Current through all regulations passed and filed through September 16, 2024
(A)
Section 2101
General
(1)2101.1 Scope. Dry cleaning plants and their operations shall
comply with the requirements of this rule.
(2)
2101.2 Permit
required. Permits shall be required as set forth in rule
1301:7-7-01
of the Administrative Code.
(B)
Section 2102
Definitions
(1) 2102.1 Definitions. The following terms are defined in rule
1301:7-7-02 of the
Administrative Code.
"Dry cleaning."
"Dry cleaning plant."
"Dry cleaning room."
"Dry cleaning system."
"Solvent or liquid
classifications."
"Class I solvents."
Class II solvents.
"Class IIIA solvents."
"Class IIIB solvents."
"Class IV solvents."
(C)
Section 2103 Classifications
(1)2103.1 Solvent
classification. Dry cleaning solvents shall be classified according to their
flash points as follows:
(a)
Class I solvents are liquids having a flash point below
100°F (38°C).
(b)
Class II solvents are liquids having a flash point at
or above 100°F (38°C) and below 140°F (60°C).
(c)
Class IIIA
solvents are liquids having a flash point at or above 140°F (60°C) and below
200°F (93°C).
(d)
Class IIIB solvents are liquids having a flash point at
or above 200°F (93°C).
(e)
Class IV solvents are liquids classified as
nonflammable.
(2)
2103.2 Classification of dry cleaning plants and
systems. Dry cleaning plants and systems shall be classified based on the
solvents used as follows:
1.
Type I-systems using Class I solvents.
2.
Type II-systems
using Class II solvents.
3.
Type III-A-systems using Class IIIA
solvents.
4.
Type III-B-systems using Class IIIB
solvents.
5.
Type IV-systems using Class IV solvents in which dry
cleaning is not conducted by the public.
6.
Type V-systems
using Class IV solvents in which dry cleaning is conducted by the public.
Spotting and pretreating operations
conducted in accordance with paragraph (F)(2106) of this rule shall not change
the type of the dry cleaning plant.
(a)
2103.2.1 Multiple
solvents. Dry cleaning plants using more than one class of solvent for dry
cleaning shall be classified based on the numerically lowest solvent
class.
(3)
2103.3 Design.
The occupancy classification, design and construction of dry cleaning plants
shall comply with the applicable requirements of the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(D)
Section 2104
General requirements
(1)2104.1 Prohibited use. Type I dry cleaning plants shall be
prohibited. Limited quantities of Class I solvents stored and used in
accordance with this paragraph shall not be prohibited in dry cleaning
plants.
(2)
2104.2 Building services. Building services and systems
shall be designed, installed and maintained in accordance with this paragraph
and rule
1301:7-7-06
of the Administrative Code.
(a)
2104.2.1 Ventilation. Ventilation shall be provided in
accordance with Section 502 of the mechanical code and DOL
29 CFR Part
1910.1000 as listed in rule
1301:7-7-80
of the Administrative Code, where applicable.
(b)
2104.2.2 Heating.
In Type II dry cleaning plants, heating shall be by indirect means using steam,
hot water or hot oil only.
(c)
2104.2.3
Electrical wiring and equipment. Electrical wiring and equipment in dry
cleaning rooms or other locations subject to flammable vapors shall be
installed in accordance with NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code.
(d)
2104.2.4 Bonding
and grounding. Storage tanks, treatment tanks, filters, pumps, piping, ducts,
dry cleaning units, stills, tumblers, drying cabinets and other such equipment,
where not inherently electrically conductive, shall be bonded together and
grounded. Isolated equipment shall be grounded.
(E)
Section 2105 Operating requirements
(1)
2105.1 General.
The operation of dry cleaning systems shall comply with the requirements of
paragraphs (E)(1)(a)(2105 1 1) to (E)(3)( 2105.3) of this rule.
(a)
2105.1.1 Written
instructions. Written instructions covering the proper installation and safe
operation and use of equipment and solvent shall be given to the buyer.
(i)
2105.1.1.1 Type
II, III-A, III-B and IV systems. In Type II, III-A, III-B and IV dry cleaning
systems, machines shall be operated in accordance with the operating
instructions furnished by the machinery manufacturer. Employees shall be
instructed as to the hazards involved in their departments and in the work they
perform.
(ii)
2105.1.1.2 Type V systems. Operating instructions for
customer use of Type V dry cleaning systems shall be conspicuously posted in a
location near the dry cleaning unit. A telephone number shall be provided for
emergency assistance.
(b)
2105.1.2
Equipment identification. The manufacturer shall provide nameplates on dry
cleaning machines indicating the class of solvent for which each machine is
designed.
(c)
2105.1.3 Open systems prohibited. Dry cleaning by
immersion and agitation in open vessels shall be prohibited.
(d)
2105.1.4
Prohibited use of solvent. The use of solvents with a flash point below that
for which a machine is designed or listed shall be prohibited.
(e)
2105.1.5
Equipment maintenance and housekeeping. Proper maintenance and operating
practices shall be observed in order to prevent the leakage of solvent or the
accumulation of lint. The handling of waste material generated by dry cleaning
operations and the maintenance of facilities shall comply with the provisions
of this paragraph.
(i)
2105.1.5.1 Floors. Class I and II liquids shall not be
used for cleaning floors.
(ii)
2105.1.5.2
Filters. Filter residue and other residues containing solvent shall be handled
and disposed of in covered metal containers.
(iii)
2105.1.5.3
Lint. Lint and refuse shall be removed from traps daily, deposited in approved
waste cans, removed from the premises, and disposed of safely. At all other
times, traps shall be held securely in place.
(iv)
2105.1.5.4
Customer areas. In Type V dry cleaning systems, customer areas shall be kept
clean.
(2)
2105.2 Type II
systems. Special operating requirements for Type II dry cleaning systems shall
comply with the provisions of paragraphs (E)(2)(a)(2105.2.1) to
(E)(2)(c)(2105.2.3) of this rule.
(a)
2105.2.1 Inspection of materials. Materials to be dry
cleaned shall be searched thoroughly and foreign materials, including matches
and metallic substances, shall be removed.
(b)
2105.2.2 Material
transfer. In removing materials from the washer, provisions shall be made for
minimizing the dripping of solvent on the floor. Where materials are
transferred from a washer to a drain tub, a nonferrous metal drip apron shall
be placed so that the apron rests on the drain tub and the cylinder of the
washer.
(c)
2105.2.3 Ventilation. A mechanical ventilation system
which is designed to exhaust 1 cubic foot of air per minute for each square
foot of floor area [ 0.0058 m3/(s.m2)] shall be installed in
dry cleaning rooms and in drying rooms. The ventilation system shall operate
automatically when the dry cleaning equipment is in operation and shall have
manual controls at an approved location.
(3)
2105.3 Type IV
and V systems. Type IV and V dry cleaning systems shall be provided with an
automatically activated exhaust ventilation system to maintain a minimum of 100
feet per minute ( 0.51 m/s) air velocity through the loading door when the door
is opened. Such systems for dry cleaning equipment shall comply with the
mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
Exception: Dry cleaning units are not
required to be provided with exhaust ventilation where an exhaust hood is
installed immediately outside of and above the loading door which operates at
an airflow rate as follows:
Q = 100 x ALD (Equation 21-1)
where:
Q = flow rate exhausted through the
hood, cubic feet per minute (m3/s).
ALD = area of the loading door,
square feet (m2).
(F)
Section 2106 Spotting and pretreating
(1)
2106.1 General.
Spotting and pretreating operations and equipment shall comply with the
provisions of paragraphs (F)(2)( 2106.2) to (F)(5)( 2106.5) of this
rule.
(2)
2106.2 Class I solvents. The maximum quantity of Class
I solvents permitted at any work station shall be 1 gallon (4 L). Spotting or
prespotting shall be permitted to be conducted with Class I solvents where they
are stored in and dispensed from approved safety cans or in sealed DOT-approved
metal shipping containers of not more than 1-gallon (4 L) capacity.
(a)
2106.2.1 Spotting
and prespotting. Spotting and prespotting shall be permitted to be conducted
with Class I solvents where dispensed from plastic containers of not more than
1 pint ( 0.5 L) capacity.
(3)
2106.3 Class II
and III solvents. Scouring, brushing, and spotting and pretreating shall be
permitted to be conducted with Class II or III solvents. The maximum quantity
of Class II or III solvents permitted at any work station shall be 1 gallon (4
L). In other than Group H-2 occupancy, the aggregate quantities of solvents
shall not exceed the maximum allowable quantity per control area for use-open
system.
(a)
2106.3.1 Spotting tables. Scouring, brushing or spotting
tables on which articles are soaked in solvent shall have a liquid-tight top
with a curb on all sides not less than 1 inch (25 mm) high. The top of the
table shall be pitched to ensure thorough draining to a 11/2-inch (38 mm) drain
connected to an approved container.
(b)
2106.3.2 Special
handling. Where approved, articles that cannot be washed in the usual washing
machines are allowed to be cleaned in scrubbing tubs. Scrubbing tubs shall
comply with the following:
(i)
Only Class II or III liquids shall be
used.
(ii)
The total amount of solvent used in such open
containers shall not exceed 3 gallons (11 L).
(iii)
Scrubbing tubs
shall be secured to the floor.
(iv)
Scrubbing tubs
shall be provided with permanent 11/2-inch (38 mm) drains. Such drain shall be
provided with a trap and shall be connected to an approved
container.
(c)
2106.3.3 Ventilation. Scrubbing tubs, scouring,
brushing or spotting operations shall be located such that solvent vapors are
captured and exhausted by the ventilating system.
(d)
2106.3.4 Bonding
and grounding. Metal scouring, brushing and spotting tables and scrubbing tubs
shall be permanently and effectively bonded and grounded.
(4)
2106.4
Type IV systems. Flammable and combustible liquids used for spotting operations
shall be stored in approved safety cans or in sealed DOTn-approved shipping
containers of not more than 1 gallon (4 L) in capacity. Aggregate amounts shall
not exceed 10 gallons (38 L).
(5)
2106.5 Type V
systems. Spotting operations using flammable or combustible liquids are
prohibited in Type V dry cleaning systems.
(G)
Section 2107 Dry
cleaning systems
(1) 2107.1 General equipment requirements. Dry cleaning systems,
including dry cleaning units, washing machines, stills, drying cabinets,
tumblers and their appurtenances, including pumps, piping, valves, filters and
solvent coolers, shall be installed and maintained in accordance with NFPA 32
as listed in rule
1301:7-7-80
of the Administrative Code. The construction of buildings in which such systems
are located shall comply with the requirements of this paragraph and the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
2107.2 Type II
systems. Type II dry cleaning and solvent tank storage rooms shall not be
located below grade or above the lowest floor level of the building and shall
comply with paragraphs (G)(2)(a)(2107.2.1) to (G)(2)(c)( 2107.2 3) of this
rule.
Exception: Solvent storage tanks
installed underground, in vaults or in special enclosures in accordance with
rule
1301:7-7-57
of the Administrative Code.
(a)
2107.2.1 Fire-fighting access. Type II dry cleaning
plants shall be located so that access is provided and maintained from one side
for fire-fighting and fire control purposes in accordance with paragraph
(C)(503) of rule
1301:7-7-05
of the Administrative Code.
(b)
2107.2.2 Number
of means of egress. Type II dry cleaning rooms shall have not less than two
means of egress doors located at opposite ends of the room, not less than one
of which shall lead directly to the outside.
(c)
2107.2.3 Spill
control and secondary containment. Curbs, drains, or other provisions for spill
control and secondary containment shall be provided in accordance with
paragraph (D)(2)( 5004.2) of rule
1301:7-7-50
of the Administrative Code to collect solvent leakage and fire protection water
and direct it to a safe location.
(3)
2107.3 Solvent
storage tanks. Solvent storage tanks for Class II, IIIA and IIIB liquids shall
conform to the requirements of rule
1301:7-7-57
of the Administrative Code and be located underground or outside, above
ground.
Exception: As provided in NFPA 32 as
listed in rule
1301:7-7-80
of the Administrative Code for inside storage or treatment tanks.
(H)
Section 2108 Fire protection
(1)2108.1 General.
Where required by this paragraph, fire protection systems, devices and
equipment shall be installed, inspected, tested and maintained in accordance
with rule
1301:7-7-09
of the Administrative Code.
(2)
2108.2 Automatic
sprinkler system. An automatic sprinkler system shall be installed in
accordance with paragraph (C)(3)(a)(i)(903.3. 1.1) of rule
1301:7-7-09
of the Administrative Code throughout dry cleaning plants containing Type II,
Type III-A or Type III-B dry cleaning systems.
Exceptions:
1.
An automatic
sprinkler system shall not be required in Type III-A dry cleaning plants where
the aggregate quantity of Class III-A solvent in dry cleaning machines and
storage does not exceed 330 gallons (1250 L) and dry cleaning machines are
equipped with a feature that will accomplish any one of the following:
1.1
Prevent oxygen
concentrations from reaching 8 per cent or more by volume.
1.2
Keep the
temperature of the solvent not less than 30°F ( 16.7 °C) below the flash
point.
1.3
Maintain the solvent vapor concentration at a level
lower than 25 per cent of the lower explosive limit (LEL).
1.4
Utilize equipment
approved for use in Class I, Division 2 hazardous locations in accordance with
NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code.
1.5
Utilize an
integrated dry-chemical, clean agent or water-mist automatic fire-extinguishing
system designed in accordance with rule
1301:7-7-09
of the Administrative Code.
2.
An automatic
sprinkler system shall not be required in Type III-B dry cleaning plants where
the aggregate quantity of Class III-B solvent in dry cleaning machines and
storage does not exceed 3,300 gallons (12 490 L).
(3)
2108.3 Automatic
fire-extinguishing systems. Type II dry cleaning units, washer- extractors, and
drying tumblers in Type II dry cleaning plants shall be provided with an
approved automatic fire-extinguishing system installed and maintained in
accordance with rule
1301:7-7-09
of the Administrative Code.
Exception: Where approved, a manual
steam jet not less than 3/4 inch (19 mm) with a continuously available steam
supply at a pressure not less than 15 pounds per square inch gauge (psig) (103
kPa) is allowed to be substituted for the automatic fire-extinguishing
system.
(4)
2108.4 Portable fire extinguishers. Portable fire
extinguishers shall be selected, installed and maintained in accordance with
this paragraph and paragraph (F) (906) of rule
1301:7-7-09
of the Administrative Code. A minimum of two 2-A:10-B:C portable fire
extinguishers shall be provided near the doors inside dry cleaning rooms
containing Type II, Type III-A and Type III-B dry cleaning systems.
Replaces: 1301:7-7-12.