Current through all regulations passed and filed through September 16, 2024
(A)
Section 2301 General
(1)
2301.1
Scope.
Automotive motor fuel-dispensing
facilities, marine motor fuel-dispensing facilities, fleet vehicle motor
fuel-dispensing facilities,
service stations at bulk plants,
aircraft motor-vehicle fuel-dispensing facilities and repair garages shall be
in accordance with this
rule, NFPA 30, NFPA 30A, the
International Fuel Gas Code, the
building code, and the
mechanical code as listed in rule
1301:7-7-80
of the Administrative Code. Such operations shall include both those
that are accessible to the public and private operations.
(a)
2301.1.1.
Notwithstanding paragraphs (B)(1)( 102.1)
and (B)(2)( 102.2) of rule
1301:7-7-01
of the Administrative Code and unless otherwise noted in this rule, the
provisions of this rule shall not apply to facilities, equipment, structures or
installations existing or approved for construction or installation prior to
the effective date of this rule, except in those cases where the fire code
official demonstrates by a preponderance of the evidence that the existing
facility, equipment, structure or installation creates a distinct hazard to
life or adjacent property.
(2)
2301.2
Permits.
Permits shall be required as set
forth in
rule
1301:7-7-01
of the Administrative Code. In accordance with paragraph
(E)(1)(a)(105.1.1)
of rule
1301:7-7-01
of the Administrative Code, permits required for the installation, alteration,
abandonment, removal or to place temporarily out of service a stationary
flammable or combustible liquid storage tank shall be obtained from the fire
marshal when such permits are required by this code and are not issued by
another officer listed in section
3737.14 of the Revised
Code.
Exception:
A stationary flammable or combustible liquid storage tank
with a capacity of 1,100 gallons or less utilized for agricultural
purposes.
(3)
2301.3 Construction documents.
Construction documents shall be submitted for review
and approval prior to the installation or construction of motor fuel-dispensing
facilities, service stations at bulk plants and repair garages
in accordance with paragraph (E)(4)( 105.4) of rule
1301:7-7-01
of the Administrative Code.
(4)
2301.4
Indoor motor fuel-dispensing facilities.
Motor fuel-dispensing facilities located inside buildings
shall comply with the
building code and NFPA 30A
as
listed in rule
1301:7-7-80
of the Administrative Code.
(a)
2301.4.1
Protection of floor openings in indoor motor fuel-dispensing facilities.
Where motor fuel-dispensing facilities are located inside buildings and the
dispensers are located above spaces within the building, openings beneath
dispensers shall be sealed to prevent the flow of leaked fuel to lower building
spaces.
(5)
2301.5 Electrical.
Electrical wiring and equipment shall be suitable for
the locations in which they are installed and shall comply with
paragraph (E)(605) of rule
1301:7-7-06
of the Administrative Code, NFPA 30A, and NFPA 70 as listed in
rule
1301:7-7-80
of the Administrative Code.
(6)
2301.6
Heat-producing appliances.
Heat-producing
appliances shall be suitable for the locations in which they are installed and
shall comply with NFPA 30A and the International Fuel Gas Code or the
mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
(B)
Section
2302 Definitions
(1)
2302.1 Definitions. The following terms
are defined in
rule
1301:7-7-02 of the
Administrative Code.
"Aircraft motor-vehicle
fuel-dispensing facility."
"Alcohol-blended
fuels."
"Automotive motor fuel-dispensing
facility."
"Dispensing device, overhead
type."
"Fleet vehicle motor
fuel-dispensing facility."
"Liquefied natural gas
(LNG)."
"Marine motor fuel-dispensing
facility."
"Motor fuel-dispensing
facility."
"Repair
garage."
"Self-service motor
fuel-dispensing facility."
(2)
2302.2 "Approved" as used in rule 1301:7-7-23
of the Administrative Code.
As used in this rule and
notwithstanding the definition as set forth in rule 1301:7-7-2 of the
Administrative Code, the term "approved", unless otherwise further specified or
defined in this rule, means: listed, labeled or tested for the specified
purpose and documented in research reports from an authoritative source listed
in paragraph (O)(2)( 115.2) of rule
1301:7-7-01
of the Administrative Code, or otherwise acceptable to the fire code
official.
(C)
Section
2303 Location of dispensing devices
(1)
2303.1
Location of dispensing devices.
Dispensing
devices shall be located as follows:
(a)
Ten feet (3048 mm) or more from lot
lines.
(b)
Ten feet (3048 mm) or more from buildings having
combustible exterior wall surfaces or buildings having noncombustible exterior
wall surfaces that are not part of a 1-hour fire-resistance-rated assembly or
buildings having combustible overhangs.
Exception:
Canopies constructed in accordance with the
building code as listed in rule
1301:7-7-80
of the Administrative Code providing weather protection for the fuel
islands.
(c)
Such that all portions of the vehicle being fueled will
be on the premises of the motor-fuel-dispensing facility.
(d)
Such that the
nozzle, when the hose is fully extended, will not reach within 5 feet (1524 mm)
of building openings.
(e)
Twenty feet (6096 mm) or more from fixed sources of
ignition.
(2)
2303.2 Emergency disconnect switches.
An approved, clearly identified and
readily accessible emergency disconnect switch shall be provided at an approved
location to stop the transfer of fuel to the fuel dispensers in the event of a
fuel spill or other emergency. The emergency disconnect switch for exterior
fuel dispensers shall be located outside and within 100 feet
(30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers.
For interior fuel-dispensing operations, the emergency disconnect switch shall
be installed at an approved location. Emergency disconnect
switches shall be distinctly labeled as: "EMERGENCY FUEL SHUTOFF."
Signs shall be provided in approved locations.
(D)
Section
2304 Dispensing operations
(1)
2304.1 Supervision of dispensing.
The dispensing of fuel at motor fuel-dispensing
facilities shall be conducted by a qualified attendant or shall be under the
supervision of a qualified attendant at all times or shall be in accordance
with paragraph (D)(3)( 2304.3) of this
rule.
(2)
2304.2 Attended self-service motor fuel-dispensing
facilities.
Attended self-service motor
fuel-dispensing facilities shall comply with
paragraphs
(D)(2)(a)(2304.2.1)
to (D)(2)(k)(2304.2.11)
of this
rule, NFPA 30A as listed in division (A) of section
3741.14 of the Revised Code, and
the "Occupational Safety and Health Act of 1970" and any amendments thereto or
standards as may be adopted by the state fire marshal pursuant to division (B)
of section 3741.14 of the Revised
Code. Attended self-service motor fuel-dispensing facilities shall
have not less than one qualified attendant on duty while the facility is open
for business. The attendant's primary function shall be to supervise, observe
and control the dispensing of fuel. The attendant shall prevent the dispensing
of fuel into containers that do not comply with
paragraph
(D)(4)(a)(2304.4.1)
of this rule, control sources of ignition,
give immediate attention to accidental spills or releases, and be prepared to
use fire extinguishers.
(a)
2304.2.1 Special-type dispensers.
Special-dispensing devices and systems such as, but not
limited to, card-or coin-operated and remote-preset types, are allowed at
attended self-service motor fuel-dispensing facilities
provided there is not less than one qualified attendant on duty while the
facility is open to the public. Remote preset-type devices shall be set in the
"off" position while not in use so that the dispenser cannot be activated
without the knowledge of the attendant.
(b)
2304.2.2
Emergency controls.
Emergency controls
shall be provided in accordance with paragraph (C)(2)( 2303.2
) of this rule.
(c)
2304.2.3
Operating instructions.
Signs
providing
dispenser operating
instructions shall be conspicuously posted in approved locations on every
dispenser.
(d)
2304.2.4 Obstructions to view.
Dispensing devices shall be in clear view of the
attendant at all times. Obstructions shall not be placed between the dispensing
area and the attendant.
(e)
2304.2.5 Communications.
The attendant shall be able to communicate with persons
in the dispensing area at all times. A telephone or other approved
method of communicating with the fire department shall be provided for the
attendant.
(f)
2304.2.6 Smoking
prohibited.
Gasoline and
other flammable or combustible liquids shall be dispensed only by a person who
is not smoking. Smoking shall be prohibited in the dispensing
area.
(g)
2304.2.7 Signage.
A sign in block letters at least four inches in
height shall be conspicuously displayed on each gasoline pump island where
self-service is offered stating that it is a self-service
island.
(h)
2304.2.8 Signage
material.
All signs required by paragraphs
(D)(2)(c)(2304.2.3), (D)(2)(g)(2304.2.7) and
(D)(3)(e)(2304.3.5) of this rule shall be constructed of rigid,
weather-resistant material.
(i)
2304.2.9 Attendant training.
It shall be the responsibility of the operator of the motor fuel
dispensing facility to see that all attendant employees are properly trained in
handling emergencies of a flammable fuel type.
(j)
2304.2.10 Codes and standards.
It shall be the responsibility of the operator of the motor fuel
dispensing facility to see that all attendant employees read and be familiar
with applicable codes and standards.
(k)
2304.2.11 Dispensing devices.
Existing listed or labeled dispensing devices shall be permitted to be
modified provided that the modifications made are "Listed by Report" by an
approved testing laboratory or as otherwise approved by the fire code official.
Modification proposals shall contain a description of the component parts used
in the modification and the recommended methods of installation on specific
dispensing devices. Modification proposals shall be made available to the fire
code official upon request
(3)
2304.3
Unattended self-service motor fuel-dispensing facilities. Unattended
self-service motor fuel-dispensing facilities shall comply with
paragraphs (D)(3)(a)(2304.3.1)
to
(D)(3)(m)(2304.3.13)
of this rule, NFPA 30A as listed in
division (A)
of section
3741.14 of the Revised Code and
the "Occupational Safety and Health Act of 1970" and any amendments thereto or
standards as may be adopted by the state fire marshal pursuant to
division (B)
of section
3741.14 of the Revised Code.
This paragraph shall not apply to an unattended fleet vehicle motor fuel
dispensing facility.
(a)
2304.3.1 General.
Where approved, unattended self-service motor
fuel-dispensing facilities are allowed. As a condition of approval, the owner
or operator shall provide, and be accountable for, daily site visits, regular
equipment inspection and maintenance.
(b)
2304.3.2
Dispensers.
Dispensing devices shall
comply with paragraph (F)(7)( 2306.7) of this rule.
Only card operated dispensing devices approved by authoritative sources listed
in rule
1301:7-7-01
of the Administrative Code shall be used. Dispensing devices operated
by the insertion of coins or currency shall not be used unless approved.
Approved key- or card-operated dispensing devices may be activated by
the customer with the use of an authorized key or
card.
(c)
2304.3.3 Emergency controls.
Emergency controls shall be provided in accordance with
paragraph (C)(2)( 2303.2) of this rule.
Emergency controls shall be of a type that is only manually
resettable.
(d)
2304.3.4 Operating instructions.
Dispenser operating instructions shall be conspicuously
posted in approved locations on every dispenser and shall indicate the location
of the emergency controls required by paragraph
(D)(3)(c)(2304.3.3) of this rule.
(e)
2304.3.5
Emergency procedures.
An approved
emergency procedures sign, in addition to the signs required by
paragraph (E)(6)( 2305.6)
of this rule,
shall be posted in a conspicuous location and shall read:
"IN CASE OF FIRE, SPILL OR
RELEASE
1.
USE EMERGENCY PUMP SHUTOFF
2.
REPORT THE
ACCIDENT!
FIRE DEPARTMENT TELEPHONE
NO.____________________
FACILITY ADDRESS_____________________
"
(f)
2304.3.6 Communications.
A telephone not requiring a coin to operate or other
approved, clearly identified means to notify the fire department shall be
provided on the site in a location approved by the fire code
official.
(g)
2304.3.7 Quantity limits.
Dispensing equipment used at unsupervised locations
shall comply with one of the following:
(i)
Dispensing
devices shall be programmed or set to limit uninterrupted fuel delivery to 25
gallons (95 L) and require a manual action to resume delivery.
(ii)
The amount of
fuel being dispensed shall be limited
to an approved quantity
by a preprogrammed card.
Exception:
This paragraph shall not apply to fixed dispensing equipment
at an unsupervised location at an airport that is used to dispense fuel
directly into the fuel tank of an
aircraft.
(h)
2304.3.8 Spill containment.
Containment of small spills shall be controlled by grading the pavement
away from the building and scoring the pavement or may be done by the use of an
oil/water separator.
(i)
2304.3.9 Dispensing devices.
Existing listed or labeled dispensing devices shall be permitted to be
modified provided that the modifications made are "Listed by Report" by an
approved testing laboratory or as otherwise approved by the fire code official.
Modification proposals shall contain a description of the component parts used
in the modification and the recommended methods of installation on specific
dispensing devices. Modification proposals shall be made available to the fire
code official upon request
(j)
2304.3.10 Smoking prohibited.
Gasoline and other flammable or combustible liquids shall be dispensed
only by a person who is not smoking. Smoking shall be prohibited in the
dispensing area.
(k)
2304.3.11 Required fire
protection.
In addition to fire protection equipment
otherwise required by this code, an unattended motor fuel-dispensing facility
shall also include automatic fixed suppression systems, and automatic fire
detection, and transmission of an alarm to an off-site approved supervising
station in accordance with paragraph (C)(4)(a)(903.4.1) of rule
1301:7-7-09
of the Administrative Code.
Exceptions:
1.
That
portion of an unattended motor fuel-dispensing facility that is exclusively
used to dispense fuel directly from fixed dispensing equipment into the fuel
tank of aircraft shall not be required to have an automatic fixed suppression
or automatic fire detection system.
2.
That
portion of an unattended motor fuel-dispensing facility that is exclusively
used to dispense fuel directly from fixed dispensing equipment into the fuel
tank of aircraft shall not be required to have transmission of an alarm to an
off-site approved supervising station provided that the facility installs a
telephone line or call box that complies with all of the
following:
2.1
An operational and fully functioning telephone or call box
shall be not less than 20 feet but not more than 10 0 feet from each dispensing
location;
2.2
Each telephone or call box shall either provide
a direct line to an off-site approved supervising station or to an approved
emergency response authority;
2.3
Each
telephone or call box shall be properly and conspicuously
identified;
2.4
Each telephone or call box shall not require a
coin or other form of payment to operate; and
2.5
The
telephone or call box shall be installed at a location that complies with the
above and that is approved by the fire code official.
(i)
2304.3.11.1 Compressed natural gas
facilities.
The requirement for an automatic fixed
suppression system shall not apply to that portion of an unattended, open to
the public motor fuel-dispensing facility where CNG is dispensed if all of the
following apply:(a)
The fueling areas where CNG is dispensed is
equipped with a fire detection device(s) that is directly tied to the emergency
shut down system; and
(b)
Upon
activation of the emergency shut down system, operation of all CNG dispensers
will automatically shut down and all CNG will automatically be isolated away
from the dispensing area; and
(c)
Upon
activation of the emergency shut down system, a notification system will
automatically trigger notification to the fire department;
and
(d)
No liquid fuels are being dispensed under the same canopy
where CNG is being dispensed.
(l)
2304.3.12 Signage.
Signs shall be provided in accordance with paragraphs
(D)(2)(c)(2304.2.3), (D)(2)(g)(2304.2.7) and
(D)(3)(e)(2304.3.5) of this rule.
(m)
2304.3.13 Signage material.
All signs required by paragraph (D)(3)(l)(2304.3.12)
of this rule shall be constructed of rigid, weather-resistant
material.
(4)
2304.4
Dispensing into portable containers. The dispensing of flammable or
combustible liquids into portable containers shall comply with
paragraphs (D)(4)(a)(2304.4.1)
to
(D)(4)(c)(2304.4.3)
of this rule.
(a)
2304.4.1
Approved containers required.
Class I, II
and IIIA liquids shall not be dispensed into a portable container unless such
container is properly constructed of metal or other material
approved by the fire code official, does not exceed a 6-gallon
( 22.7 L) capacity and has a tight closure with a screwed or spring-loaded
cover so designed that the contents can be dispensed without spilling. Liquids
shall not be dispensed into portable or cargo tanks.
(b)
2304.4.2
Nozzle operation.
A hose nozzle valve used
for dispensing Class I liquids into a portable container shall be in compliance
with paragraph (F)(7)(f)(2306.7.6) of this rule. No
person shall utilize the automatic latch-open device during the dispensing
operation.
(c)
2304.4.3 Location of containers being
filled.
Portable containers shall not be
filled while located inside the trunk, passenger compartment or truck bed of a
vehicle.
(E)
Section
2305 Operational requirements
(1)
2305.1 Tank
filling operations for Class I, II or III liquids.
Delivery operations to tanks for Class I, II or III
liquids shall comply with
paragraphs (E)(1)(a)(2305.1.1)
to (E)(1)(c)(2305.1.3)
of this rule and the
applicable requirements of
rule
1301:7-7-57
of the Administrative Code.(a)
2305.1.1 Delivery vehicle location.
Where liquid delivery to above-ground storage tanks is
accomplished by positive-pressure operation, tank vehicles shall be positioned
not less than 25 feet (7620 mm) from tanks receiving Class I liquids and 15
feet (4572 mm) from tanks receiving Class II and IIIA liquids.
(b)
2305.1.2
Tank capacity calculation.
The driver,
operator or attendant of a tank vehicle shall, before making delivery to a
tank, determine the unfilled, available capacity of such tank in
accordance with accepted industry practices.
(c)
2305.1.3
Tank fill connections.
Delivery of
flammable liquids to tanks more than 1,000 gallons (3785 L) in capacity shall
be made by means of approved liquid- and vapor-tight connections between the
delivery hose and tank fill pipe. Where tanks are equipped with any type of
vapor recovery system, all connections required to be made for the safe and
proper functioning of the particular vapor recovery process shall be made. Such
connections shall be made liquid and vapor tight and remain connected
throughout the unloading process. Vapors shall not be discharged at grade level
during delivery.
(2)
2305.2
Equipment maintenance and inspection.
Motor fuel-dispensing facility equipment shall be maintained
in proper working order at all times in accordance with
paragraphs (E)(2)(a)(2305.2.1)
to
(E)(2)(e)(2305.2.5)
of this rule.
(a)
2305.2.1
Inspections.
Flammable and combustible
liquid fuel-dispensing and containment equipment shall be periodically
inspected where required by the fire code official to verify that the equipment
is in proper working order and not subject to leakage. Records of inspections
shall be maintained in accordance with paragraph (G)(3)( 107.3) of
rule
1301:7-7-01
of the Administrative Code.
(b)
2305.2.2
Repairs and service.
The fire code
official is authorized to require damaged or unsafe containment and dispensing
equipment to be repaired or serviced in an approved manner.
(c)
2305.2.3
Dispensing devices.
Where maintenance to
Class I liquid dispensing devices becomes necessary and such maintenance could
allow the accidental release or ignition of liquid, the following precautions
shall be taken before such maintenance is begun:
(i)
Only persons
knowledgeable in performing the required maintenance shall perform the
work.
(ii)
Electrical power to the dispensing device and pump
serving the dispenser shall be shut off at the main electrical disconnect
panel.
(iii)
The emergency shutoff valve at the dispenser, where
installed, shall be closed.
(iv)
Vehicle traffic
and unauthorized persons shall be prevented from coming within 12 feet (3658
mm) of the dispensing device.
(d)
2305.2.4
Emergency shutoff valves.
Automatic
emergency shutoff valves required by paragraph
(F)(7)(d)(2306.7.4) of this rule shall be checked not
less than once per year by manually tripping the hold-open
linkage.
(e)
2305.2.5 Leak detectors.
Leak detection devices required by
paragraph (F)(7)(g)(i)(2306.7.7.1) of this rule
shall be checked and tested not less than annually in accordance with
the manufacturer's specifications to ensure proper installation and
operation.
(3)
2305.3 Spill control.
Provisions shall be made to prevent liquids spilled
during dispensing operations from flowing into buildings. Acceptable methods
include, but shall not be limited to, grading driveways, raising doorsills or
other approved means.
(4)
2305.4 Sources of ignition.
Smoking and open flames shall be prohibited in areas
where fuel is dispensed. The engines of vehicles being fueled shall be shut off
during fueling. Electrical equipment shall be in accordance with NFPA 70
as listed in rule
1301:7-7-80
of the Administrative Code.
(5)
2305.5 Fire
extinguishers.
Portable fire extinguishers
complying with paragraph (F)(906) of rule
1301:7-7-09
of the Administrative Code with a minimum rating of 2-A:20-B:C shall
be provided and located such that an extinguisher is not more than 75 feet (22
860 mm) from pumps, dispensers or storage tank fill-pipe
openings.
(6)
2305.6 Warning signs.
As required by section
3741.14 of the Revised Code,
signs bearing the following words in block letters shall be conspicuously
posted on each gasoline pump island where self-service is
offered:
(a)
"STOP ENGINE"
(b)
"NO
SMOKING"
(c)
"WARNING-IT IS UNLAWFUL AND DANGEROUS TO
DISPENSE GASOLINE INTO UNAPPROVED CONTAINERS"
(d)
"PERSONS
USING DISPENSERS WITH HOLD-OPEN LATCHES MUST REMAIN AT THE REFUELING POINT
DURING REFUELING"
Such signs shall also
state:
(e)
Discharge your static electricity before
fueling by touching a metal surface away from the
nozzle.
(f)
To prevent static charge, do not reenter your
vehicle while gasoline is pumping.
(g)
If a fire
starts, do not remove nozzle-back away immediately.
(h)
No
filling of portable containers in or on a motor vehicle. Place container on
ground before filling.
Exception:
Signs installed at
dispensers prior to July 1, 2018 containing language that is substantially
similar to items (a) to (h) of this paragraph shall be deemed as compliant with
this code.
(7)
2305.7
Control of brush and debris. Fenced and diked areas surrounding
above-ground tanks shall be kept free from vegetation, debris and other
material that is not necessary to the proper operation of the tank and piping
system.
Weeds, brush, trash and other
combustible materials shall be kept not less than 10 feet (3048 mm) from
fuel-handling equipment.
(F)
Section
2306 Flammable and combustible liquid motor fuel-dispensing
facilities.
(1)
2306.1 General.
Storage
of flammable and combustible liquids shall be in accordance with rule
1301:7-7-57
of the Administrative Code and paragraphs (F)(2)(
2306.2) to (F)(6)(c)(2306.6.3) of this
rule.
(2)
2306.2 Method of storage.Storage ofClass I, II
and IIIA
flammable or combustible liquids at motor
fuel-dispensing facilities
to which the public does not have
access, shall be
stored in aboveground tanks in
accordance with
paragraphs (F)(2)(a)(2306.2.1)
of this
rule or stored in underground tanks in accordance with Chapter 1301:7-9 of the
Administrative Code. At motor fuel-dispensing facilities to which the public
has access the only approved method of storage shall be in underground tanks in
accordance with Chapter 1301:7-9 of the Administrative Code.
Exception:
Where approved by the fire code official in accordance with
paragraph
(J)(1)( 2310.1) of
this rule, the approved method of storage of Class I, II and IIIA flammable or
combustible liquids at marine motor fuel-dispensing facilities shall be in
accordance with paragraphs (F)(2)(a)(2306.2.1) to
(F)(2)(f)(2306.2.6) of this rule.
(a)
2306.2.1
Underground tanks.
Underground tanks for
the storage of Class I, II and IIIA liquid motor fuels shall comply with
rule
1301:7-7-57
of the Administrative Code.
(i)
2306.2.1.1
Inventory control for underground tanks. Accurate daily inventory
records shall be maintained and reconciled on underground fuel storage tanks
for indication of possible leakage from tanks and piping. The records shall
include records for each product showing daily reconciliation between sales,
use, receipts and inventory on hand. Where there is more than one system
consisting of tanks serving separate pumps or dispensers for a product, the
reconciliation shall be ascertained separately for each tank system. A
consistent or accidental loss of product shall be immediately reported to the
fire code official.
(b)
2306.2.2
Above-ground tanks located inside buildings.
Above-ground tanks for the storage of Class I, II and
IIIA liquid fuels are allowed to be located in buildings. Such tanks shall be
located in special enclosures complying with paragraph
(F)(2)(f)(2306.2.6) of this rule, in a liquid storage room or
a liquid storage warehouse complying with rule
1301:7-7-57
of the Administrative Code, or shall be listed and labeled as
protected above-ground tanks in accordance with UL 2085 as listed in
rule
1301:7-7-80
of the Administrative Code.
(c)
2306.2.3
Above-ground tanks located outside, above grade. Above-ground tanks
shall not be used for the storage of Class I, II or III motor liquid fuels
except as provided.
Existing aboveground tank installations, even if
previously approved, that are determined to constitute a hazard by the fire
code official shall not be continued in service. Unsafe tanks shall be removed
as required by the fire code official and in accordance with this
code.
(i)
Above-ground tanks used for outside, above-grade
storage of Class I liquids shall be listed and labeled as protected
above-ground tanks in accordance with UL 2085
as listed in rule
1301:7-7-80
of the Administrative Code and shall be in accordance with
rule
1301:7-7-57
of the Administrative Code. Such tanks shall be located in accordance
with Table 2306.2.3
of this rule.
Exception:
An aboveground tank
approved by an authoritative source listed in rule
1301:7-7-01
of the Administrative Code as a fire-resistant tank may be utilized in lieu of
a protected tank when installed in accordance with Table 2306.2.3 of this
rule.
(ii)
Above-ground tanks used for outside, above-grade
storage of Class II or IIIA liquids shall be listed and labeled as protected
above-ground tanks in accordance with UL 2085
as listed in rule
1301:7-7-80
of the Administrative Code and shall be installed in accordance with
rule
1301:7-7-57 of the Administrative Code. Tank locations
shall be in accordance with Table 2306.2.3
of this rule.
Exception:
Other above-ground tanks that comply with rule
1301:7-7-57
of the Administrative Code where approved by the fire code
official.
(iii)
Tanks containing fuels shall not exceed 12,000 gallons
(45 420 L) in individual capacity or 48,000 gallons (181 680 L) in aggregate
capacity. Installations with the maximum allowable aggregate capacity shall be
separated from other such installations by not less than 100 feet (30 480
mm).
(iv)
Tanks located at areas used for agricultural
purposes and construction projects shall comply with
paragraph (F)(2)( 5706.2) of rule
1301:7-7-57
of the Administrative Code.
(v)
Above-ground
tanks used for outside above-grade storage of Class IIIB liquid motor fuel
shall be listed and labeled in accordance with UL 142
as listed in rule
1301:7-7-80
of the Administrative Code or listed and labeled as protected
above-ground tanks in accordance with UL 2085
as listed in rule
1301:7-7-80
of the Administrative Code and shall be installed in accordance with
rule
1301:7-7-57
of the Administrative Code. Tank locations shall be in accordance with
Table 2306.2.3
of this rule.
Table
2306.2.3
Minimum separation requirements
for above-ground tanks
Class of liquid and tank
type
|
Individual tank capacity
(gallons)
|
Minimum distance from
nearest important building on same property (feet)
|
Minimum distance from
nearest fuel dispenser (feet)
|
Minimum distance from lot
line that is or can be built upon, including the opposite side of a public way
(feet)
|
Minimum distance from
nearest side of any public way (feet)
|
Minimum distance between
tanks (feet)
|
Class I
protected above
|
Less than or equal to
6,000
|
5
|
25a
|
15
|
5
|
3
|
ground tanksb
|
Greater than 6,000
|
15
|
25a
|
25
|
15
|
3
|
Class II and III protected
above-ground tanks
|
Same as Class I
|
Same as Class I
|
Same as Class
Ic
|
Same as Class I
|
Same as Class I
|
Same as Class I
|
Tanks in vaults
|
0-20,000
|
0b
|
0
|
0b
|
0
|
Separate compartment for each
tank
|
Other tanks
|
All
|
50
|
50
|
100
|
50
|
3
|
For SI: 1 foot = 304.8 mm, 1 gallon =
3.785 L.
a.
At fleet vehicle motor fuel-dispensing facilities, no
minimum separation distance is required.
b.
A
fire-resistant tank may be utilized in lieu of a protected tank when approved
by the fire code official and installed in accordance with the distance
requirements of NFPA 30A as listed in rule
1301:7-7-80
of the Administrative Code.
c.
For Class IIIB
liquids in protected above-ground tanks, a minimum separation distance is not
required.
(d)
2306.2.4
Above-ground tanks located in above-grade vaults or below-grade vaults.
Above-ground tanks used for storage of
Class I, II or IIIA liquid motor fuels are allowed to be installed in vaults
located above grade or below grade in accordance with
paragraph (D)(2)(h)(5704.2.8)
of rule
1301:7-7-57
of the Administrative Code and shall comply with
paragraphs (F)(2)(d)(i)(2306.2.4.1) and
(F)(2)(d)(ii)(2306.2.4.2)
of this rule. Tanks in above-grade
vaults shall also comply with Table 2306.2.3
of this
rule.(i)
2306.2.4.1 Tank capacity limits. Tanks
storing Class I and Class II liquids at an individual site shall be limited to
a maximum individual capacity of 15,000 gallons (56 776 L) and an aggregate
capacity of 48,000 gallons (181 680 L).
(ii)
2306.2.4.2
Fleet vehicle motor fuel-dispensing facilities. Tanks storing Class II
and Class IIIA liquids at a fleet vehicle motor fuel-dispensing facility shall
be limited to a maximum individual fueling capacity of 20,000 gallons (75 700
L) and an aggregate capacity of 80,000 gallons (302 800
L).
(e)
2306.2.5 Portable tanks.
Where approved by the fire code official, portable
tanks are allowed to be temporarily used in conjunction with the dispensing of
Class I, II or III liquids into the fuel tanks of motor vehicles or motorized
equipment on premises not normally accessible to the public. The approval shall
include a definite time limit.
(f)
2306.2.6
Special enclosures.
Where installation of
tanks in accordance with
paragraph (D)(2)(k)(5704.2.11)
of rule
1301:7-7-57
of the Administrative Code is impractical, or because of property or
building limitations, tanks for liquid fuels are allowed to be installed in
buildings in special enclosures in accordance with all of the following:
(i)
The special
enclosure shall be liquid tight and vapor tight.
(ii)
The special
enclosure shall not contain backfill.
(iii)
Sides, top and
bottom of the special enclosure shall be of reinforced concrete not less than 6
inches (152 mm) thick, with openings for inspection through the top
only.
(iv)
Tank connections shall be piped or closed such that
neither vapors nor liquid can escape into the enclosed space between the
special enclosure and any tanks inside the special enclosure.
(v)
Means shall be
provided whereby portable equipment can be employed to discharge to the outside
any vapors that might accumulate inside the special enclosure should leakage
occur.
(vi)
Tanks containing Class I, II or IIIA liquids inside a
special enclosure shall not exceed 6,000 gallons (22 710 L) in individual
capacity or 18,000 gallons (68 130 L) in aggregate capacity.
(vii)
Each tank
within special enclosures shall be surrounded by a clear space of not less than
3 feet (910 mm) to allow for maintenance and
inspection.
(3)
2306.3
Security.
Aboveground tanks for the
storage of liquid motor fuels shall be safeguarded from public access or
unauthorized entry.
Tanks shall be enclosed with a chain link fence at
least 6 feet ( 1.8 m) high. The fence shall be separated from the tanks by at
least 3 feet ( 0.9 m) and shall have a gate that is secured against
unauthorized entry.
Exceptions:
1.
Fueling
facilities that are located on a property that has a perimeter security
fence.
2.
Tanks that are enclosed in
vaults.
(4)
2306.4
Physical protection.
Guard posts complying
with paragraph (L)(312) of rule
1301:7-7-03
of the Administrative Code or other approved means shall be provided
to protect above-ground tanks against impact by a motor vehicle unless the tank
is listed as a protected above-ground tank with vehicle impact
protection.
(5)
2306.5 Secondary containment.
Above-ground tanks shall be provided with drainage
control or diking in accordance with rule
1301:7-7-57
of the Administrative Code. Drainage control and diking is not
required for listed secondary containment tanks. Secondary containment systems
shall be monitored either visually or automatically. Enclosed secondary
containment systems shall be provided with emergency venting in accordance with
paragraph (F)(6)(b)(v)(2306.6.2.5) of this
rule.
(6)
2306.6 Piping, valves, fittings and ancillary equipment for
use with flammable or combustible liquids.
The design, fabrication, assembly, testing and inspection of
piping valves, fittings and ancillary equipment for use with flammable or
combustible liquids shall be in accordance with
rule
1301:7-7-57
of the Administrative Code and
paragraphs
(F)(6)(a)(2306.6.1)
to (F)(6)(c)(2306.6.3)
of this
rule.(a)
2306.6.1 Protection from damage.
Piping shall be located such that it is protected from
physical damage.
(b)
2306.6.2 Piping, valves, fittings and ancillary
equipment for above-ground tanks for Class I, II and III liquids.
Piping, valves, fittings and ancillary equipment for
above-ground tanks storing Class I, II and III liquids shall comply with
paragraphs (F)(6)(b)(i)(2306.6.2.1)
to
(F)(6)(b)(vi)(2306.6.2.6)
of this rule.
(i)
2306.6.2.1
Tank openings. Tank openings for above-ground tanks shall be through the
top only.
(ii)
2306.6.2.2 Fill-pipe connections. The fill
pipe for above-ground tanks shall be provided with a means for making a direct
connection to the tank vehicle's fuel-delivery hose so that the delivery of
fuel is not exposed to the open air during the filling operation. Where any
portion of the fill pipe exterior to the tank extends below the level of the
top of the tank, a check valve shall be installed in the fill pipe not more
than 12 inches (305 mm) from the fill-hose connection.
(iii)
2306.6.2.3 Overfill protection. Overfill
protection shall be provided for above-ground flammable and combustible liquid
storage tanks in accordance with paragraphs
(D)(2)(g)(v)(h)(5704.2.7.5.8) and (D)(2)(i)(vii)(f)(5704.2.9.7.6) of
rule
1301:7-7-57
of the Administrative Code.
(iv)
2306.6.2.4
Siphon prevention. An approved anti-siphon method shall be provided in
the piping system to prevent flow of liquid by siphon action.
(v)
2306.6.2.5
Emergency relief venting. Above-ground storage tanks, tank compartments
and enclosed secondary containment spaces shall be provided with emergency
relief venting in accordance with rule
1301:7-7-57
of the Administrative Code.
(vi)
2306.6.2.6
Spill containers. A spill container having a capacity of not less than 5
gallons (19 L) shall be provided for each fill connection. For tanks with a top
fill connection, spill containers shall be noncombustible and shall be fixed to
the tank and equipped with a manual drain valve that drains into the primary
tank. For tanks with a remote fill connection, a portable spill container is
allowed.
(c)
2306.6.3 Piping, valves, fittings and ancillary
equipment for underground tanks. Piping, valves, fittings and ancillary
equipment for underground tanks shall comply with rule
1301:7-7-57
of the Administrative Code and NFPA 30A as listed in rule
1301:7-7-80
of the Administrative Code.
(7)
2306.7
Fuel-dispensing systems for flammable or combustible liquids. The
design, fabrication and installation of fuel-dispensing systems for flammable
or combustible liquid fuels shall be in accordance with
paragraphs (F)(7)(a)(2306.7.1)
to
(F)(7)(i)(ii)(d)(2306.7.9.2.4)
of this rule. Fuel-dispensing systems
for alcohol blended fuel
s shall also comply with
paragraph (F)(8)( 2306.8)
of this
rule.
(a)
2306.7.1 Listed equipment.
Electrical equipment, dispensers, hose, nozzles and
submersible or subsurface pumps used in fuel-dispensing systems shall be
listed.
(b)
2306.7.2 Fixed pumps required.
Class I and Class II liquids shall be transferred from
tanks by means of fixed pumps designed and equipped to allow control of the
flow and prevent leakage or accidental discharge.
(c)
2306.7.3
Mounting of dispensers.
Dispensing
devices, except those installed on top of a protected above-ground tank that
qualifies as vehicle-impact resistant, shall be protected against physical
damage by mounting on a concrete island 6 inches (152 mm) or more in height, or
shall be protected in accordance with paragraph (L)(312)
of rule
1301:7-7-03
of the Administrative Code. Dispensing devices shall be installed and
securely fastened to their mounting surface in accordance with the dispenser
manufacturer's instructions. Dispensing devices installed indoors shall be
located in an approved position where they cannot be struck by an
out-of-control vehicle descending a ramp or other slope.
(d)
2306.7.4
Dispenser emergency shutoff valve.
An
approved automatic emergency shutoff valve designed to close in the event of a
fire or impact shall be properly installed in the liquid supply line at the
base of each dispenser supplied by a remote pump. The valve shall be installed
so that the shear groove is flush with or within 1/2 inch ( 12.7 mm) of the top
of the concrete dispenser island and there is clearance provided for
maintenance purposes around the valve body and operating parts. The valve shall
be installed at the liquid supply line inlet of each overhead-type dispenser.
Where installed, a vapor return line located inside the dispenser housing shall
have a shear section or approved flexible connector for the liquid supply line
emergency shutoff valve to function. Emergency shutoff valves shall be
installed and maintained in accordance with the manufacturer's instructions,
tested at the time of initial installation and not less than yearly thereafter
in accordance with paragraph (E)(2)(d)(2305.2.4) of
this rule.
(e)
2306.7.5 Dispenser hose.
Dispenser hoses shall be not more than 18 feet (5486
mm) in length unless otherwise approved. Dispenser hoses shall be approved.
When not in use, hoses shall be reeled, racked or otherwise protected from
damage.
(i)
2306.7.5.1 Emergency breakaway devices.
Dispenser hoses for Class I and II liquids shall be equipped with a listed
emergency breakaway device designed to retain liquid on both sides of a
breakaway point. Such devices shall be installed and maintained in accordance
with the manufacturer's instructions. Where hoses are attached to
hose-retrieving mechanisms, the emergency breakaway device shall be located
between the hose nozzle and the point of attachment of the hose-retrieval
mechanism to the hose.
(f)
2306.7.6
Fuel delivery nozzles.
A listed
automatic-closing-type hose nozzle valve with or without a latch-open device
shall be provided on island-type dispensers used for dispensing Class I, II or
III liquids.
Overhead-type dispensing units shall be
provided with a listed automatic-closing-type hose nozzle valve without a
latch-open device.
Exception:
A listed automatic-closing-type hose nozzle valve with
latch-open device is allowed to be used on overhead-type dispensing units where
the design of the system is such that the hose nozzle valve will close
automatically in the event the valve is released from a fill opening or upon
impact with a driveway.
(i)
2306.7.6.1 Special requirements for
nozzles. Where dispensing of Class I, II or IIIA liquids is performed, a
listed automatic-closing-type hose nozzle valve shall be used incorporating
one of the following features:
(a)
The hose nozzle
valve shall be equipped with an integral latch-open device.
(b)
Where the flow of
product is normally controlled by devices or equipment other than the hose
nozzle valve, the hose nozzle valve shall not be capable of being opened unless
the delivery hose is pressurized. If pressure to the hose is lost, the nozzle
shall close automatically.
Exception:
Vapor recovery nozzles incorporating insertion
interlock devices designed to achieve shutoff on disconnect from the vehicle
fill pipe.
(c)
The hose nozzle shall be designed such that the nozzle
is retained in the fill pipe during the filling operation.
(d)
The system shall
include listed equipment with a feature that causes or requires the closing of
the hose nozzle valve before the product flow can be resumed or before the hose
nozzle valve can be replaced in its normal position in the
dispenser.
(g)
2306.7.7
Remote pumping systems.
Remote pumping
systems for liquid fuels shall comply with
paragraphs
(F)(7)(g)(i)(2306.7.7.1) and (F)(7)(g)(ii)(2306.7.7.2)
of this
rule.
(i)
2306.7.7.1 Leak detection. Where remote
pumps are used to supply fuel dispensers, each pump shall have installed on the
discharge side a listed leak detection device that will detect a leak in the
piping and provide an indication to alert the operator of the presence
of a leak. A leak detection device is not required if the piping from
the pump discharge to under the dispenser is above ground and
visible.
(ii)
2306.7.7.2 Location. Remote pumps
installed above grade, outside of buildings, shall be located not less than 10
feet (3048 mm) from lines of adjoining property that can be built upon and not
less than 5 feet (1524 mm) from any building opening. Where an outside pump
location is impractical, pumps are permitted to be installed inside buildings
as provided for dispensers in paragraph (A)(4)( 2301.4)
of this rule and rule
1301:7-7-57
of the Administrative Code. Pumps shall be substantially anchored and
protected against physical damage.
(h)
2306.7.8
Gravity and pressure dispensing. Flammable liquids shall not be
dispensed by gravity from tanks, drums, barrels or similar containers.
Flammable or combustible liquids shall not be dispensed by a device operating
through pressure within a storage tank, drum or container.
(i)
2306.7.9
Vapor-recovery and vapor-processing systems. Vapor-recovery and
vapor-processing systems shall be in accordance with
paragraphs (F)(7)(i)(i)(2306.7.9.1)
to
(F)(7)(i)(ii)(
d)(2306.7.9.2.4)
of this
rule.(i)
2306.7.9.1 Vapor-recovery
systems.
Vapor recovery systems are systems designed to capture
and retain, without processing, vapors displaced during transfer or filling
operations. Vapor
-recovery systems
shall comply with
paragraphs
(F)(7)(i)(i)(
a)(2306.7.9.1.1) to
(F)(7)(i)(i)(
e)(2306.7.9.1.5)
of this
rule.
(a)
2306.7.9.1.1 Dispensing devices.
Dispensing devices incorporating provisions for vapor
recovery shall be listed and labeled. Where existing listed or labeled
dispensing devices are modified for vapor recovery, such modifications shall be
listed by report by a nationally recognized testing laboratory or by an
authoritative source listed in rule
1301:7-7-01
of the Administrative Code. The listing by report shall contain a
description of the component parts used in the modification and recommended
method of installation on specific dispensers. Such report shall be made
available on request of the fire code official.
(b)
2306.7.9.1.2 Vapor-return line closeoff.
A means shall be provided to
prevent the discharge of vapor from dispensers when the
product is not being dispensed.
(c)
2306.7.9.1.3 Piping.
Piping in
vapor-recovery systems shall be
in accordance with
paragraph (C)(6)( 5703.6)
of rule
1301:7-7-57
of the Administrative Code. Nonmetallic piping shall be installed in
accordance with the manufacturer's installation instructions.
Vent piping shall be in accordance with
paragraphs (C)(6)( 5703.6) and (D)(2)( 5704.2) of
rule
1301:7-7-57
of the Administrative Code. Vapor return piping shall be installed in
a manner that drains back to the tank, without sags or traps in which liquid
can become trapped. If necessary, because of grade, condensate tanks are
allowed in vapor return piping. Condensate tanks shall be designed and
installed so that they can be drained without opening.
(d)
2306.7.9.1.4 Flexible joints and shear joints.
Flexible joints shall be installed in accordance with
paragraph (C)(6)(i)(5703.6.9)
of rule
1301:7-7-57
of the Administrative Code.
An approved shear joint shall be
rigidly mounted and connected by a union in the vapor return piping at the base
of each dispensing device. The shear joint shall be mounted flush with the top
of the surface on which the dispenser is mounted.
(e)
2306.7.9.1.5 Testing.
Vapor return lines and vent piping shall be tested in
accordance with paragraph (C)(6)c)(5703.6.3) (of rule
1301:7-7-57
of the Administrative Code.
(ii)
2306.7.9.2
Vapor-processing systems.
Vapor processing systems are designed
to capture and process vapors displaced during transfer or filling operations
by use of mechanical or chemical means. Vapor-processing systems shall
comply with
paragraphs
(F)(7)(i)(ii)(
a)(2306.7.9.2.1)
to
(F)(7)(i)(ii)(
d)(2306.7.9.2.4)
of this
rule.
(a)
2306.7.9.2.1 Equipment.
Equipment in vapor-processing systems, including hose nozzle
valves, vapor pumps, flame arresters, fire checks or systems for prevention of
flame propagation, controls and vapor-processing equipment, shall be
individually listed for the intended use in a specified manner.
Vapor-processing systems that introduce
air into the underground piping or storage tanks shall be provided with
equipment for prevention of flame propagation that has been tested and listed
as suitable for the intended use.
(b)
2306.7.9.2.2 Location.
Vapor-processing equipment shall be located at or above
grade. Sources of ignition shall be located not less than
20
feet
(6096 mm) from fuel-transfer areas and not less than 18
inches (457 mm) above tank fill openings and tops of dispenser islands.
Vapor-processing units shall be located not less than 10 feet (3048 mm) from
the nearest building or lot line of a property that can be built upon.
Exception:
Where the required distances to buildings, lot lines or
fuel-transfer areas cannot be obtained, means shall be provided to protect
equipment against fire exposure. Acceptable means shall include but not be
limited to either of the following:
1.
Approved
protective enclosures, which extend not less than 18 inches (457 mm) above the
equipment, constructed of fire-resistant or noncombustible
materials.
2.
Fire protection using an approved water-spray
system.
(i)
2306.7.9.2. 2.1 Distance from dispensing
devices. Vapor-processing equipment shall be located not less than 20
feet (6096 mm) from dispensing devices.
(ii)
2306.7.9.2. 2.2 Physical protection.
Vapor-processing equipment shall be protected against physical damage by
guardrails, curbs, protective enclosures or fencing. Where approved protective
enclosures are used, approved means shall be provided to ventilate the volume
within the enclosure to prevent pocketing of flammable vapors.
(iii)
2306.7.9.2. 2.3 Downslopes. Where a downslope
exists toward the location of the vapor-processing unit from a fuel-transfer
area, the fire code official is authorized to require additional separation by
distance and height.
(c)
2306.7.9.2.3 Installation.
Vapor-processing units shall be securely mounted on
concrete, masonry or structural steel supports on concrete or other
noncombustible foundations. Vapor-processing equipment is allowed to be
installed on roofs when approved.
(d)
2306.7.9.2.4 Piping.
Piping for vapor processing systems shall
be in accordance with paragraph (C)(6)( 5703.6) of
rule
1301:7-7-57
of the Administrative Code.
(8)
2306.8Fuel-dispensing systems for alcohol
blended fuels. The design, fabrication and installation of
fuel-dispensing systems
for alcohol blended fuels shall be in
accordance with
paragraph (F)(7)(
2306.7) and
paragraphs (F)(8)(a)(2306.8.1)
to (F)(8)(e)(2306.8.5)
of this rule.
(a)
2306.8.1
Listed equipment.
Dispensers shall be
listed in accordance with UL 87A as listed in rule
1301:7-7-80
of the Administrative Code. Hoses, nozzles, breakaway fittings,
swivels, flexible connectors or dispenser emergency shutoff valves, vapor
recovery systems, leak detection devices and pumps used in alcohol-blended
fuel-dispensing systems shall be listed for the specific purpose and
approved as that term is defined in this rule.
(b)
2306.8.2
Compatibility.
Dispensers shall be used
only with the fuels for which they have been listed and which are marked on the
product. Field-installed components including hose assemblies, breakaway
fittings, swivel connectors and hose nozzle valves shall be provided in
accordance with the listing and the marking on the unit. Existing
dispensers may be modified to meet compatibility requirements in accordance
with paragraph (D)(3)(i)(2304.3.9) of this rule.
(c)
2306.8.3
Facility identification.
Facilities
dispensing alcohol-blended fuels shall be identified by marking the
fill pipes in accordance with API 1637 as listed in rule
1301:7-7-80
of the Administrative Code or an approved means.
(d)
2306.8.4
Marking.
As approved by the state
fire marshal
ispensers shall be marked
to identify the types of alcohol blended fuels to be dispensed.
(e)
2306.8.5
Maintenance and inspection.
Equipment
shall be maintained and inspected in accordance with paragraph (E)(2)(
2305.2) of this rule.
(G)
Section
2307 Liquefied petroleum gas motor fuel-dispensing facilities
(1)
2307.1
General.
Motor fuel-dispensing facilities
for liquefied petroleum gas (LP-gas) fuel shall be in accordance with this
paragraph and rule
1301:7-7-61
of the Administrative Code.
(2)
2307.2
Approvals.
Storage vessels and equipment
used for the storage or dispensing of LP-gas shall be approved or listed in
accordance with
paragraphs (G)(2)(a)(2307.2.1) and
(G)(2)(b)(2307.2.2)
of this rule.
(a)
2307.2.1
Approved equipment.
Containers, pressure
relief devices (including pressure relief valves), pressure regulators and
piping for LP-gas shall be approved.
(b)
2307.2.2
Listed equipment.
Hoses, hose connections,
vehicle fuel connections, dispensers, LP-gas pumps and electrical equipment
used for LP-gas shall be listed.
(3)
2307.3
Attendants.
Motor fuel-dispensing
operations for LP-gas shall be conducted by qualified attendants or in
accordance with paragraph (G)(7)( 2307.7) of this
rule by persons trained in the proper handling of
LP-gas.
(4)
2307.4 Location of dispensing operations and
equipment.
The point of transfer for
LP-gas dispensing operations shall be separated from buildings and other
exposures in accordance with the following:
(a)
Not less than 25
feet (7620 mm) from buildings where the exterior wall is not part of a
fire-resistance-rated assembly having a rating of 1 hour or
greater.
(b)
Not less than 25 feet (7620 mm) from combustible
overhangs on buildings, measured from a vertical line dropped from the face of
the overhang at a point nearest the point of transfer.
(c)
Not less than 25
feet (7620 mm) from the lot line of property that can be built
upon.
(d)
Not less than 25 feet (7620 mm) from the centerline of
the nearest mainline railroad track.
(e)
Not less than 10
feet (3048 mm) from public streets, highways, thoroughfares, sidewalks and
driveways.
(f)
Not less than 10 feet (3048 mm) from buildings where
the exterior wall is part of a fire-resistance-rated assembly having a rating
of 1 hour or greater.
Exception:
The point of transfer for LP-gas dispensing operations
need not be separated from canopies that are constructed in accordance with the
building code as listed in rule
1301:7-7-80
of the Administrative Code and that provide weather protection for the
dispensing equipment.
LP-gas containers shall be located in
accordance with rule
1301:7-7-61
of the Administrative Code. LP-gas storage and dispensing equipment
shall be located outdoors.
(5)
2307.5
Additional requirements for LP-gas dispensers and equipment.
LP-gas dispensers and related equipment shall comply
with the following provisions.
(a)
Pumps shall be fixed in place and shall be designed to
allow control of the flow and to prevent leakage and accidental
discharge.
(b)
Dispensing devices installed within 10 feet (3048 mm)
of where vehicle traffic occurs shall be protected against physical damage by
mounting on a concrete island 6 inches (152 mm) or more in height, or shall be
protected in accordance with paragraph (L)(312) of
rule
1301:7-7-03
of the Administrative Code.
(c)
Dispensing
devices shall be securely fastened to their mounting surface in accordance with
the dispenser manufacturer's instructions.
(6)
2307.6
Installation of LP-gas dispensing devices and equipment.
The installation and operation of LP-gas dispensing
systems shall be in accordance with
paragraphs
(G)(6)(a)(2307.6.1)
to (G)(6)(d)(2307.6.4)
of this
rule and
rule
1301:7-7-61
of the Administrative Code. LP-gas dispensers and dispensing stations
shall be installed in accordance with the manufacturer's specifications and
their listing.
(a)
2307.6.1 Product control valves.
The dispenser system piping shall be protected from
uncontrolled discharge in accordance with the following:
(i)
Where mounted on
a concrete base, a means shall be provided and installed within 1/2 inch ( 12.7
mm) of the top of the concrete base that will prevent flow from the supply
piping in the event that the dispenser is displaced from its
mounting.
(ii)
A manual shutoff valve and an excess flow-control check
valve shall be located in the liquid line between the pump and the dispenser
inlet where the dispensing device is installed at a remote location and is not
part of a complete storage and dispensing unit mounted on a common
base.
(iii)
An excess flow-control check valve or an emergency
shutoff valve shall be installed in or on the dispenser at the point at which
the dispenser hose is connected to the liquid piping.
(iv)
A listed
automatic-closing type hose nozzle valve with or without a latch-open device
shall be provided on island-type dispensers.
(b)
2307.6.2
Hoses.
Hoses and piping for the dispensing
of LP-gas shall be provided with hydrostatic relief valves. The hose length
shall not exceed 18 feet (5486 mm). An approved method shall be provided to
protect the hose against mechanical damage.
(c)
2307.6.3
Emergency breakaway devices.
Dispenser
hoses shall be equipped with a listed emergency breakaway device designed to
retain liquid on both sides of the breakaway point. Where hoses are attached to
hose-retrieving mechanisms, the emergency breakaway device shall be located
such that the breakaway device activates to protect the dispenser from being
displaced.
(d)
2307.6.4 Vehicle impact protection.
Where installed within 10 feet of vehicle traffic,
LP-gas storage containers, pumps and dispensers shall be protected in
accordance with paragraph (G)(5)( 2307.5), item (b)
of this rule.
(7)
2307.7
Public fueling of motor vehicles.
Self-service LP-gas dispensing systems, including key, code
and card lock dispensing systems, shall be limited to the filling of
permanently mounted containers providing fuel to the LP-gas powered
vehicle.
The requirements for self-service
LP-gas dispensing systems shall be in accordance with the
following:
(a)
The arrangement and operation of the transfer of
product into a vehicle shall be in accordance with this
paragraph and rule
1301:7-7-61
of the Administrative Code.
(b)
The system shall
be provided with an emergency shutoff switch located within 100 feet (30 480
mm) of, but not less than 20 feet (6096 mm) from, dispensers.
(c)
The owner of the
LP-gas motor fuel-dispensing facility or the owner's designee shall provide for
the safe operation of the system and the training of users.
(d)
The dispenser and
hose-end valve shall release not more than
1/8 fluid ounce (4 cc) of
liquid to the atmosphere upon breaking the connection with the fill valve on
the vehicle.
(e)
Portable fire extinguishers shall be provided in
accordance with paragraph (E)(5)( 2305.5) of this
rule.
(f)
Warning signs shall be provided in accordance with
paragraph (E)(6)( 2305.6) of this
rule.
(g)
The area around the dispenser shall be maintained in
accordance with paragraph (E)(7)( 2305.7) of this
rule.
(8)
2307.8 Overfilling. LP-gas containers
shall not be filled with LP-gas in excess of the volume determined using the
fixed maximum liquid level gauge installed on the container, the volume
determined by the overfilling prevention device installed on the container or
the weight determined by the required percentage of the water capacity marked
on the container.
(H)
Section
2308 Compressed natural gas motor fuel-dispensing facilities
(1)
2308.1
General.
Motor fuel-dispensing facilities
for compressed natural gas (CNG) fuel shall be in accordance with this
paragraph and rule
1301:7-7-53 of
the Administrative Code.
(2)
2308.2
Approvals.
Storage vessels and equipment
used for the storage, compression or dispensing of CNG shall be approved or
listed in accordance with
paragraphs (H)(2)(a)(2308.2.1) and
(H)(2)(b)(2308.2.2)
of this rule.
(a)
2308.2.1
Approved equipment.
Containers,
compressors, pressure relief devices (including pressure relief valves), and
pressure regulators and piping used for CNG shall be approved.
(b)
2308.2.2
Listed equipment.
Hoses, hose connections,
dispensers, gas detection systems and electrical equipment used for CNG shall
be listed. Vehicle-fueling connections shall be listed and
labeled.
(3)
2308.3 Location of dispensing operations and
equipment.
Compression, storage and
dispensing equipment shall be located above ground, outside.
Exceptions:
1.
Compression,
storage or dispensing equipment shall be allowed in buildings of noncombustible
construction, as set forth in the building code as listed in rule
1301:7-7-80
of the Administrative Code, that are unenclosed for three-quarters or
more of the perimeter.
2.
Compression, storage and dispensing equipment shall be
allowed indoors or in vaults in accordance with
rule
1301:7-7-53 of
the Administrative Code.(a)
2308.3.1 Location on property. In addition
to the requirements of
paragraph (C)(1)( 2303.1)
of
this rule, compression, storage and dispensing equipment not located
in vaults complying with
rule
1301:7-7-53 of
the Administrative Code shall be installed as follows:
(i)
Not beneath power
lines.
(ii)
Ten feet (3048 mm) or more from the nearest building or
lot line that could be built on, public street, sidewalk or source of
ignition.
Exception:
Dispensing equipment need not be separated from
canopies that are constructed in accordance with the building code as
listed in rule
1301:7-7-80
of the Administrative Code and that provide weather protection for the
dispensing equipment.
(iii)
Twenty-five
feet (7620 mm) or more from the nearest rail of any railroad track and 50 feet
(15240 mm) or more from the nearest rail of any railroad main track or any
railroad or transit line where power for train propulsion is provided by an
outside electrical source, such as third rail or overhead
catenary.
(iv)
Fifty feet (15240 mm) or more from the vertical plane
below the nearest overhead wire of a trolley bus line.
(4)
2308.4 Private fueling of motor vehicles.
Self-service CNG-dispensing systems, including key,
code and card lock dispensing systems, shall be limited to the filling of
permanently mounted fuel containers on CNG-powered vehicles.
In addition to the requirements in
paragraph (E)(2305) of this rule, the owner
of a self-service CNG motor fuel-dispensing facility shall ensure the safe
operation of the system and the training of users.
(5)
2308.5
Pressure regulators.
Pressure regulators
shall be designed and installed or protected so that their operation will not
be affected by the elements (freezing rain, sleet, snow or ice), mud or debris.
The protection is allowed to be an integral part of the
regulator.
(6)
2308.6 Valves.
Gas
piping to equipment shall be provided with a remote, readily accessible manual
shutoff valve.
(7)
2308.7 Emergency shutdown control.
An emergency shutdown control shall be located within
75 feet (22 860 mm) of, but not less than 25 feet (7620 mm) from, dispensers
and shall also be provided in the compressor area. Upon activation, the
emergency shutdown system shall automatically shut off the power supply to the
compressor and close valves between the main gas supply and the compressor and
between the storage containers and dispensers.
(8)
2308.8
Discharge of CNG from motor vehicle fuel storage containers.
The discharge of CNG from motor vehicle fuel cylinders
for the purposes of maintenance, cylinder certification, calibration of
dispensers or other activities shall be in accordance with
paragraphs (H)(8)(a)(2308.8.1)
to
(H)(8)(a)(ii)(
f)(2308.8.1.2.6)
of this
rule.(a)
2308.8.1 Methods of discharge. The
discharge of CNG from motor vehicle fuel cylinders shall be accomplished
through a closed transfer system in accordance with
paragraph
(H)(8)(a)(i)(2308.8.1.1)
of this rule or an approved method of
atmospheric venting in accordance with
paragraph
(H)(8)(a)(ii)(2308.8.1.2)
of this rule.
(i)
2308.8.1.1
Closed transfer system. A documented procedure that explains the logical
sequence for discharging the cylinder shall be provided to the fire code
official for review and approval. The procedure shall include what actions the
operator will take in the event of a low-pressure or high-pressure natural gas
release during the discharging activity. A drawing illustrating the arrangement
of piping, regulators and equipment settings shall be provided to the fire code
official for review and approval. The drawing shall illustrate the piping and
regulator arrangement and shall be shown in spatial relation to the location of
the compressor, storage vessels and emergency shutdown devices.
(ii)
2308.8.1.2
Atmospheric venting. Atmospheric venting of CNG shall comply with
paragraphs (H)(8)(a)(ii)(
a)(2308.8.1.2.1)
to (H)(8)(a)(ii)(
f)(2308.8.1.2.6)
of
this rule.
(a)
2308.8.1.2.1 Plans and specifications.
A drawing illustrating the location of the vessel
support, piping, the method of grounding and bonding, and other requirements
specified herein shall be provided to the fire code official for review and
approval.
(b)
2308.8.1.2.2 Cylinder stability.
A method of rigidly supporting the vessel during the
venting of CNG shall be provided. The selected method shall provide not less
than two points of support and shall prevent the horizontal and lateral
movement of the vessel. The system shall be designed to prevent the movement of
the vessel based on the highest gas-release velocity through valve orifices at
the vessel's rated pressure and volume. The structure or appurtenance shall be
constructed of noncombustible materials.
(c)
2308.8.1.2.3 Separation. The structure or
appurtenance used for stabilizing the cylinder shall be separated from the site
equipment, features and exposures and shall be located in accordance with Table
2308.8.1.2.3
of this rule.
Table
2308.8.1.2.3
Separation distance for
atmospheric venting of CNG
Equipment or
feature
|
Minimum separation
(feet)
|
Buildings
|
25
|
Building openings
|
25
|
CNG compressor and storage
vessels
|
25
|
CNG dispensers
|
25
|
Lot lines
|
15
|
Public ways
|
15
|
Vehicles
|
25
|
For SI: 1 foot = 304.8 mm.
(d)
2308.8.1.2.4 Grounding and bonding.
The structure or appurtenance used for supporting the
cylinder shall be grounded in accordance with NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code. The cylinder valve shall be bonded prior
to the commencement of venting operations.
(e)
2308.8.1.2.5 Vent tube.
A vent tube that will divert the gas flow to atmosphere
shall be installed on the cylinder prior to commencement of the venting and
purging operation. The vent tube shall be constructed of pipe or tubing
materials approved for use with CNG in accordance with
rule
1301:7-7-53 of
the Administrative Code.
The vent tube shall be capable of
dispersing the gas not less than 10 feet (3048 mm) above grade level. The vent
tube shall not be provided with a rain cap or other feature that would limit or
obstruct the gas flow.
At the connection fitting of the vent
tube and the CNG cylinder, a listed bidirectional detonation flame arrester
shall be provided.
(f)
2308.8.1.2.6 Signage.
"No Smoking" signs complying with
paragraph (J)(310) of rule
1301:7-7-03
of the Administrative Code shall be posted within 10 feet (3048 mm) of
the cylinder support structure or appurtenance. Signs that
read "CYLINDER SHALL BE BONDED" shall be posted on the cylinder
support structure or
appurtenance.
(I)
Section
2309 Hydrogen motor fuel-dispensing and generation facilities
(1)
2309.1
General.
Hydrogen motor fuel-dispensing
and generation facilities shall be in accordance with this
paragraph and rule
1301:7-7-58
of the Administrative Code. Where a fuel-dispensing facility also
includes a repair garage, the repair operation shall comply with
paragraph (K)(2311) of this
rule.
(2)
2309.2 Equipment.
Equipment used for the generation, compression, storage or
dispensing of hydrogen shall be designed for the specific application in
accordance with
paragraphs (I)(2)(a)(2309.2.1)
to (I)(2)(c)(2309.2.3)
of this rule.
(a)
2309.2.1
Approved equipment.
Cylinders, containers
and tanks; pressure relief devices, including pressure valves; hydrogen
vaporizers; pressure regulators; and piping used for gaseous hydrogen systems
shall be designed and constructed in accordance with rule
1301:7-7-53 of
the Administrative Code, rule 1301:7-7-55 of the Administrative Code and rule
1301:7-7-58
of the Administrative Code.
(b)
2309.2.2
Listed or approved equipment.
Hoses, hose
connections, compressors, hydrogen generators, dispensers, detection systems
and electrical equipment used for hydrogen shall be listed or approved for use
with hydrogen. Hydrogen motor-fueling connections shall be listed and labeled
or approved for use with hydrogen.
(c)
2309.2.3
Electrical equipment.
Electrical
installations shall be in accordance with NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code.
(3)
2309.3
Location on property. In addition to the requirements of
paragraph (C)(1)( 2303.1)
of this rule,
dispensing equipment shall be located in accordance with
paragraphs (I)(3)(a)(2309.3.1)
to
(I)(3)(c)(2309.3.3)
of this rule.
(a)
2309.3.1
Location of dispensing operations and equipment. Generation,
compression, storage and dispensing equipment shall be located in accordance
with
paragraphs (I)(3)(a)(i)(2309.3.1.1)
to
(I)(3)(a)(v)(e)(2309.3.1.5.5)
of this rule.
(i)
2309.3.1.1
Outdoors. Generation, compression, or storage equipment shall be allowed
outdoors in accordance with rule
1301:7-7-58
of the Administrative Code and NFPA 2 as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
2309.3.1.2
Indoors. Generation, compression, storage and dispensing equipment shall
be located in indoor rooms or areas constructed in accordance with the
requirements of the
building code, the International Fuel Gas
Code, the
mechanical code and NFPA 2
as listed in rule
1301:7-7-80
of the Administrative Code.
(a)
2309.3.1.2.1 Maintenance.
Gaseous hydrogen systems and detection devices shall be
maintained in accordance with the manufacturer's instructions.
(b)
2309.3.1.2.2 Smoking.
Smoking shall be prohibited in hydrogen cutoff rooms. "No
Smoking" signs shall be provided at all entrances to hydrogen fuel gas
rooms.
(c)
2309.3.1.2.3 Ignition source control.
Open flames, flame-producing devices and other sources
of ignition shall be controlled in accordance with rule
1301:7-7-58
of the Administrative Code.
(d)
2309.3.1.2.4 Housekeeping.
Hydrogen fuel gas rooms shall be kept free from
combustible debris and storage.
(iii)
2309.3.1.3 Gaseous hydrogen storage. Storage of
gaseous hydrogen shall be in accordance with rules
1301:7-7-53
and 1301:7-7-58 of the Administrative Code.
(iv)
2309.3.1.4
Liquefied hydrogen storage. Storage of liquefied hydrogen shall be in
accordance with rules
1301:7-7-55
and 1301:7-7-58 of the Administrative Code.
(v)
2309.3.1.5
Canopy tops. Gaseous hydrogen compression and storage equipment located
on top of motor fuel-dispensing facility canopies shall be in accordance with
paragraphs (I)(3)(a)(v)(a)(2309.3.1.5.1) to
(I)(3)(a)(v)(e)(2309.3.1.5.5)
of this rule, rules
1301:7-7-53 and
1301:7-7-58 of the Administrative Code and the International Fuel Gas
Code
as listed in rule
1301:7-7-80
of the Administrative Code.
(a)
2309.3.1.5.1 Construction.
Canopies shall be constructed in accordance with the
motor fuel-dispensing facility canopy requirements of section 406.7 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
2309.3.1.5.2 Fire-extinguishing systems.
Fuel-dispensing areas under canopies shall be equipped
throughout with an approved automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code. The design of the sprinkler system shall
be not less than that required for Extra Hazard Group 2 occupancies. Operation
of the sprinkler system shall activate the emergency functions of
paragraphs (I)(3)(a)(v)(c)(2309.3.1.5.3) and
(I)(3)(a)(v)(d)(2309.3.1.5.4) of this
rule.
(c)
2309.3.1.5.3 Emergency discharge.
Operation of the automatic sprinkler system shall
activate an automatic emergency discharge system, which will discharge the
hydrogen gas from the equipment on the canopy top through the vent pipe
system.
(d)
2309.3.1.5.4 Emergency shutdown control.
Operation of the automatic sprinkler system shall
activate the emergency shutdown control required in paragraph
(I)(5)(c)(2309.5.3) of this rule.
(e)
2309.3.1.5.5 Signage.
Approved signage having 2-inch (51 mm) block letters shall
be affixed at approved locations on the exterior of the canopy structure
stating: "CANOPY TOP HYDROGEN STORAGE."
(b)
2309.3.2
Canopies. Dispensing equipment need not be separated from canopies of
Type I or II construction that are constructed in a manner that prevents the
accumulation of hydrogen gas and in accordance with section 406.7 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(4)
2309.4
Dispensing into motor vehicles at self-service hydrogen motor fuel-dispensing
facilities.
Self-service hydrogen motor
fuel-dispensing systems, including key, code and card lock dispensing systems,
shall be limited to the filling of permanently mounted fuel containers on
hydrogen-powered vehicles.
In addition to the requirements in
paragraph (K)(2311) of this rule, the owner
of a self-service hydrogen motor fuel-dispensing facility shall provide for the
safe operation of the system through the institution of a fire safety plan
submitted in accordance with paragraph (D)(404) of
rule
1301:7-7-04
of the Administrative Code, the training of employees and operators
who use and maintain the system in accordance with paragraph
(F)(406) of rule
1301:7-7-04
of the Administrative Code, and provisions for hazard communication in
accordance with paragraph (G)(407) of rule
1301:7-7-04
of the Administrative Code.
(a)
2309.4.1
Dispensing systems. Dispensing systems shall be equipped with an
overpressure protection device set at not greater than 140 per
cent of the service pressure of the fueling nozzle it
supplies.
(5)
2309.5 Safety precautions.
Safety precautions at hydrogen motor fuel-dispensing
and generation facilities shall be in accordance with
paragraphs (I)(5)(a)(2309.5.1)
to
(I)(5)(c)(i)(2309.5.3.1)
of this rule.
(a)
2309.5.1
Protection from vehicles.
Guard posts or
other approved means shall be provided to protect hydrogen storage systems and
use areas subject to vehicular damage in accordance with
paragraph (L)(312)
of rule
1301:7-7-03
of the Administrative Code.
(i)
2309.5.1.1
Vehicle fueling pad. The vehicle shall be fueled on noncoated concrete
or other approved paving material having a resistance not exceeding 1 megohm as
determined by the methodology specified in EN 1081 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
2309.5.2
Emergency shutoff valves.
A manual
emergency shutoff valve shall be provided to shut down the flow of gas from the
hydrogen supply to the piping system.
(i)
2309.5.2.1
Identification. Manual emergency shutoff valves shall be identified and
the location shall be clearly visible, accessible and indicated by means of a
sign.
(c)
2309.5.3 Emergency shutdown controls. In
addition to the manual emergency shutoff valve required by
paragraph (I)(5)(b)(2309.5.2)
of this rule, a
remotely located, manually activated emergency shutdown control shall be
provided. An emergency shutdown control shall be located within 75 feet (22 860
mm) of, but not less than 25 feet (7620 mm) from, dispensers and hydrogen
generators.
(i)
2309.5.3.1 System requirements. Activation of
the emergency shutdown control shall automatically shut off the power supply to
all hydrogen storage, compression and dispensing equipment; shut off natural
gas or other fuel supply to the hydrogen generator; and close valves between
the main supply and the compressor and between the storage containers and
dispensing equipment.
(6)
2309.6
Defueling of hydrogen from fuel storage containers. The discharge or
defueling of hydrogen from fuel storage tanks for the purpose of maintenance,
cylinder certification, calibration of dispensers or other activities shall be
in accordance with
paragraphs (I)(6)(a)(2309.6.1)
to (I)(6)(a)(ii)(
d)(2309.6.1.2.4)
of
this rule.(a)
2309.6.1 Methods of discharge. The
discharge of hydrogen from fuel storage tanks shall be accomplished through a
closed transfer system in accordance with
paragraph
(I)(6)(a)(i)(2309.6.1.1)
of this rule or a method of
atmospheric venting in accordance with
paragraph
(I)(6)(a)(ii)(2309.6.1.2)
of this rule.
(i)
2309.6.1.1
Closed transfer system. A documented procedure that explains the logic
sequence for discharging the storage tank shall be provided to the fire code
official for review and approval. The procedure shall include what actions the
operator is required to take in the event of a low-pressure or high-pressure
hydrogen release during discharging activity. Schematic design documents shall
be provided illustrating the arrangement of piping, regulators and equipment
settings. The construction documents shall illustrate the piping and regulator
arrangement and shall be shown in spatial relation to the location of the
compressor, storage vessels and emergency shutdown devices.
(ii)
2309.6.1.2 Atmospheric venting of hydrogen from fuel storage containers.
Where atmospheric venting is used for the discharge of hydrogen from
fuel storage tanks, such venting shall be in accordance with
paragraphs
(I)(6)(
a)(ii)(
a)(2309.6.1.2.1) to
(I)(6)(a)(ii)(
a)(
iv)(2309.6.1.2. 1.4)
of this rule.
(a)
2309.6.1.2.1 Defueling equipment.
Equipment used for defueling shall be listed and
labeled or approved for the intended use.
(i)
2309.6.1.2.
1.1 Manufacturer's equipment required. Equipment supplied by the
manufacturer shall be used to connect the storage tanks to be defueled to the
vent pipe system.
(ii)
2309.6.1.2. 1.2 Vent pipe maximum
diameter. Defueling vent pipes shall have a maximum inside diameter of 1
inch (25 mm).
(iii)
2309.6.1.2. 1.3 Maximum flow rate. The
maximum rate of hydrogen flow through the vent pipe system shall not exceed
1,000 cfm at NTP ( 0.47 m3/s) and shall be
controlled by means of the manufacturer's equipment, at low pressure and
without adjustment.
(iv)
2309.6.1.2. 1.4 Isolated use. The vent
pipe used for defueling shall not be connected to another venting system used
for any other purpose.
(b)
2309.6.1.2.2 Construction documents.
Construction documents shall be provided illustrating
the defueling system to be utilized. Plan details shall be of sufficient detail
and clarity to allow for evaluation of the piping and control systems to be
utilized and include the method of support for cylinders, containers or tanks
to be used as part of a closed transfer system, the method of grounding and
bonding and other requirements specified herein.
(c)
2309.6.1.2.3 Stability of cylinders, containers and
tanks.
A method of rigidly supporting
cylinders, containers or tanks used during the closed transfer system discharge
or defueling of hydrogen shall be provided. The method shall provide not less
than two points of support and shall be designed to resist lateral movement of
the receiving cylinder, container or tank. The system shall be designed to
resist movement of the receiver based on the highest gas-release velocity
through valve orifices at the receiver's rated service pressure and volume.
Supporting structures or appurtenances used to support receivers shall be
constructed of noncombustible materials in accordance with the building
code as listed in rule
1301:7-7-80
of the Administrative Code.
(d)
2309.6.1.2.4 Grounding and bonding.
Cylinders, containers or tanks and piping systems used
for defueling shall be bonded and grounded. Structures or appurtenances used
for supporting the cylinders, containers or tanks shall be grounded in
accordance with NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code. The valve of the vehicle storage tank
shall be bonded with the defueling system prior to the commencement of
discharge or defueling operations.
(b)
2309.6.2
Repair of hydrogen piping.
Piping systems
containing hydrogen shall not be opened to the atmosphere for repair without
first purging the piping with an inert gas to achieve 1 per
cent hydrogen or less by volume. Defueling operations and exiting
purge flow shall be vented in accordance with paragraph
(I)(6)(a)(ii)(2309.6.1.2) of this rule.
(c)
2309.6.3
Purging.
Each individual manufactured
component of a hydrogen generating, compression, storage or dispensing system
shall have a label affixed as well as a description in the installation and
owner's manuals describing the procedure for purging air from the system during
startup, regular maintenance and for purging hydrogen from the system prior to
disassembly (to admit air).
For the interconnecting piping between
the individual manufactured components, the pressure rating must be not less
than 20 times the absolute pressure present in the piping when any hydrogen
meets any air.
(i)
2309.6.3.1 System purge required. After
installation, repair or maintenance, the hydrogen piping system shall be purged
of air in accordance with the manufacturer's procedure for purging air from the
system.
(J)
Section
2310 Marine motor fuel-dispensing facilities
(1)
2310.1
General.
The construction of marine motor
fuel-dispensing facilities shall be in accordance with the building
code and NFPA 30A as listed in rule
1301:7-7-80
of the Administrative Code. The storage of Class I, II or IIIA liquids
at marine motor fuel-dispensing facilities shall be in accordance with
this rule and rule
1301:7-7-57
of the Administrative Code. Where underground storage of flammable or
combustible liquids is impractical due to geological conditions of the site,
shore tanks supplying marine service stations may be located aboveground in
special enclosures, vaults or protected aboveground tanks which provide
physical protection and fire-resistive protection as a unit, when approved by
the fire code official. The request to install such aboveground tanks shall be
accompanied by a site survey which supports the request. The survey shall be
prepared by a registered professional engineer of the appropriate
discipline.
(2)
2310.2 Storage and handling.
The storage and handling of Class I, II or IIIA liquids
at marine motor fuel-dispensing facilities shall be in accordance with
paragraphs (J)(2)(a)(2310.2.1)
to
(J)(2)(c)(2310.2.3)
of this rule.
(a)
2310.2.1
Class I, II or IIIA liquid storage. Class I, II or IIIA liquids stored
inside of buildings used for marine motor fuel-dispensing facilities shall be
stored in approved containers or portable tanks. Storage of Class I liquids
shall not exceed 10 gallons (38 L).
Exception:
Storage in liquid storage rooms in accordance with
paragraph (D)(3)(g)(5704.3.7) of rule
1301:7-7-57
of the Administrative Code.
(b)
2310.2.2
Class II or IIIA liquid storage and dispensing.
Class II or IIIA liquids stored or dispensed inside of
buildings used for marine motor fuel-dispensing facilities shall be stored in
and dispensed from approved containers or portable tanks. Storage of Class II
and IIIA liquids shall not exceed 120 gallons (454 L).
(c)
2310.2.3
Heating equipment.
Heating equipment
installed in Class I, II or IIIA liquid storage or dispensing areas shall
comply with paragraph (A)(6)( 2301.6) of this
rule.
(3)
2310.3 Dispensing.
The dispensing of liquid fuels at marine motor
fuel-dispensing facilities shall comply with
paragraphs
(J)(3)(a)(2310.3.1)
to (J)(3)(e)(2310.3.5)
of this
rule.
(a)
2310.3.1 General.
Wharves, piers or floats at marine motor fuel-dispensing
facilities shall be used exclusively for the dispensing or transfer of
petroleum products to or from marine craft, except that transfer of essential
ship stores is allowed.
(b)
2310.3.2 Supervision.
Marine motor fuel-dispensing facilities shall have an
attendant or supervisor who is fully aware of the operation, mechanics and
hazards inherent to fueling of boats on duty whenever the facility is open for
business. The attendant's primary function shall be to supervise, observe and
control the dispensing of Class I, II or IIIA liquids or flammable
gases.
(c)
2310.3.3 Hoses and nozzles.
Dispensing of Class I, II or IIIA liquids into the fuel
tanks of marine craft shall be by means of an approved hose equipped with a
listed automatic-closing nozzle without a latch-open device.
Hoses used for dispensing or
transferring Class I, II or IIIA liquids, when not in use, shall be reeled,
racked or otherwise protected from mechanical damage.
(d)
2310.3.4
Portable containers.
Dispensing of Class
I, II or IIIA liquids into containers, other than fuel tanks, shall be in
accordance with paragraph (D)(4)(a)(2304.4.1) of this
rule.
(e)
2310.3.5 Liquefied petroleum gas.
Liquefied petroleum gas cylinders shall not be filled
at marine motor fuel-dispensing facilities unless approved. Storage facilities
for LP-gas cylinders shall be provided in accordance with
paragraph (G)(2307) of this
rule.
(4)
2310.4 Fueling of marine vehicles at other than
approved marine motor fuel-dispensing facilities.
Fueling of floating marine craft at other than a marine
motor fuel-dispensing facility shall comply with
paragraph
(J)(4)(a)(2310.4.1) and (J)(4)(b)(2310.4.2)
of this
rule.
(a)
2310.4.1 Class I liquid fuels.
Fueling of floating marine craft with Class I fuels at
other than a marine motor fuel-dispensing facility is
prohibited.
(b)
2310.4.2 Class II or III liquid fuels.
Fueling of floating marine craft with Class II or III
fuels at other than a marine motor fuel-dispensing facility shall be in
accordance with all of the following:
(i)
The premises and
operations shall be approved by the fire code official.
(ii)
Tank vehicles
and fueling operations shall comply with paragraph (F)(6)(
5706.6) of rule
1301:7-7-57
of the Administrative Code.
(iii)
The dispensing
nozzle shall be of the listed automatic-closing type without a latch-open
device.
(iv)
Nighttime deliveries shall only be made in lighted
areas.
(v)
The tank vehicle flasher lights shall be in operation
while dispensing.
(vi)
Fuel expansion space shall be left in each fuel tank to
prevent overflow in the event of temperature
increase.
(5)
2310.5 Fire
prevention regulations. General fire safety regulations for marine motor
fuel-dispensing facilities shall comply with
paragraphs
(J)(5)(a)(2310.5.1)
to (J)(5)(g)(2310.5.7)
of this
rule.
(a)
2310.5.1 Housekeeping.
Marine motor fuel-dispensing facilities shall be maintained
in a neat and orderly manner. Accumulations of rubbish or waste oils in
excessive amounts shall be prohibited.
(b)
2310.5.2
Spills.
Spills of Class I, II or IIIA
liquids at or on the water shall be reported immediately to the fire department
and jurisdictional authorities.
(c)
2310.5.3
Rubbish containers.
Containers with
tight-fitting or self-closing lids shall be provided for temporary storage of
combustible debris, rubbish and waste material. The rubbish containers shall be
constructed entirely of materials that comply with any one of the
following:
(i)
Noncombustible materials.
(ii)
Materials that
meet a peak rate of heat release not exceeding 300
kW/m2
when tested in
accordance with ASTM E 1354 as listed in rule
1301:7-7-80
of the Administrative Code at an incident heat flux of 50
kW/m2in the horizontal orientation.
(d)
2310.5.4 Marine vessels and craft.
Vessels or craft shall not be made fast to fuel docks
serving other vessels or craft occupying a berth at a marine motor
fuel-dispensing facility.
(e)
2310.5.5 Sources of ignition.
Construction, maintenance, repair and reconditioning
work involving the use of open flames, arcs or spark-producing devices shall
not be performed at marine motor fuel-dispensing facilities or within 50 feet
(15 240 mm) of the dispensing facilities, including piers, wharves or floats,
except for emergency repair work approved in writing by the fire code official.
Fueling shall not be conducted at the pier, wharf or float during the course of
such emergency repairs.
(i)
2310.5.5.1 Smoking. Smoking or open flames
shall be prohibited within 50 feet (15 240 mm) of fueling operations. "No
Smoking" signs complying with paragraph (J)(310) of
rule
1301:7-7-03
of the Administrative Code shall be posted conspicuously about the
premises. Such signs shall have letters not less than 4 inches (102 mm) in
height on a background of contrasting color.
(f)
2310.5.6
Preparation of tanks for fueling.
Boat
owners and operators shall not offer their craft for fueling unless the tanks
being filled are properly vented to dissipate fumes to the outside
atmosphere.
(g)
2310.5.7 Warning signs.
Warning signs shall be predominately displayed at the face
of each wharf, pier or float at such elevation as to be clearly visible from
the decks of marine craft being fueled. Such signs shall have letters not less
than 3 inches (76 mm) in height on a background of contrasting color bearing
the following or approved equivalent wording:
"WARNING
NO SMOKING-STOP ENGINE WHILE
FUELING,
SHUT OFF ELECTRICITY.
DO NOT START ENGINE UNTIL AFTER
BELOW
DECK SPACES ARE
VENTILATED."
(6)
2310.6 Fire
protection. Fire protection features for marine motor fuel-dispensing
facilities shall comply with
paragraphs (J)(6)(a)(2310.6.1)
to (J)(6)(d)(2310.6.4)
of this rule.
(a)
2310.6.1
Standpipe hose stations.
Fire hose, where
provided, shall be enclosed within a cabinet, and hose stations shall be
labeled: "FIRE HOSE-EMERGENCY USE ONLY."
(b)
2310.6.2
Obstruction of fire protection equipment.
Materials shall not be placed on a pier in such a manner as
to obstruct access to fire-fighting equipment or piping system control
valves.
(c)
2310.6.3 Access.
Where
the pier is accessible to vehicular traffic, an unobstructed roadway to the
shore end of the wharf shall be maintained for access by fire
apparatus.
(d)
2310.6.4 Portable fire extinguishers.
Portable fire extinguishers in accordance with
paragraph (F)(906)
of rule
1301:7-7-09
of the Administrative Code, each having a minimum rating of 20-B:C,
shall be provided as follows:
(i)
One on each float.
(ii)
One on the pier
or wharf within 25 feet (7620 mm) of the head of the gangway to the float,
unless the office is within 25 feet (7620 mm) of the gangway or is on the float
and an extinguisher is provided thereon.
(K)
Section 2311 Repair garages
(1)
2311.1
General.
Repair garages shall comply with
this
paragraph and the
building code as listed in rule
1301:7-7-80
of the Administrative Code. Repair garages for vehicles that use more
than one type of fuel shall comply with the applicable provisions of this
paragraph for each type of fuel used.
Where a repair garage includes a motor
fuel-dispensing facility, the fuel-dispensing operation shall comply with the
requirements of this rule for motor fuel-dispensing
facilities.
(2)
2311.2 Storage and use of flammable and
combustible liquids.
The storage and use
of flammable and combustible liquids in repair garages shall comply with
rule
1301:7-7-57
of the Administrative Code and
paragraphs
(K)(2)(a)(2311.2.1)
to (K)(2)(d)(2311.2.4)
of this
rule.
(a)
2311.2.1 Cleaning of parts.
Cleaning of parts shall be conducted in approved parts
cleaning machines in accordance with rule
1301:7-7-57
of the Administrative Code.
(b)
2311.2.2
Waste oil, motor oil and other Class IIIB liquids.
Waste oil, motor oil and other Class IIIB liquids shall
be stored in tanks or containers
approved in accordance with rule
1301:7-7-57
of the Administrative Code, which are allowed to be stored and
dispensed from inside repair garages.
(i)
2311.2.2.1
Tank location. Tanks storing Class IIIB liquids in repair garages are
allowed to be located at, below or above grade, provided that adequate drainage
or containment is provided.
(ii)
2311.2.2.2
Liquid classification. Crankcase drainings shall be classified as Class
IIIB liquids unless otherwise determined by testing.
(c)
2311.2.3
Drainage and disposal of liquids and oil-soaked waste.
Garage floor drains, where provided, shall drain to oil
separators or traps discharging to a sewer in accordance with the
plumbing code as listed in rule
1301:7-7-80
of the Administrative Code. Contents of oil separators, traps and
floor drainage systems shall be collected at sufficiently frequent intervals
and removed from the premises to prevent oil from being carried into
sewers.
(i)
2311.2.3.1 Disposal of liquids. Crankcase
drainings and liquids shall not be dumped into sewers, streams or on the
ground, but shall be stored in tanks or containers in accordance with
rule
1301:7-7-57
of the Administrative Code until removed from the
premises.
(ii)
2311.2.3.2 Disposal of oily waste.
Self-closing metal cans shall be used for oily waste.
(d)
2311.2.4
Spray finishing. Spray finishing with flammable or combustible liquids
shall comply with rule
1301:7-7-24 of
the Administrative Code.
(3)
2311.3
Sources of ignition.
Sources of ignition
shall not be located within 18 inches (457 mm) of the floor and shall comply
with
rules
1301:7-7-03
and
1301:7-7-35 of the Administrative Code.
(a)
2311.3.1
Equipment.
Appliances and equipment
installed in a repair garage shall comply with the provisions of the
building code, the mechanical code and NFPA
70 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
2311.3.2
Smoking.
Smoking shall not be allowed in
repair garages except in approved locations.
(4)
2311.4
Below-grade areas.
Pits and below grade
work areas in repair garages shall comply with
paragraphs
(K)(4)(a)(2311.4.1)
to (K)(4)(c)(2311.4.3)
of this
rule.(a)
2311.4.1 Construction.
Pits and below-grade work areas shall be constructed in
accordance with the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
2311.4.2
Means of egress.
Pits and below-grade work
areas shall be provided with means of egress in accordance with rule
1301:7-7-10 of
the Administrative Code.
(c)
2311.4.3
Ventilation.
Where Class I liquids or
LP-gas are stored or used within a building having a basement or pit wherein
flammable vapors could accumulate, the basement or pit shall be provided with
mechanical ventilation in accordance with the mechanical code as listed
in rule
1301:7-7-80
of the Administrative Code, at a minimum rate of 11/2 cubic feet per
minute per square foot (cfm/ft2) [ 0.008
m3/(s"m2) to prevent the accumulation of flammable
vapors.
(5)
2311.5 Preparation of vehicles for repair.
For vehicles powered by gaseous fuels,
the fuel shutoff valves shall be closed prior to repairing any portion of the
vehicle fuel system.
Vehicles powered by gaseous fuels in
which the fuel system has been damaged shall be inspected and evaluated for
fuel system integrity prior to being brought into the repair garage. The
inspection shall include testing of the entire fuel delivery system for
leakage.
(6)
2311.6 Fire extinguishers.
Fire extinguishers shall be provided in accordance with
paragraph (F)(906) of rule
1301:7-7-09
of the Administrative Code.
(7)
2311.7
Repair garages for vehicles fueled by lighter-than-air fuels.
Repair garages for the conversion and repair of
vehicles that use CNG, liquefied natural gas (LNG), hydrogen or other
lighter-than-air motor fuels shall be in accordance with
paragraphs (K)(7)( 2311.7)
to
(K)(7)(b)(iii)(2311.7.2.3)
of this rule in addition to the
other requirements of
paragraph (K)(2311)
of this
rule.
Exceptions:
1.
Repair garages
where work is not performed on the fuel system and is limited to exchange of
parts and maintenance not requiring open flame or welding on the CNG-, LNG-,
hydrogen- or other lighter-than-air-fueled motor vehicle.
2.
Repair garages for
hydrogen-fueled vehicles where work is not performed on the hydrogen storage
tank and is limited to the exchange of parts and maintenance not requiring open
flame or welding on the hydrogen-fueled vehicle. During the work, the entire
hydrogen fuel system shall contain a quantity that is less than 200 cubic feet
( 5.6 m3) of hydrogen.
(a)
2311.7.1
Ventilation.
Repair garages used for the
repair of natural gas-or hydrogen-fueled vehicles shall be provided with
a mechanical ventilation system. The mechanical ventilation
system shall be in accordance with the
mechanical code as listed in
rule
1301:7-7-80
of the Administrative Code and
paragraphs
(K)(7)(a)(i)(2311.7.1.1) and (K)(7)(a)(ii)(2311.7.1.2)
of this
rule.
Exception:
Repair garages with natural ventilation when
approved.
(i)
2311.7.1.1 Design. Indoor locations shall
be ventilated utilizing air supply inlets and exhaust outlets arranged to
provide uniform air movement to the extent practical. Inlets shall be uniformly
arranged on exterior walls near floor level. Outlets shall be located at the
high point of the room in exterior walls or the roof.
Ventilation shall be by a continuous
mechanical ventilation system or by a mechanical ventilation system activated
by a continuously monitoring natural gas detection system or, for hydrogen, a
continuously monitoring flammable gas detection system, each activating at a
gas concentration of not more than 25 per cent of the lower
flammable limit (LFL). In all cases, the system shall shut down the fueling
system in the event of failure of the ventilation system.
The ventilation rate shall be not less
than 1 cubic foot per minute per 12 cubic feet [ 0.00139
m3
x (s "
m3)] of room
volume.
(ii)
2311.7.1.2 Operation. The mechanical
ventilation system shall operate continuously.
Exceptions:
1.
Mechanical
ventilation systems that are interlocked with a gas detection system designed
in accordance with paragraphs (K)(7)(b)(2311.7.2) to
(K)(7)(b)(iii)(2311.7.2.3) of this
rule.
2.
Mechanical ventilation systems in repair garages that
are used only for repair of vehicles fueled by liquid fuels or odorized gases,
such as CNG, where the ventilation system is electrically interlocked with the
lighting circuit.
(b)
2311.7.2
Gas detection system.
Repair garages used
for repair of vehicles fueled by nonodorized gases, including, but not limited
to, hydrogen and nonodorized LNG, shall be provided with a flammable gas
detection system.
(i)
2311.7.2.1 System design. The flammable
gas detection system shall be listed or approved and shall be calibrated to the
types of fuels or gases used by vehicles to be repaired. The gas detection
system shall be designed to activate when the level of flammable gas exceeds 25
per cent of the lower flammable limit (LFL). Gas detection
shall be provided in lubrication or chassis service pits of repair garages used
for repairing nonodorized LNG-fueled vehicles.
(a)
2311.7.2.1.1 Gas detection system components.
Gas detection system control units shall be listed and
labeled in accordance with UL 864 or UL 2017 as listed in rule
1301:7-7-80
of the Administrative Code. Gas detectors shall be listed and labeled
in accordance with UL 2075 as listed in rule
1301:7-7-80
of the Administrative Code for use with the gases and vapors being
detected.
(ii)
2311.7.2.2 Operation. Activation of the
gas detection system shall result in all of the following:
(a)
Initiation of
distinct audible and visual alarm signals in the repair garage.
(b)
Deactivation of
all heating systems located in the repair garage.
(c)
Activation of the
mechanical ventilation system, where the system is interlocked with gas
detection.
(iii)
2311.7.2.3 Failure of the gas detection
system. Failure of the gas detection system shall result in the
deactivation of the heating system, activation of the mechanical ventilation
system where the system is interlocked with gas detection and causes a trouble
signal to sound in an occupied area or other location approved by the
fire code official.
(8)
2311.8
Defueling equipment required at vehicle maintenance and repair
facilities. Facilities for repairing hydrogen fuel systems on
hydrogen-fueled vehicles shall have equipment to defuel vehicle storage tanks.
Where work must be performed on a vehicle's fuel storage tank for the purpose
of maintenance, repair or cylinder certification, defueling and purging shall
be conducted in accordance with paragraph (I)(6)( 2309.6)
of this rule.
(L)
Section 2312 Service station at a bulk plant
or terminal
(1)
2312.1 General.
That portion of a bulk plant property where
flammable or combustible liquids are stored and dispensed from fixed equipment
into the fuel tanks of motor vehicles, marine craft or approved containers
shall comply with this paragraph and NFPA 30A as listed in rule
1301:7-7-80
of the Administrative Code.
Exception:
The dispensing of diesel fuel at a terminal or bulk plant
into a motor vehicle that is transporting petroleum products or equipment
essential to the operation of the terminal or bulk plant, provided that the
motor vehicle is owned or leased by or operated under a contract with a person
who has been issued a motor fuel dealers license under section
5735.02 of the Revised Code. For
such dispensing, the provisions of this rule governing capacity limitations
shall not apply.
(2)
2312.2 Separation.
All equipment utilized in connection with the storage and
dispensing operations of a motor fuel-dispensing facility shall be separated by
a minimum of 100 feet from the area in which aboveground bulk plant operations
are conducted and by a security fence. Any gates in the required fence shall be
secured against unauthorized entry.
(3)
2312.3 Independent operations.
Motor fuel-dispensing facility operations shall
be totally independent of the bulk plant operations to include:
(a)
Above-ground tanks located in the bulk plant shall not
supply dispensing devices at the motor fuel-dispensing
facility.
(b)
Storage tanks at the motor fuel-dispensing
facility shall not be connected by piping to aboveground tanks located in the
bulk plant.
Replaces: 1301:7-7-23