
kettles. Open kettles shall be located in an outside area provided with a
protective roof; in a separate structure of noncombustible construction;
or separated from other areas by a
noncombustible wall having a fire-resistance rating of not less than 2
hours.
(4)
2906.4 Closed kettles. Contact-heated kettles
containing solvents shall be equipped with safety devices that, in case of a
fire, will turn off the process heat, turn on the cooling medium and inject
inert gas into the kettle.
(a)
2906.4.1 Vaporizer location. The vaporizer section of
heat-transfer systems that heat closed kettles containing solvents shall be
remotely located.
(5)
2906.5 Kettle
controls. The kettle and thin-down tank shall be instrumented, controlled and
interlocked so that any failure of the controls will result in a safe
condition. The kettle shall be provided with a pressure-rupture disc in
addition to the primary vent. The vent piping from the rupture disc shall be of
minimum length and shall discharge to an approved location. The thin-down tank
shall be adequately vented. Thinning operations shall be provided with an
adequate vapor removal system.
(G)
Section 2907
Process piping
(1)
2907.1 Design. Piping, valves and fittings shall be
designed for the working pressures and structural stresses to which the piping,
valves and fittings will be subjected, and shall be of steel or other material
approved for the service intended.
(2)
2907.2 Valves.
Valves shall be of an indicating type. Terminal valves on remote pumping
systems shall be of the dead-man type, shutting off both the pump and the flow
of solvent.
(3)
2907.3 Support. Piping systems shall be supported
adequately and protected against physical damage. Piping shall be pitched to
avoid unintentional trapping of liquids, or approved drains shall be
provided.
(4)
2907.4 Connectors. Approved flexible connectors shall
be installed where vibration exists or frequent movement is necessary. Hose at
dispensing stations shall be of an approved type.
(5)
2907.5 Tests.
Before being placed in service, all piping shall be free of leaks when tested
for not less than 30 minutes at not less than 1.5 times the working pressure or
a minimum of 5 pounds per square inch gauge (psig)(35 kPa) at the highest point
in the system.
(H)
Section 2908 Raw materials in process areas
(1)
2908.1
Nitrocellulose quantity. The amount of nitrocellulose brought into the
operating area shall not exceed the amount required for a work shift.
Nitrocellulose spillage shall be promptly swept up and disposed of
properly.
(2)
2908.2 Organic peroxides quantity. Organic peroxides
brought into the operating area shall be in the original shipping container.
When in the operating area, the organic peroxide shall not be placed in
locations exposed to ignition sources, heat or mechanical
shocks.
(I)
Section 2909 Raw materials and finished products
(1)
2909.1 General.
The storage, handling and use of flammable and combustible liquids in process
areas shall be in accordance with rule
1301:7-7-57
of the Administrative Code.
(2)
2909.2 Tank
storage. Tank storage for flammable and combustible liquids located inside of
structures shall be limited to storage areas at or above grade which are
separated from the processing area in accordance with the building code as
listed in rule
1301:7-7-80
of the Administrative Code. Processing equipment containing flammable and
combustible liquids and storage in quantities essential to the continuity of
the operations shall not be prohibited in the processing area.
(3)
2909.3 Tank
vehicle. Tank car and tank vehicle loading and unloading stations for Class I
liquids shall be separated from the processing area, other plant structures,
nearest lot line of property that can be built upon or public thoroughfare by a
minimum clear distance of 25 feet (7620 mm).
(a)
2909.3.1 Loading.
Loading and unloading structures and platforms for flammable and combustible
liquids shall be designed and installed in accordance with rule
1301:7-7-57
of the Administrative Code.
(b)
2909.3.2 Safety.
Tank cars for flammable liquids shall be unloaded such that the safety to
persons and property is ensured. Tank vehicles for flammable and combustible
liquids shall be loaded and unloaded in accordance with rule
1301:7-7-57
of the Administrative Code.
(4)
2909.4
Nitrocellulose storage. Nitrocellulose storage shall be located on a detached
pad or in a separate structure or a room enclosed in accordance with the
building code as listed in rule
1301:7-7-80
of the Administrative Code. The nitrocellulose storage area shall not be
utilized for any other purpose. Electrical wiring and equipment installed in
storage areas adjacent to process areas shall comply with paragraph (D)(2)(
2904.2) of this rule.
(a)
2909.4.1 Containers. Nitrocellulose shall be stored in
closed containers. Barrels shall be stored on end and not more than two tiers
high. Barrels or other containers of nitrocellulose shall not be opened in the
main storage structure but at the point of use or other location intended for
that purpose.
(b)
2909.4.2 Spills. Spilled nitrocellulose shall be
promptly wetted with water and disposed of by use or burning in the open at an
approved detached location.
(5)
2909.5 Organic
peroxide storage. The storage of organic peroxides shall be in accordance with
rule
1301:7-7-62 of
the Administrative Code.
(a)
2909.5.1 Size. The size of the package containing
organic peroxide shall be selected so that, as nearly as practical, full
packages are utilized at one time. Spilled peroxide shall be promptly cleaned
up and disposed of as specified by the supplier.
(6)
2909.6 Finished
products. Finished products that are flammable or combustible liquids shall be
stored outside of structures, in a separate structure, or in a room separated
from the processing area in accordance with the building code as listed in rule
1301:7-7-80
of the Administrative Code. The storage of finished products shall be in tanks
or closed containers in accordance with rule
1301:7-7-57
of the Administrative Code.
Replaces: 1301:7-7-20.