Current through all regulations passed and filed through September 16, 2024
(A)
Section
1001 General
(1)
1001.1 General.
Buildings or portions thereof shall be provided with a means
of egress system as required by this rule and in compliance with
accessibility requirements as set forth in chapter 11 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code. The provisions of this
rule shall control the design, construction and arrangement of
means of egress components required to provide an approved means of egress from
structures and portions thereof. Paragraphs (C)(1003)
to (DD)(1030) of this rule shall apply to new
construction. The new construction requirements of this rule for the
means of egress in structures regulated by the building code as listed in rule
1301:7-7-80
of the Administrative Code submitted for plan review in accordance with this
paragraph are subject to and do not supersede or otherwise conflict with the
requirements of paragraph (D)(2)(a)(104.2.1) of rule
1301:7-7-01
of the Administrative Code. Paragraph (EE)(1031) of this
rule shall apply to existing buildings. Except for maintenance
requirements contained in paragraph (EE)(1031) of this rule,
the provisions of this rule for a means of egress system in existing buildings
shall apply only in accordance with paragraph (B)(1)(c)( 102.1)
of rule
1301:7-7-01
of the Administrative Code.
(2)
1001.2
Minimum requirements.
It shall be unlawful
to alter a building or structure in a manner that will reduce the number of
exits or the capacity of the means of egress to less than required by this
code.
(B)
Section 1002 Definitions
(1)
[BE] 1002.1
Definitions. The following terms are defined in
rule
1301:7-7-02 of the
Administrative Code.
"Accessible means of
egress."
"Aisle accessway."
"Alternating tread device."
"Area of
refuge."
"Bleachers."
"Breakout."
"Common path of egress
travel."
"Corridor."
"Door,
balanced."
"Egress
court."
"Emergency escape and rescue
opening."
"Exit."
"Exit
access."
"Exit access
doorway."
"Exit access
ramp."
"Exit access
stairway."
"Exit
discharge."
"Exit discharge, level
of."
"Exit,
horizontal."
"Exit
passageway."
"Exterior exit
ramp."
"Exterior exit
stairway."
"Fire exit
hardware."
"Fixed
seating."
"Flight."
"Folding and telescopic
seating."
"Grandstand."
"Guard."
"Handrail."
"Interior exit
ramp."
"Interior exit
stairway."
"Low energy power-operated
door."
"Means of
egress."
"Merchandise
pad."
"Nosing."
"Occupant
load."
"Open-ended
corridor."
"Panic
hardware."
"Photoluminescent."
"Power-assisted door."
"Power-operated
door."
"Public way."
"Ramp."
"Scissor stairway."
"Self-luminous."
"Smoke-protected assembly
seating."
"Stair."
"Stairway."
"Stairway,
interior."
"Stairway, spiral."
"Temporary door locking
device."
"Winder."
(C)
[BE]
Section 1003 General means of egress
(1)
1003.1
Applicability.
The general requirements
specified in paragraphs (C)(1003) to
(O)(1015) of this rule shall apply to all three elements of
the means of egress system, in addition to those specific requirements for the
exit access, the exit and the exit discharge detailed elsewhere in this
rule.
(2)
[BE] 1003.2 Ceiling height.
The means of egress shall have a ceiling height of not
less than 7 feet 6 inches (2286 mm).
Exceptions:
1.
Sloped ceilings in
accordance with section 1208.2 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
2.
Ceilings of
dwelling units and sleeping units within residential occupancies in accordance
with section 1208.2 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
3.
Allowable
projections in accordance with paragraph (C)(3)( 1003.3)
of this rule.
4.
Stair headroom in
accordance with paragraph (K)(3)( 1011.3) of this
rule.
5.
Door height in accordance with paragraph
(J)(1)(a)(1010.1.1) of this rule.
6.
Ramp headroom in
accordance with paragraph (L)(5)(b)(1012.5.2) of this
rule.
7.
The clear height of floor levels in vehicular and
pedestrian traffic areas of public and private parking garages in accordance
with section 406.4.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
8.
Areas above and
below mezzanine floors in accordance with section 505.2 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code.
(3)
[BE] 1003.3
Protruding objects.
Protruding objects on
circulation paths shall comply with the requirements of
paragraphs (C)(3)(a)(1003.3.1)
to
(C)(3)(d)(1003.3.4)
of this rule.
(a)
[BE]
1003.3.1 Headroom.
Protruding objects are
permitted to extend below the minimum ceiling height required by
paragraph (C)(2)( 1003.2)
of this rule where
a minimum headroom of 80 inches (2032 mm) is provided over any walking surface,
including walks, corridors, aisles and passageways. Not more than 50
per cent of the ceiling area of a means of egress shall be
reduced in height by protruding objects.
Exception:
Door closers and stops shall not reduce headroom to
less than 78 inches (1981 mm).
A barrier shall be provided where the
vertical clearance is less than 80 inches (2032 mm) high. The leading edge of
such a barrier shall be located 27 inches (686 mm) maximum above the
floor.
(b)
[BE] 1003.3.2 Post-mounted objects.
A free-standing object mounted on a post or pylon shall
not overhang that post or pylon more than 4 inches (102 mm) where the lowest
point of the leading edge is more than 27 inches (686 mm) and less than 80
inches (2032 mm) above the walking surface. Where a sign or other obstruction
is mounted between posts or pylons and the clear distance between the posts or
pylons is greater than 12 inches (305 mm), the lowest edge of such sign or
obstruction shall be 27 inches (685 mm) maximum or 80 inches (2032 mm) minimum
above the finished floor or ground.
Exception:
These requirements shall not apply to sloping portions
of handrails between the top and bottom riser of stairs and above the ramp run.
(c)
[BE] 1003.3.3 Horizontal projections.
Objects with leading edges more than 27 inches (685 mm)
and not more than 80 inches (2032 mm) above the floor shall not project
horizontally more than 4 inches (102 mm) into the circulation path.
Exception:
Handrails are permitted to protrude 41/2 inches (114 mm)
from the wall.
(d)
[BE] 1003.3.4 Clear width.
Protruding objects shall not reduce the minimum clear
width of accessible routes.
(4)
[BE] 1003.4
Floor surface.
Walking surfaces of the
means of egress shall have a slip-resistant surface and be securely
attached.
(5)
[BE] 1003.5 Elevation change.
Where changes in elevation of less than 12 inches (305
mm) exist in the means of egress, sloped surfaces shall be used. Where the
slope is greater than one unit vertical in 20 units horizontal (5-
per
cent slope), ramps complying with
paragraph (K)(1012)
of this rule shall be used. Where the difference in elevation
is 6 inches (152 mm) or less, the ramp shall be equipped with either handrails
or floor finish materials that contrast with adjacent floor finish
materials.
Exceptions:
1.
A single step with
a maximum riser height of 7 inches (178 mm) is permitted for buildings with
occupancies in Groups F, H, R-2 and R-3 as applicable in
paragraph (A)(1)( 1001.1) of this rule, and Groups S
and U at exterior doors not required to be accessible by chapter 11 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
2.
A stair with a
single riser or with two risers and a tread is permitted at locations not
required to be accessible by chapter 11 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code, where the risers and treads comply with
paragraph (K)(5)( 1011.5) of this rule, the
minimum depth of the tread is 13 inches (330 mm) and not less than one handrail
complying with paragraph (N)(1014) of this
rule is provided within 30 inches (762 mm) of the centerline of the
normal path of egress travel on the stair.
3.
A step is
permitted in aisles serving seating that has a difference in elevation less
than 12 inches (305 mm) at locations not required to be accessible by chapter
11 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code, provided that the risers and treads comply
with
paragraph (CC)(13)( 1029.13)
of this
rule and the aisle is provided with a handrail complying with
paragraph (CC)(15)( 1029.15)
of this
rule.
Throughout a story in a Group I-2
occupancy, any change in elevation in portions of the means of egress that
serve nonambulatory persons shall be by means of a ramp or sloped
walkway.
(6)
[BE] 1003.6 Means of egress
continuity.
The path of egress travel
along a means of egress shall not be interrupted by a building element other
than a means of egress component as specified in this rule.
Obstructions shall not be placed in the minimum width or required capacity of a
means of egress component except projections permitted by this
rule. The minimum width or required capacity of a means of
egress system shall not be diminished along the path of egress
travel.
(7)
[BE] 1003.7 Elevators, escalators and moving
walks.
Elevators, escalators and moving
walks shall not be used as a component of a required means of egress from any
other part of the building.
Exception:
Elevators used as an accessible means of egress in
accordance with paragraph (I)(4)( 1009.4) of this
rule.
(D)
Section
1004 Occupant load
(1)
[BE] 1004.1 Design occupant load. In
determining means of egress requirements, the number of occupants for whom
means of egress facilities are provided shall be determined in accordance with
this
paragraph.(a)
[BE] 1004.1.1 Cumulative occupant loads.
Where the path of egress travel includes intervening rooms, areas or spaces,
cumulative occupant loads shall be determined in accordance with this
paragraph.(i)
[BE] 1004.1.1.1 Intervening spaces or accessory
areas. Where occupants egress from one or more rooms, areas or spaces
through others, the design occupant load shall be the combined occupant load of
interconnected accessory or intervening spaces. Design of egress path capacity
shall be based on the cumulative portion of occupant loads of all rooms, areas
or spaces to that point along the path of egress travel
(ii)
[BE]
1004.1.1.2 Adjacent levels for mezzanines. That portion of the occupant
load of a mezzanine with required egress through a room, area or space on an
adjacent level shall be added to the occupant load of that room, area or
space.
(iii)
[BE] 1004.1.1.3 Adjacent stories. Other
than for the egress components designed for convergence in accordance with
paragraph (E)(6)( 1005.6) of this rule, the
occupant load from separate stories shall not be added.
(b)
[BE] 1004.1.2 Areas without fixed seating. The
number of occupants shall be computed at the rate of one occupant per unit of
area as prescribed in Table 1004.1.2
of this rule. For areas
without fixed seating, the occupant load shall be not less than that number
determined by dividing the floor area under consideration by the occupant load
factor assigned to the function of the space as set forth in Table 1004.1.2
of this rule. Where an intended function is not listed in
Table 1004.1.2
of this rule, the fire code official shall
establish a function based on a listed function that most nearly resembles the
intended function.
Exception:
Where approved by the building official, the actual
number of occupants for whom each occupied space, floor or building is
designed, although less than those determined by calculation, shall be
permitted to be used in the determination of the design occupant
load.
[BE] Table
1004.1.2
Maximum floor area allowances per
occupant
Function of
space
|
Occupant load
factora
|
Accessory storage
areas-mechanical equipment room
|
300 gross
|
Agricultural
building
|
300 gross
|
Aircraft hangars
|
500 gross
|
Airport terminal
Baggage claim
Baggage handling
Concourse
Waiting areas
|
20 gross
300 gross
100 gross
15 gross
|
Assembly
Gaming floors (keno, slots,
etc.)
Exhibit gallery and
museum
|
11 gross
30 net
|
Assembly with fixed
seats
|
See paragraph
(D)(4)( 1004.4) of this rule
|
Assembly without fixed
seats
Concentrated (chairs only-not
fixed)
Standing space
Unconcentrated (tables and
chairs)
|
7 net
5 net
15 net
|
Bowling centers, allow 5
persons for each lane including 15 feet of runway, and for additional
areas
|
7 net
|
Business areas
|
100 gross
|
Courtrooms-other than fixed
seating areas
|
40 net
|
Day care
|
35 net
|
Dormitories
|
50 gross
|
Educational
Classroom area
Shops and other vocational room
areas
|
20 net
50 net
|
Exercise rooms
|
50 gross
|
Group H-5 fabrication and
manufacturing areas
|
200 gross
|
Industrial areas
|
100 gross
|
Institutional
areas
Inpatient treatment
areas
Outpatient areas
Sleeping areas
|
240 gross
100 gross
120 gross
|
Kitchens,
commercial
|
200 gross
|
Library
Reading rooms
Stack area
|
50 net
100 gross
|
Locker rooms
|
50 gross
|
Mall buildings-covered and
open
|
See Section 402.8.2 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code
|
Mercantile
Storage, stock, shipping
areas
|
60 gross
300 gross
|
Parking garages
|
200 gross
|
Residential
|
200 gross
|
Skating rinks, swimming
pools
Rink and pool
Decks
|
50 gross
15 gross
|
Stages and
platforms
|
15 net
|
Warehouses
|
500 gross
|
For SI: 1 square foot = 0.0929
m2, 1 foot = 304.8 mm.
a. Floor area in square feet per
occupant.
(2)
[BE] 1004.2
Increased occupant load.
The occupant load
permitted in any building or portion thereof, is permitted to be increased from
that number established for the occupancies in Table 1004.1.2 of this
rule provided that all other requirements of the code are met based on
such modified number and the occupant load does not exceed one occupant per 7
square feet ( 0.65 m2) of occupiable floor space.
Where required by the fire code official pursuant to paragraph
(A)(1)( 1001.1) of this rule, an approved aisle, seating or
fixed equipment diagram substantiating any increase in occupant load shall be
submitted. Where required by the fire code official, such diagram shall be
posted. At locations or in structures not regulated by the building
code as listed in rule
1301:7-7-80
of the Administrative Code, the increased occupant load shall be approved by
the fire code official.
(3)
[BE] 1004.3
Posting of occupant load. Every room or
space that is an assembly occupancy shall have the occupant load of the room or
space posted in a conspicuous place, near the main exit or exit access doorway
from the room or space. Posted signs shall be of an approved legible permanent
design and shall be maintained by the owner or the owner's authorized
agent.
(4)
[BE] 1004.4 Fixed seating.
For areas having fixed seats and aisles, the occupant
load shall be determined by the number of fixed seats installed therein. The
occupant load for areas in which fixed seating is not installed, such as
waiting spaces, shall be determined in accordance with
paragraph (D)(1)(b)(1004.1.2)
of this rule
and added to the number of fixed seats.
The occupant load of wheelchair spaces
and the associated companion seat shall be based on one occupant for each
wheelchair space and one occupant for the associated companion seat provided in
accordance with section 1108.2.3 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
For areas having fixed seating without
dividing arms, the occupant load shall be not less than the number of seats
based on one person for each 18 inches (457 mm) of seating length.
The occupant load of seating booths
shall be based on one person for each 24 inches (610 mm) of booth seat length
measured at the backrest of the seating booth.
(5)
[BE] 1004.5
Outdoor areas.
Yards, patios, courts and
similar outdoor areas accessible to and usable by the building occupants shall
be provided with means of egress as required by this
rule. The
occupant load of such outdoor areas shall be assigned by the fire code official
pursuant to
paragraph (A)(1)( 1001.1)
of this
rule in accordance with the anticipated use. Where outdoor areas are
to be used by persons in addition to the occupants of the building, and the
path of egress travel from the outdoor areas passes through the building, means
of egress requirements for the building shall be based on the sum of the
occupant loads of the building plus the outdoor areas.
At locations or
in structures not regulated by the building code as listed in rule
1301:7-7-80
of the Administrative Code, the occupant load shall be approved by the fire
code official.
Exceptions:
1.
Outdoor areas used
exclusively for service of the building need only have one means of
egress.
2.
Both outdoor areas dedicated to individual
dwelling units in Group R-3 and Group R-2.
(6)
[BE] 1004.6
Multiple occupancies. Where a building contains two or more occupancies,
the means of egress requirements shall apply to each portion of the building
based on the occupancy of that space. Where two or more occupancies utilize
portions of the same means of egress system, those egress components shall meet
the more stringent requirements of all occupancies that are
served.
(E)
Section 1005 Means of egress sizing
(1)
[BE] 1005.1
General.
All portions of the means of
egress system shall be sized in accordance with this
paragraph.
Exception:
Aisles and aisle accessways in rooms or spaces used for
assembly purposes complying with paragraph (CC)(1029)
of this rule.
(2)
[BE] 1005.2
Minimum width based on component.
The
minimum width, in inches (mm), of any means of egress components shall be not
less than that specified for such component, elsewhere in this
code.
(3)
[BE] 1005.3 Required capacity based on occupant
load.
The required capacity, in inches
(mm), of the means of egress for any room, area, space or story shall be not
less than that determined in accordance with
paragraphs
(E)(3)(a)(1005.3.1) and (E)(3)(b)(1005.3.2)
of this
rule.(a)
[BE] 1005.3.1 Stairways.
The capacity, in inches (mm), of the means of egress
stairways shall be calculated by multiplying the occupant load served by such
stairways by a means of egress capacity factor of 0.3 inch ( 7.6 mm) per
occupant. Where stairways serve more than one story, only the occupant load of
each story considered individually shall be used in calculating the required
capacity of the stairways serving that story.
Exceptions:
1.
For other than
Group H and I-2 occupancies, the capacity, in inches (mm), of means of egress
stairways shall be calculated by multiplying the occupant load served by such
stairways by a means of egress capacity factor of 0.2 inches ( 5.1 mm) per
occupant in buildings equipped throughout with an automatic sprinkler system
installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1)
or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code and an emergency voice/alarm communication
system in accordance with paragraph (G)(5)(b)(ii)(907.5.2.2)
of rule
1301:7-7-09
of the Administrative Code.
2.
Facilities with
smoke-protected assembly seating shall be permitted to use the capacity factors
in Table 1029.6.2 of this rule indicated for stepped aisles
for exit access or exit stairways where the entire path for means of egress
from the seating to the exit discharge is provided with a smoke control system
complying with paragraph (I)(909) of rule
1301:7-7-09
of the Administrative Code.
3.
Facilities with
outdoor smoke-protected assembly seating shall be permitted to the capacity
factors in paragraph (CC)(6)(c)(1029.6.3) of this
rule indicated for stepped aisles for exit access or exit stairways
where the entire path for means of egress from the seating to the exit
discharge is open to the outdoors.
(b)
[BE]
1005.3.2 Other egress components.
The
capacity, in inches (mm), of means of egress components other than stairways
shall be calculated by multiplying the occupant load served by such component
by a means of egress capacity factor of 0.2 inch ( 5.1 mm) per occupant.
Exceptions:
1.
For other than
Group H and I-2 occupancies, the capacity, in inches (mm), of means of egress
components other than stairways shall be calculated by multiplying the occupant
load served by such component by a means of egress capacity factor of 0.15
inches ( 3.8 mm) per occupant in buildings equipped throughout with an
automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code and an emergency voice/alarm communication
system in accordance with paragraph (G)(5)(b)(ii)(907.5.2.2)
of rule
1301:7-7-09
of the Administrative Code.
2.
Facilities with
smoke-protected assembly seating shall be permitted to use the capacity factors
in Table 1029.6.2 of this rule indicated for level or ramped
aisles for means of egress components other than stairways where the entire
path for means of egress from the seating to the exit discharge is provided
with a smoke control system complying with paragraph (I)(909)
of rule
1301:7-7-09
of the Administrative Code.
3.
Facilities with
outdoor smoke-protected assembly seating shall be permitted to the capacity
factors in paragraph (CC)(6)(c)(1029.6.3) of this
rule indicated for level or ramped aisles for means of egress
components other than stairways where the entire path for means of egress from
the seating to the exit discharge is open to the
outdoors.
(4)
[BE] 1005.4
Continuity.
The minimum width or required
capacity of the means of egress required from any story of a building shall not
be reduced along the path of egress travel until arrival at the public
way.
(5)
[BE] 1005.5 Distribution of minimum width and required
capacity.
Where more than one exit, or
access to more than one exit, is required, the means of egress shall be
configured such that the loss of any one exit, or access to one exit, shall not
reduce the available capacity or width to less than 50 per
cent of the required capacity or width.
(6)
[BE] 1005.6
Egress convergence.
Where the means of
egress from stories above and below converge at an intermediate level, the
capacity of the means of egress from the point of convergence shall be not less
than the largest minimum width or the sum of the required capacities for the
stairways or ramps serving the two adjacent stories, whichever is
larger.
(7)
[BE] 1005.7 Encroachment.
Encroachments into the required means of egress width
shall be in accordance with the provisions of this
paragraph.
(a)
[BE] 1005.7.1 Doors. Doors, when fully
opened, shall not reduce the required width by more than 7 inches (178 mm).
Doors in any position shall not reduce the required width by more than
one-half.
Exceptions:
1.
Surface-mounted
latch release hardware shall be exempt from inclusion in the 7-inch maximum
(178 mm) encroachment where both of the following conditions exists:
1.1
The hardware is
mounted to the side of the door facing away from the adjacent wall where the
door is in the open position.
1.2
The hardware is
mounted not less than 34 inches (865 mm) nor more than 48 inches (1219 mm)
above the finished floor.
2.
The restrictions
on door swing shall not apply to doors within individual dwelling units and
sleeping units of Group R-2 occupancies and dwelling units of Group R-3
occupancies.
(b)
[BE] 1005.7.2 Other projections.
Handrail projections shall be in accordance with the
provisions of
paragraph (N)(8)( 1014.8)
of this
rule. Other nonstructural projections such as trim and similar
decorative features shall be permitted to project into the required width not
more than 11/2 inches (38 mm) on each side.
Exception:
Projections are permitted in corridors within Group I-2
Condition 1 in accordance with Section 407.4.3 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code.
(c)
[BE]
1005.7.3 Protruding objects.
Protruding
objects shall comply with the applicable requirements of
paragraph (C)(3)( 1003.3) of this
rule.
(F)
Section
1006 Numbers of exits and exit access doorways
(1)
[BE] 1006.1
General.
The number of exits or exit
access doorways required within the means of egress system shall comply with
the provisions of paragraph (F)(2)( 1006.2) of this
rule for spaces, including mezzanines, and paragraph
(F)(3)( 1006.3) of this rule for stories.
(2)
[BE] 1006.2
Egress from spaces.
Rooms, areas or
spaces, including mezzanines, within a story or basement shall be provided with
the number of exits or access to exits in accordance with this
paragraph.
(a)
[BE] 1006.2.1 Egress based on occupant load and
common path of egress travel distance. Two exits or exit access doorways
from any space shall be provided where the design occupant load or the common
path of egress travel distance exceeds the values listed in Table
1006.2.1 of this rule.
Exceptions:
1.
In Group R-2 and
R-3 occupancies, one means of egress is permitted within and from individual
dwelling units with a maximum occupant load of 20 where the dwelling unit is
equipped throughout with an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code and the common path of egress travel does
not exceed 125 feet (38 100 mm).
2.
Care suites in
Group I-2 occupancies complying with section 407.4 of the
building code
as listed in rule
1301:7-7-80
of the Administrative Code.
[BE] Table
1006.2.1
Spaces with one exit or exit
access doorway
Occupancy
|
Maximum occupant load of
space
|
Maximum common path of
egress travel distance (feet)
|
Without sprinkler system
(feet)
|
With sprinkler system
(feet)
|
Occupant
load
|
OL <=
30
|
OL >
30
|
Ac,
E, M
|
49
|
75
|
75
|
75a
|
B
|
49
|
100
|
75
|
100a
|
F
|
49
|
75
|
75
|
100a
|
H-1, H-2, H-3
|
3
|
NP
|
NP
|
25b
|
H-4, H-5
|
10
|
NP
|
NP
|
75b
|
I-1,
I-2d, I-4
|
10
|
NP
|
NP
|
75a
|
I-3
|
10
|
NP
|
NP
|
100a
|
R-1
|
10
|
NP
|
NP
|
75a
|
R-2
|
10
|
NP
|
NP
|
125a
|
R-3e,g
|
10
|
NP
|
NP
|
125a
|
R-4e,g
|
10
|
75
|
75
|
125a
|
Sf
|
29
|
100
|
75
|
100a
|
U
|
49
|
100
|
75
|
75a
|
For SI: 1 foot = 304.8 mm.
NP=Not Permitted.
a. Buildings equipped throughout with
an automatic sprinkler system in accordance with paragraph
(C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code. See paragraph (C)(903)
of rule
1301:7-7-09
of the Administrative Code for occupancies where automatic sprinkler
systems are permitted in accordance with paragraph
(C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code.
b. Group H occupancies equipped
throughout with an automatic sprinkler system in accordance with
paragraph (C)(2)(e)(903.2.5) of rule
1301:7-7-09
of the Administrative Code.
c. For a room or space used for
assembly purposes having fixed seating, see paragraph (CC)(8)(
1029.8) of this rule.
d. For the travel distance limitations
in Group I-2, see section 407.4 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
e. The length of common path of egress
travel distance in a Group R-3 occupancy located in a mixed occupancy building
or within a Group R-3 or R-4 congregate living facility.
f. The length of common path of egress
travel distance in a Group S-2 open parking garage shall be not more than 100
feet.
g. For the travel distance
limitations in Group R-3 and R-4 equipped throughout with an automatic
sprinkler system in accordance with paragraph (C)(3)(a)(iii)(903.3.1.3) of rule
1301:7-7-09
of the Administrative Code, see paragraph (F)(2)(b)(vi)(1006.2.2.6) of this
rule.
(i)
[BE] 1006.2.1.1 Three or more exits or exit
access doorways. Three exits or exit access doorways shall be provided
from any space with an occupant load of 501 to 1,000. Four exits or exit access
doorways shall be provided from any space with an occupant load greater than
1,000.
(b)
[BE]
1006.2.2 Egress based on use. The numbers of exits or access to exits
shall be provided in the uses described in
paragraphs
(F)(2)(b)(i)(1006.2.2.1)
to (F)(2)(b)(v)(1006.2.2.5)
of this rule.(i)
[BE] 1006.2.2.1 Boiler, incinerator and furnace
rooms. Two exit access doorways are required in boiler, incinerator and
furnace rooms where the area is over 500 square feet (46
m2) and any fuel-fired equipment exceeds 400,000
British thermal units (Btu) (422 000 KJ) input capacity. Where two exit access
doorways are required, one is permitted to be a fixed ladder or an alternating
tread device. Exit access doorways shall be separated by a horizontal distance
equal to one-half the length of the maximum overall diagonal dimension of the
room.
(ii)
[BE] 1006.2.2.2 Refrigeration machinery
rooms. Machinery rooms larger than 1,000 square feet (93
m2) shall have not less than two exits or exit
access doorways. Where two exit access doorways are required, one such doorway
is permitted to be served by a fixed ladder or an alternating tread device.
Exit access doorways shall be separated by a horizontal distance equal to
one-half the maximum horizontal dimension of the room.
All portions of machinery rooms shall
be within 150 feet (45 720 mm) of an exit or exit access doorway. An increase
in exit access travel distance is permitted in accordance with
paragraph (Q)(1)( 1017.1) of this
rule.
Doors shall swing in the direction of
egress travel, regardless of the occupant load served. Doors shall be tight
fitting and self-closing.
(iii)
[BE]
1006.2.2.3 Refrigerated rooms or spaces. Rooms or spaces having a floor
area larger than 1,000 square feet (93 m2),
containing a refrigerant evaporator and maintained at a temperature below 68°F
(20°C), shall have access to not less than two exits or exit access
doorways.
Exit access travel distance shall be
determined as specified in paragraph (Q)(1)( 1017.1)
of this rule, but all portions of a refrigerated room or space
shall be within 150 feet (45 720 mm) of an exit or exit access doorway where
such rooms are not protected by an approved automatic sprinkler system. Egress
is allowed through adjoining refrigerated rooms or spaces.
Exception:
Where using refrigerants in quantities limited to the
amounts based on the volume set forth in the mechanical code as listed
in rule
1301:7-7-80
of the Administrative Code.
(iv)
[BE]
1006.2.2.4 Day care means of egress. Day care facilities, rooms or
spaces where care is provided for more than 10 children that are 2 1/2 years of
age or less, shall have access to not less than two exits or exit access
doorways.
(v)
[BE] 1006.2.2.5 Vehicular ramps. Vehicular
ramps shall not be considered as an exit access ramp unless pedestrian
facilities are provided.
(3)
[BE] 1006.3
Egress from stories or occupied roofs. The means of egress system
serving any story or occupied roof shall be provided with the number of exits
or access to exits based on the aggregate occupant load served in accordance
with this
paragraph. The path of egress travel to an exit
shall not pass through more than one adjacent story.
(a)
[BE]
1006.3.1 Egress based on occupant load. Each story and occupied roof
shall have the minimum number of independent exits, or access to exits, as
specified in Table 1006.3.1
of this rule. A single exit or
access to a single exit shall be permitted in accordance with
paragraph (F)(3)(b)(1006.3.2)
of this rule.
The required number of exits, or exit access stairways or ramps providing
access to exits, from any story or occupied roof shall be maintained until
arrival at the exit discharge or a public way.
[BE] Table
1006.3.1
Minimum number of exits or access
to exits per story
Occupant load per
story
|
Minimum number of exits
or access to exits from story
|
1-500
|
2
|
501-1,000
|
3
|
More than 1,000
|
4
|
(b)
[BE] 1006.3.2 Single exits. A single exit
or access to a single exit shall be permitted from any story or occupied roof,
where one of the following conditions exists:
1.
The occupant load,
number of dwelling units and exit access travel distance do not exceed the
values in Table 1006.3.2(1) or 1006.3.2(2) of this
rule.
2.
Rooms, areas and spaces complying with
paragraph (F)(2)(a)(1006.2.1) of this rule
with exits that discharge directly to the exterior at the level of exit
discharge, are permitted to have one exit or access to a single
exit.
3.
Parking garages where vehicles are mechanically parked
shall be permitted to have one exit or access to a single exit.
4.
Group R-3 and R-4
occupancies shall be permitted to have one exit or access to a single
exit.
5.
Individual single-story or multistory dwelling units
shall be permitted to have a single exit or access to a single exit from the
dwelling unit provided that both of the following criteria are met:
5.1.
The dwelling
unit complies with paragraph (F)(2)(a)(1006.2.1) of
this rule as a space with one means of egress.
5.2.
Either the exit
from the dwelling unit discharges directly to the exterior at the level of exit
discharge, or the exit access outside the dwelling unit's entrance door
provides access to not less than two approved independent exits.
[BE] Table
1006.3.2(1)
Stories with one exit or access
to one exit for R-2 occupancies
Story
|
Occupancy
|
Maximum number of
dwelling units
|
Maximum common path of
egress travel distance
|
Basement, first, second or
third story above grade plane
|
R-2a,b
|
4 dwelling units
|
125 feet
|
Fourth story above grade plane
and higher
|
NP
|
NA
|
NA
|
For SI: 1 foot = 3048 mm.
NP-Not Permitted.
NA-Not Applicable
a. Buildings classified as Group R-2
equipped throughout with an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code and provided with emergency escape and
rescue openings in accordance with paragraph (DD)(1030)
of this rule.
b. This Table is used for R-2
occupancies consisting of dwelling units. For R-2 occupancies consisting of
sleeping units, use Table 1006.3.2(2) of this
rule.
[BE] Table
1006.3.2(2)
Stories with one exit or access
to one exit for other occupancies
Story
|
Occupancy
|
Maximum occupant load per
story
|
Maximum common path of
egress travel distance (feet)
|
First story above or below
grade plane
|
A,
Bb, E, Fb, M,
U
|
49
|
75
|
H-2, H-3
|
3
|
25
|
H-4, H-5, I, R-1,
R-2a,c, R-4
|
10
|
75
|
Sb,d
|
29
|
75
|
Second story above grade
plane
|
B, F, M,
Sd
|
29
|
75
|
Third story above grade plane
and higher
|
NP
|
NA
|
NA
|
For SI: 1 foot= 304.8 mm.
NP=Not Permitted.
NA=Not Applicable.
a. Buildings classified as Group R-2
equipped throughout with an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code and provided with emergency escape and
rescue openings in accordance with paragraph (DD)(1030)
of this rule.
b. Group B, F and S occupancies in
buildings equipped throughout with an automatic sprinkler system in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code shall have a maximum exit access travel
distance of 100 feet.
c. This table is used for R-2
occupancies consisting of sleeping units. For R-2 occupancies consisting of
dwelling units, use Table 1006.3.2(1) of this rule.
d. The length of exit access travel
distance in a Group S-2 open parking garage shall be not more than 100
feet.
(i)
[BE] 1006.3.2.1 Mixed occupancies. Where one
exit, or exit access stairway or ramp providing access to exits at other
stories, is permitted to serve individual stories, mixed occupancies shall be
permitted to be served by single exits provided each individual occupancy
complies with the applicable requirements of Table 1006.3.2(1) or 1006.3.2(2)
of this rule for that occupancy.
Where applicable, cumulative occupant
loads from adjacent occupancies shall be considered in accordance with the
provisions of paragraph (D)(1)( 1004.1) of this
rule. In each story of a mixed occupancy building, the maximum number
of occupants served by a single exit shall be such that the sum of the ratios
of the calculated number of occupants of the space divided by the allowable
number of occupants indicated in Table 1006.3.2(2) of this
rule for each occupancy does not exceed one. Where dwelling units are
located on a story with other occupancies, the actual number of dwelling units
divided by four plus the ratio from the other occupancy does not exceed
one.
(G)
Section
1007 Exit and exit access doorway configuration
(1)
[BE] 1007.1
General. Exits, exit access doorways, and exit access stairways and
ramps serving spaces, including individual building stories, shall be separated
in accordance with the provisions of this
paragraph.
(a)
[BE]
1007.1.1 Two exit or exit access doorways.
Where two exits, exit access doorways exit access stairways
or ramps, or any combination thereof, are required from any portion of the exit
access, they shall be placed a distance apart equal to not less than one-half
of the length of the maximum overall diagonal dimension of the building or area
to be served measured in a straight line between them. Interlocking or scissor
stairways shall be counted as one exit stairway.
Exceptions:
1.
Where interior
exit stairways or ramps are interconnected by a 1-hour fire-resistance-rated
corridor conforming to the requirements of paragraph (T)(1020)
of this rule, the required exit separation shall be measured
along the shortest direct line of travel within the corridor.
2.
Where a building
is equipped throughout with an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code, the separation distance shall be not less
than one-third of the length of the maximum overall diagonal dimension of the
area served.
(i)
[BE] 1007.1.1.1 Measurement point. The
separation distance required in
paragraph (G)(1)(a)(1007.1.1)
of this rule shall be measured in accordance with the
following:
(a)
The separation distance to exit or exit access doorways
shall be measured to any point along the width of the doorway.
(b)
The separation
distance to exit access stairways shall be measured to the closest
riser.
(c)
The separation distance to exit access ramps shall be
measured to the start of the ramp
run.
(b)
[BE]
1007.1.2 Three or more exits or exit access doorways.
Where access to three or more exits is required, not
less than two exit or exit access doorways shall be arranged in accordance with
the provisions of paragraph (G)(a)(i)(1007.1.1) of
this rule. Additional required exit or exit access doorways shall be
arranged a reasonable distance apart so that if one becomes blocked, the others
will be available.
(c)
[BE] 1007.1.3 Remoteness of exit access stairways
or ramps.
Where two exit access stairways
or ramps provide the required means of egress to exits at another story, the
required separation distance shall be maintained for all portions of such exit
access stairways or ramps.
(i)
[BE] 1007.1.3.1 Three or more exit access
stairways or ramps. Where more than two exit access stairways or ramps
provide the required means of egress, not less than two shall be arranged in
accordance with paragraph (B)(1)(c)(1007.1.3) of this
rule.
(H)
[BE]
Section 1008 Means of egress illumination
(1)
[BE] 1008.1
Means of egress illumination. Illumination shall be provided in the
means of egress in accordance with paragraph (BB)(2)( 1008.2)
of this rule. Under emergency power, means of egress
illumination shall comply with paragraph (H)(3)( 1008.3) of this
rule.
(2)
[BE] 1008.2 Illumination required.
The means of egress serving a room or space shall be
illuminated at all times that the room or space is occupied.
Exceptions:
1.
Occupancies in
Group U.
2.
Aisle accessways in Group A.
3.
Dwelling units and
sleeping units in Groups R-1, R-2 and R-3.
4.
Sleeping units of
Group I occupancies.
(a)
[BE] 1008.2.1 Illumination level under normal
power.
The means of egress illumination
level shall not be less than 1 footcandle (11 lux) at the walking
surface.
Exception:
For auditoriums, theaters, concert or opera halls and
similar assembly occupancies, the illumination at the walking surface is
permitted to be reduced during performances by one of the following methods
provided that the required illumination is automatically restored upon
activation of a premises' fire alarm system:
1.
Externally
illuminated walking surfaces shall be permitted to be illuminated to not less
than 0.2 footcandle ( 2.15 lux).
2.
Steps, landings
and the sides of ramps shall be permitted to be marked with self-luminous
materials in accordance with paragraphs (Y)(2)(a)(1025.2.1),
(Y)(2)(b)(1025.2.2) and (Y)(2)(d)(1025.2.4) of this rule by
systems listed in accordance with UL 1994 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
[BE]
1008.2.2 Exit discharge.
In Group I-2
occupancies where two or more exits are required, on the exterior landings
required by paragraph (J)(6)(a)(1010.6.1) of this
rule, means of egress illumination levels for the exit discharge shall
be provided such that failure of any single lighting unit shall not reduce the
illumination level at the landing to less than 1 footcandle (11
lux).
(3)
[BE] 1008.3 Emergency power for
illumination.
The power supply for means
of egress illumination shall normally be provided by the premises' electrical
supply.
(a)
[BE] 1008.3.1 General.
In the event of power supply failure in rooms and spaces
that require two or more means of egress an emergency electrical system shall
automatically illuminate all of the following areas:
(i)
Aisles.
(ii)
Corridors.
(iii)
Exit access
stairways and ramps.
(b)
[BE]
1008.3.2 Buildings.
In the event of power
supply failure, in buildings that require two or more means of egress, an
emergency electrical system shall automatically illuminate all of the following
areas:
(i)
Interior exit access stairways and ramps.
(ii)
Interior and
exterior exit stairways and ramps.
(iii)
Exit
passageways.
(iv)
Vestibules and areas on the level of discharge used for
exit discharge in accordance with paragraph (BB)(1)( 1028.1)
of this rule.
(v)
Exterior landings
as required by paragraph (J)(1)(f)(1010.1.6) of this
rule for exit doorways that lead directly to the exit
discharge.
(c)
[BE] 1008.3.3 Rooms and spaces.
In the event of power supply failure, an emergency
electrical system shall automatically illuminate all of the following
areas:
(i)
Electrical equipment rooms.
(ii)
Fire command
centers.
(iii)
Fire pump rooms.
(iv)
Generator
rooms.
(v)
Public restrooms with an area greater than 300 square
feet ( 27.87 m2).
(d)
[BE]
1008.3.4 Duration.
The emergency power
system shall provide power for a duration of not less than 90 minutes and shall
consist of storage batteries, unit equipment or an on-site generator. The
installation of the emergency power system shall be in accordance with
paragraph (D)(604) of rule
1301:7-7-06
of the Administrative Code.
(e)
[BE]
1008.3.5 Illumination level under emergency power.
Emergency lighting facilities shall be arranged to
provide initial illumination that is not less than an average of 1 footcandle
(11 lux) and a minimum at any point of 0.1 footcandle (1 lux) measured along
the path of egress at floor level. Illumination levels shall be permitted to
decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06
footcandle ( 0.6 lux) at the end of the emergency lighting time duration. A
maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be
exceeded. In Group I-2 occupancies, failure of any single lighting unit shall
not reduce the illumination level to less than 0.2 footcandle ( 2.2
lux).
(I)
[BE]
Section 1009 Accessible means of egress
(1)
[BE] 1009.1
Accessible means of egress required.
Accessible means of egress shall comply with this
paragraph. Accessible spaces shall be provided with not less
than one accessible means of egress. Where more than one means of egress is
required by
paragraphs (F)(2)( 1006.2) or (F)(2)( 1006.3)
of this rule from any accessible space, each accessible
portion of the space shall be served by not less than two accessible means of
egress.
Exceptions:
1.
Accessible means
of egress are not required to be provided in existing
buildings.
2.
One accessible means of egress is required from an
accessible mezzanine level in accordance with paragraph
(I)(3)( 1009.3), (I)(4)( 1009.4) or (I)(5)( 1009.5) of this
rule.
3.
In assembly areas with ramped aisles or stepped aisles,
one accessible means of egress is permitted where the common path of travel is
accessible and meets the requirements in paragraph (CC)(8)(
1029.8) of this rule.
(2)
[BE] 1009.2
Continuity and components.
Each required
accessible means of egress shall be continuous to a public way and shall
consist of one or more of the following components:
1.
Accessible routes
complying with section 1104 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
2.
Interior exit
stairways complying with paragraphs (I)(3)( 1009.3) and
(W)(1023) of this rule.
3.
Exit access
stairways complying with paragraphs (G)(3)( 1009.3) and
(S)(3)( 1019.3) or (S)(3)( 1019.4) of this
rule.
4.
Exterior exit stairways complying with
paragraphs (I)(3)( 1009.3) and (AA)(1027) of this
rule and serving levels other than the level of exit
discharge.
5.
Elevators complying with paragraph
(I)(4)( 1009.4) of this rule.
6.
Platform lifts
complying with paragraph (I)(5)( 1009.5) of this
rule.
7.
Horizontal exits complying with
paragraph (Z)(1026) of this
rule.
8.
Ramps complying with paragraph
(L)(1012) of this rule.
9.
Areas of refuge
complying with paragraph (I)(6)( 1009.6) of this
rule.
10.
Exterior areas for assisted rescue complying with
paragraph (I)(7)( 1009.7)
of this rule
serving exits at the level of exit discharge.
(a)
[BE]
1009.2.1 Elevators required. In buildings where a required accessible
floor is four or more stories above or below a level of exit discharge, not
less than one required accessible means of egress shall be an elevator
complying with
paragraph (I)(4)( 1009.4)
of this
rule.
Exceptions:
1.
In buildings
equipped throughout with an automatic sprinkler system installed in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) or
(C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code, the elevator shall not be required on
floors provided with a horizontal exit and located at or above the levels of
exit discharge.
2.
In buildings equipped throughout with an automatic
sprinkler system installed in accordance with paragraph
(C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code, the elevator shall not be required on
floors provided with a ramp conforming to the provisions of
paragraph (L)(1012) of this rule.
(3)
[BE] 1009.3 Stairways. In order to be
considered part of an accessible means of egress, a stairway between stories
shall have a clear width of 48 inches (1219 mm) minimum between handrails and
shall either incorporate an area of refuge within an enlarged floor-level
landing or shall be accessed from either an area of refuge complying with
paragraph (I)(6)( 1009.6)
of this rule. Exit
access stairways that connect levels in the same story are not permitted as
part of an accessible means of egress.
Exceptions:
1.
Exit access
stairways providing means of egress from mezzanines are permitted as part of an
accessible means of egress.
2.
The clear width of
48 inches (1219 mm) between handrails is not required in buildings equipped
throughout with an automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code.
3.
The clear width of
48 inches (1219 mm) between handrails is not required for stairways accessed
from a refuge area in conjunction with a horizontal exit.
4.
Areas of refuge
are not required at exit access stairways where a two-way communication is
provided at the elevator landing in accordance with paragraph
(I)(8)( 1009.8) of this rule.
5.
Areas of refuge
are not required at stairways in buildings equipped throughout with an
automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code.
6.
Areas of refuge
are not required at stairways serving open parking garages.
7.
Areas of refuge
are not required for smoke protected assembly seating areas complying with
paragraph (CC)(6)(b)(1029.6.2)
8.
Areas of refuge
are not required at stairways in Group R-2 occupancies.
9.
Areas of refuge
are not required for stairways accessed from a refuge area in conjunction with
a horizontal exit.
(4)
[BE] 1009.4
Elevators.
In order to be considered part
of an accessible means of egress, an elevator shall comply with the emergency
operation and signaling device requirements of section 2.27 of ASME A 17.1 /CSA
B44
as listed in rule
1301:7-7-80
of the Administrative Code. Standby power shall be provided in
accordance with
paragraph (D)(604)
of rule
1301:7-7-06
of the Administrative Code and section 3003 of the
building
code as listed in rule
1301:7-7-80
of the Administrative Code. The elevator shall be accessed from an
area of refuge complying with
paragraph
(I)(6)(
1009.6)
of this rule.
Exceptions:
1.
Areas of refuge
are not required at the elevator in open parking garages.
2.
Areas of refuge
are not required in buildings and facilities equipped throughout with an
automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code.
3.
Areas of refuge
are not required at elevators not required to be located in a shaft in
accordance with section 712 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
4.
Areas of refuge
are not required at elevators serving smoke protected seating areas complying
with paragraph (CC)(6)(b)(1029.6.2) of this
rule.
5.
Areas of refuge are not required for elevators accessed
for a refuge area in conjunction with a horizontal exit
(5)
[BE] 1009.5 Platform lifts.
Platform lifts shall be permitted to serve as part of
an accessible means of egress where allowed as part of a required accessible
route in section 1109.8 of the building code as listed in rule
1301:7-7-80
of the Administrative Code except for Item 10. Standby power for the
platform lift shall be provided in accordance with paragraph
(D)(604) of rule
1301:7-7-06
of the Administrative Code.
(6)
[BE] 1009.6
Areas of refuge.
Every required area of
refuge shall be accessible from the space it serves by an accessible means of
egress.
(a)
[BE] 1009.6.1 Travel distance.
The maximum travel distance from any accessible space
to an area of refuge shall not exceed the exit access travel distance permitted
for the occupancy in accordance with paragraph (Q)(1)( 1017.1
) of this rule.
(b)
[BE]
1009.6.2 Stairway or elevator access.
Every required area of refuge shall have direct access to a
stairway complying with paragraphs (I)(3)( 1009.3) and
(W)(1023) of this rule or an elevator complying with
paragraph (I)(4)( 1009.4) of this
rule.
(c)
[BE] 1009.6.3 Size.
Each area of refuge shall be sized to accommodate one
wheelchair space of 30 inches by 48 inches (762 mm by 1219 mm) for each 200
occupants or portion thereof, based on the occupant load of the area of refuge
and areas served by the area of refuge. Such wheelchair spaces shall not reduce
the means of egress minimum width or required capacity. Access to any of the
required wheelchair spaces in an area of refuge shall not be obstructed by more
than one adjoining wheelchair space.
(d)
[BE]
1009.6.4 Separation.
Each area of refuge
shall be separated from the remainder of the story by a smoke barrier complying
with section 709 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code or a horizontal exit complying with
paragraph (Z)(1026)
of this rule. Each area
of refuge shall be designed to minimize the intrusion of smoke.
Exceptions:
1.
Areas of refuge
located within an enclosure for interior exit stairways complying with
paragraph (W)(1023) of this
rule.
2.
Areas of refuge in outdoor facilities where exit access
is essentially open to the outside.
(e)
[BE]
1009.6.5 Two-way communication.
Areas of
refuge shall be provided with a two-way communication system complying with
paragraphs (I)(8)(a)(1009.8.1) and (I)(8)(b)(1009.8.2)
of this rule.(i)
1009.6.5.1 Testing and
maintenance.
All two-way communication systems shall be
tested in the presence of the fire code official upon completion of
installation. Communication systems shall be inspected and tested in accordance
with NFPA 72 as listed in rule
1301:7-7-80
of the Administrative Code to verify that all components are
operational.
(7)
[BE] 1009.7
Exterior areas for assisted rescue.
Exterior areas for assisted rescue shall be accessed by an
accessible route from the area served.
Where the exit discharge does not
include an accessible route from an exit located on the level of exit discharge
to a public way, an exterior area of assisted rescue shall be provided on the
exterior landing in accordance with paragraphs
(I)(7)(a)(1009.7.1) to (I)(7)(d)(1009.7.4) of
this rule.
(a)
[BE] 1009.7.1 Size.
Each exterior area for assisted rescue shall be sized
to accommodate wheelchair spaces in accordance with paragraph
(I)(6)(a)(1009.6.3) of this rule.
(b)
[BE]
1009.7.2 Separation.
Exterior walls
separating the exterior area of assisted rescue from the interior of the
building shall have a minimum fire-resistance rating of 1 hour, rated for
exposure to fire from the inside. The fire-resistance-rated exterior wall
construction shall extend horizontally 10 feet (3048 mm) beyond the landing on
either side of the landing or equivalent fire-resistance-rated construction is
permitted to extend out perpendicular to the exterior wall 4 feet (1219 mm)
minimum on the side of the landing. The fire-resistance-rated construction
shall extend vertically from the ground to a point 10 feet (3048 mm) above the
floor level of the area for assisted rescue or to the roof line, whichever is
lower. Openings within such fire-resistance-rated exterior walls shall be
protected in accordance with section 716 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code.
(c)
[BE]
1009.7.3 Openness.
The exterior area for
assisted rescue shall be open to the outside air. The sides other than the
separation walls shall be not less than 50 per cent open, and
the open area shall be so distributed as to minimize the accumulation of smoke
or toxic gases.
(d)
[BE] 1009.7.4 Stairways.
Stairways that are part of the means of egress for the
exterior area for assisted rescue shall provide a clear width of 48 inches
(1220 mm) between handrails.
Exception:
The clear width of 48 inches (1220 mm) between
handrails is not required at stairways serving buildings equipped throughout
with an automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code.
(8)
[BE] 1009.8
Two-way communication.
A two-way
communication system complying with
paragraphs
(I)(8)(a)(1009.8.1) and (I)(8)(b)(1009.8.2)
of this rule shall
be provided at the landing serving each elevator or bank of elevators on each
accessible floor that is one or more stories above or below the level of exit
discharge.
Exceptions:
1.
Two-way
communication systems are not required at the landing serving each elevator or
bank of elevators where the two-way communication system is provided within
areas of refuge in accordance with paragraph
(I)(6)(e)(1009.6.5) of this rule.
2.
Two-way
communication systems are not required on floors provided with ramps conforming
to the provisions of paragraph (L)(1012) of this
rule.
3.
Two-way communication systems are not required at the
landings serving only service elevators that are not designated as part of the
accessible means of egress or serve as part of the required accessible route
into a facility.
4.
Two-way communication systems are not required at the
landings serving only freight elevators.
5.
Two-way
communication systems are not required at the landing serving a private
residence elevator.
(a)
[BE] 1009.8.1 System requirements.
Two-way communication systems shall provide
communication between each required location and the fire command center or a
central control point location approved by the fire department. Where the
central control point is not constantly attended, a two-way communication
system shall have a timed automatic telephone dial-out capability to a
monitoring location or 9-1-1. The two-way communication system shall include
both audible and visible signals.
(b)
[BE]
1009.8.2 Directions.
Directions for the
use of the two-way communication system, instructions for summoning assistance
via the two-way communication system and written identification of the location
shall be posted adjacent to the two-way communication system. Signage shall
comply with the ICC A 117.1as listed in rule
1301:7-7-80
of the Administrative Code requirements for visual
characters.
(9)
[BE] 1009.9
Signage.
Signage indicating special
accessibility provisions shall be provided as shown:
(a)
Each door
providing access to an area of refuge from an adjacent floor area shall be
identified by a sign stating: "AREA OF REFUGE."
(b)
Each door
providing access to an exterior area for assisted rescue shall be identified by
a sign stating: "EXTERIOR AREA FOR ASSISTED RESCUE."
Signage shall comply with the ICC A
117.1as listed in rule
1301:7-7-80
of the Administrative Code requirements for visual characters and
include the "International Symbol of Accessibility." Where exit sign
illumination is required by paragraph (M)(3)( 1013.3)
of this rule, the signs shall be illuminated. Additionally,
visual characters, raised character and Braille signage complying with ICC A
117.1 as listed in rule
1301:7-7-80
of the Administrative Code shall be located at each door to an area of
refuge and exterior area for assisted rescue in accordance with
paragraph (M)(4)( 1013.4) of this
rule.
(10)
[BE]
1009.10 Directional signage.
Directional
signage indicating the location of all other means of egress and which of those
are accessible means of egress shall be provided at the following:
(a)
At exits serving
a required accessible space but not providing an approved accessible means of
egress.
(b)
At elevator landings.
(c)
Within areas of
refuge.
(11)
[BE] 1009.11 Instructions.
In areas of refuge and exterior areas for assisted
rescue, instructions on the use of the area under emergency conditions shall be
posted. Signage shall comply with the ICC A 117.1
as listed in rule
1301:7-7-80
of the Administrative Code requirements for visual characters. The
instructions shall include all of the following:
(a)
Persons able to
use the exit stairway do so as soon as possible, unless they are assisting
others.
(b)
Information on planned availability of assistance in
the use of stairs or supervised operation of elevators and how to summon such
assistance.
(c)
Directions for use of the two-way communications system
where provided.
(J)
[BE]
Section 1010 Doors, gates and turnstiles
(1)
[BE] 1010.1
Doors. Means of egress doors shall meet the requirements of this
paragraph. Doors serving a means of egress system shall meet
the requirements of this
paragraph and
paragraph (V)(2)( 1022.2)
of this rule.
Doors provided for egress purposes in numbers greater than required by this
code shall meet the requirements of
this paragraph.
Means of egress doors shall be readily
distinguishable from the adjacent construction and finishes such that the doors
are easily recognizable as doors. Mirrors or similar reflecting materials shall
not be used on means of egress doors. Means of egress doors shall not be
concealed by curtains, drapes, decorations or similar materials.
(a)
[BE]
1010.1.1 Size of doors. The required capacity of each door opening shall
be sufficient for the occupant load thereof and shall provide a minimum clear
width of 32 inches (813 mm). Clear openings of doorways with swinging doors
shall be measured between the face of the door and the stop, with the door open
90 degrees (1.57 rad). Where this
paragraph requires a minimum clear width of 32 inches (813 mm)
and a door opening includes two door leaves without a mullion, one leaf shall
provide a clear opening width of 32 inches (813 mm). The maximum width of a
swinging door leaf shall be 48 inches (1219 mm) nominal. Means of egress doors
in a Group I-2 occupancy used for the movement of beds shall provide a clear
width not less than 411/2 inches (1054 mm). The height of door openings shall not
be less than 80 inches (2032 mm).
Exceptions:
1.
The minimum and
maximum width shall not apply to door openings that are not part of the
required means of egress in Group R-2 and R-3 occupancies.
2.
Door openings to
resident sleeping units in Group I-3 occupancies shall have a clear width of
not less than 28 inches (711 mm).
3.
Door openings to
reach in storage closets less than 10 square feet ( 0.93
m2) in area shall not be limited by the minimum
width.
4.
Width of door leafs in revolving doors that comply with
paragraph (J)(1)(d)(i)(1010.1.4.1) of this
rule shall not be limited.
5.
Door openings
within a dwelling unit or sleeping unit shall be not less than 78 inches (1981
mm) in height.
6.
Exterior door openings in dwelling units and sleeping
units, other than the required exit door, shall be not less than 76 inches
(1930 mm) in height.
7.
In other than Group R-1 occupancies, the minimum widths
shall not apply to interior egress doors within a dwelling unit or sleeping
unit that is not required to be an Accessible unit, Type A unit or Type B
unit.
8.
Door openings required to be accessible within Type B
units shall have a minimum clear width of 31.75 inches (806
mm).
9.
Doors to walk-in freezers and coolers less than 1,000
square feet (93 m2) in area shall have a maximum
width of 60 inches (1524 mm).
10.
In Group R-1
dwelling units or sleeping units not required to be Accessible units, the
minimum width shall not apply to doors for showers or saunas.
(i)
[BE]
1010.1.1.1 Projections into clear width. There shall not be projections
into the required clear width lower than 34 inches (864 mm) above the floor or
ground. Projections into the clear opening width between 34 inches (864 mm) and
80 inches (2032 mm) above the floor or ground shall not exceed 4 inches (102
mm).
Exception:
Door closers and door stops shall be permitted to be 78
inches (1980 mm) minimum above the floor.
(b)
[BE] 1010.1.2 Door swing. Egress doors shall be of the pivoted or
side-hinged swinging type.
Exceptions:
1.
Private garages,
office areas, factory and storage areas with an occupant load of 10 or
less.
2.
Group I-3 occupancies used as a place of
detention.
3.
Critical or intensive care patient rooms within suites
of health care facilities.
4.
Doors within or serving a single dwelling unit in
Groups R-2 and R-3.
5.
In other than Group H occupancies, revolving doors
complying with paragraph (J)(1)(d)(i)(1010.1.4.1) of
this rule.
6.
In other than Group H occupancies, special purpose
horizontal sliding, accordion or folding door assemblies complying with
paragraph (J)(1)(d)(iii)(1010.1.4.3) of this
rule.
7.
Power-operated doors in accordance with
paragraph (J)(1)(d)(ii)(1010.1.4.2) of this
rule.
8.
Doors serving a bathroom within an individual sleeping
unit in Group R-1.
9.
In other than Group H occupancies, manually operated
horizontal sliding doors are permitted in a means of egress from spaces with an
occupant load of 10 or less.
(i)
[BE] 1010.1.2.1 Direction of swing. Pivot
or side-hinged swinging doors shall swing in the direction of egress travel
where serving a room or area containing an occupant load of 50 or more persons
or a Group H occupancy.
(c)
[BE]
1010.1.3 Door opening force.
Doors
required to be accessible shall comply with accessibility requirements as set
forth in chapter 11 of the building code as listed in rule
1301:7-7-80
of the Administrative Code. Doors not required to be accessible or for which
accessibility requirements as set forth in chapter 11 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code has no requirements, shall comply with the
following:
The force for pushing or
pulling open interior swinging egress doors, other than fire doors, shall not
exceed 5 pounds (22 N). These forces do not apply to the force required to
retract latch bolts or disengage other devices that hold the door in a closed
position. For other swinging doors, as well as sliding and folding doors, the
door latch shall release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N) force. The door
shall swing to a full-open position when subjected to a 15-pound (67 N)
force.
(i)
[BE] 1010.1.3.1 Location of applied forces.
Forces shall be applied to the latch side of the door.
(d)
[BE] 1010.1.4 Special doors.
Special doors and security grilles shall comply with
the requirements of
paragraphs (J)(1)(d)(i)(1010.1.4.1)
to (J)(1)(d)(iv)(1010.1.4.4)
of this
rule.
(i)
1010.1.4.1 Revolving doors. Revolving
doors shall comply with the following:
1.
Revolving doors
shall comply with BHMA A 156.27as listed in rule
1301:7-7-80
of the Administrative Code and shall be installed in accordance with
the manufacturer's instructions.
2.
Each revolving
door shall be capable of breakout in accordance with BHMA A 156.27as
listed in rule
1301:7-7-80
of the Administrative Code and shall provide an aggregate width of not
less than 36 inches (914 mm).
3.
A revolving door
shall not be located within 10 feet (3048 mm) of the foot or top of stairways
or escalators. A dispersal area shall be provided between the stairways or
escalators and the revolving doors.
4.
The revolutions
per minute (rpm) for a revolving door shall not exceed the maximum rpm as
specified in BHMA A 156.27as listed in rule
1301:7-7-80
of the Administrative Code. Manual revolving doors shall comply with
Table 1010.1.4.1(1) of this rule. Automatic or power-operated
revolving doors shall comply with Table 1010.1.4.1(2) of this
rule.
5.
An emergency stop switch shall be provided near each
entry point of power or automatic operated revolving doors within 48 inches
(1220 mm) of the door and between 24 inches (610 mm) and 48 inches (1220 mm)
above the floor. The activation area of the emergency stop switch button shall
be not less than 1 inch (25 mm) in diameter and shall be red.
6.
Each revolving
door shall have a side-hinged swinging door that complies with
paragraph (J)(1)(1010.1) of this rule in the
same wall and within 10 feet (3048 mm) of the revolving door.
7.
Revolving doors
shall not be part of an accessible route required by
paragraph
(I)(1009)
of this rule and chapter 11 of the
building
code as listed in rule
1301:7-7-80
of the Administrative Code.
[BE] Table
1010.1.4.1(1)
Maximum door speed manual
revolving doors
Revolving door maximum
nominal diameter (FT-IN)
|
Maximum allowable
revolving door speed (RPM)
|
6-0
|
12
|
7-0
|
11
|
8-0
|
10
|
9-0
|
9
|
10-0
|
8
|
For SI: 1 inch = 25.4 mm, 1 foot =
304.8 mm.
[BE] Table
1010.1.4(2)
Maximum door speed automatic or
power-operated revolving doors
Revolving door maximum
nominal diameter (FT-IN)
|
Maximum allowable
revolving door speed (RPM)
|
8-0
|
7.2
|
9-0
|
6.4
|
10-0
|
5.7
|
11-0
|
5.2
|
12-0
|
4.8
|
12-6
|
4.6
|
14-0
|
4.1
|
16-0
|
3.6
|
17-0
|
3.4
|
18-0
|
3.2
|
20-0
|
2.9
|
24-0
|
2.4
|
For SI: 1 inch = 25.4 mm, 1 foot =
304.8 mm.
(a)
[BE] 1010.1.4.1.1 Egress component.
A revolving door used as a component of a means of
egress shall comply with
paragraph (J)(1)(d)(i)(1010.1.4.1)
of this rule and the following three conditions:
(i)
Revolving doors
shall not be given credit for more than 50 per cent of the
minimum width or required capacity.
(ii)
Each revolving
door shall be credited with a capacity based on not more than a 50-person
occupant load.
(iii)
Each revolving door shall provide for egress in
accordance with BHMA A 156.27as listed in rule
1301:7-7-80
of the Administrative Code with a breakout force of not more than 130
pounds (578 N).
(b)
[BE] 1010.1.4.1.2 Other than egress component.
A revolving door used as other than a
component of a means of egress shall comply with
paragraph
(J)(1)(d)(a)(1010.1.4.1)
of this rule. The breakout force of a
revolving door not used as a component of a means of egress shall not be more
than 180 pounds (801 N).
Exception:
A breakout force in excess of 180 pounds (801 N) is
permitted if the collapsing force is reduced to not more than 130 pounds (578
N) when not less than one of the following conditions is
satisfied.
1.
There is a power failure or power is removed to the
device holding the door wings in position.
2.
There is an
actuation of the automatic sprinkler system where such system is
provided.
3.
There is an actuation of a smoke detection system that
is installed in accordance with paragraph (G)(907) of
rule
1301:7-7-09
of the Administrative Code to provide coverage in areas within the
building that are within 75 feet (22 860 mm) of the revolving
doors.
4.
There is an actuation of a manual control switch, in an
approved location and clearly identified, that reduces the breakout force to
not more than 130 pounds (578 N).
(ii)
[BE] 1010.1.4.2 Power-operated doors.
Where means of egress doors are operated or assisted by power, the design shall
be such that in the event of power failure, the door is capable of being opened
manually to permit means of egress travel or closed where necessary to
safeguard means of egress. The forces required to open these doors manually
shall not exceed those specified in
paragraph(J)(1)(c)(1010.1.3)
of this rule,
except that the force to set the door in motion shall not exceed 50 pounds (220
N). The door shall be capable of swinging open from any position to the full
width of the opening in which such door is installed when a force is applied to
the door on the side from which egress is made. Power-operated swinging doors,
power-operated sliding doors and power-operated folding doors shall comply with
BHMA A 156.10
as listed in rule
1301:7-7-80
of the Administrative Code. Power-assisted swinging doors and
low-energy power-operated swinging doors shall comply with BHMA A
156.19
as listed in rule
1301:7-7-80
of the Administrative Code.
Exceptions:
1.
Occupancies in
Group I-3.
2.
Horizontal sliding doors complying with
paragraph (J)(1)(d)(iii)(1010.1.4.3) of this
rule.
3.
For a biparting door in the emergency breakout mode, a
door leaf located within a multiple-leaf opening shall be exempt from the
minimum 32-inch (813 mm) single-leaf requirement of paragraph
(J)(1)(a)(1010.1.1) of this rule, provided a minimum 32-inch
(813 mm) clear opening is provided when the two biparting leaves meeting in the
center are broken out.
(iii)
[BE]
1010.1.4.3 Special purpose horizontal sliding, accordion or folding
doors. In other than Group H occupancies, special purpose horizontal
sliding, accordion, or folding door assemblies permitted to be a component of a
means of egress in accordance with exception 6 to
paragraph
(J)(1)(b)(1010.1.2)
of this rule shall comply with all of the
following criteria:
(a)
The doors shall be power operated and shall be capable
of being operated manually in the event of power failure.
(b)
The doors shall
be openable by a simple method from both sides without special knowledge or
effort.
(c)
The force required to operate the door shall not exceed
30 pounds (133 N) to set the door in motion and 15 pounds (67 N) to close the
door or open it to the minimum required width.
(d)
The door shall be
openable with a force not to exceed 15 pounds (67 N) when a force of 250 pounds
(1100 N) is applied perpendicular to the door adjacent to the operating
device.
(e)
The door assembly shall comply with the applicable fire
protection rating and, where rated, shall be self-closing or automatic closing
by smoke detection, in accordance with section 716.5.9.3 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code, shall be installed in accordance with NFPA
80 as listed in rule
1301:7-7-80
of the Administrative Code and shall comply with section 716
of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(f)
The door assembly
shall have an integrated standby power supply.
(g)
The door assembly
power supply shall be electrically supervised.
(h)
The door shall
open to the minimum required width within 10 seconds after activation of the
operating device.
(iv)
[BE]
1010.1.4.4 Security grilles. In Groups B, F, M and S, horizontal sliding
or vertical security grilles are permitted at the main exit and shall be
openable from the inside without the use of a key or special knowledge or
effort during periods that the space is occupied. The grilles shall remain
secured in the full-open position during the period of occupancy by the general
public. Where two or more means of egress are required, not more than one-half
of the exits or exit access doorways shall be equipped with horizontal sliding
or vertical security grilles.
(e)
1010.1.5
Floor elevation. There shall be a floor or landing on each side of a
door. Such floor or landing shall be at the same elevation on each side of the
door. Landings shall be level except for exterior landings, which are permitted
to have a slope not to exceed
one unit vertical in
fifty units horizontal (2
per cent
slope).
Exceptions:
1.
Doors serving
individual dwelling units in Groups R-2 and R-3 where the following
apply:
1.1
A
door is permitted to open at the top step of an interior flight of stairs,
provided the door does not swing over the top step.
1.2
Screen doors and
storm doors are permitted to swing over stairs or landings.
2.
Exterior doors as provided for in
paragraph (C)(5)( 1003.5) of this rule
exception 1, and paragraph (V)(2)( 1022.2) of this
rule, which are not on an accessible route.
3.
In Group R-3
occupancies not required to be Accessible units, Type A units or Type B units,
the landing at an exterior doorway shall be not more than 73/4 inches (197 mm)
below the top of the threshold, provided the door, other than an exterior storm
or screen door, does not swing over the landing.
4.
In units
not required to be Type A, Type B or accessible, variations in elevation due to differences in finish
materials, but not more than 1/2 inch ( 12.7 mm).
5.
Exterior decks,
patios or balconies that are part of Type B dwelling units, have impervious
surfaces and that are not more than 4 inches (102 mm) below the finished floor
level of the adjacent interior space of the dwelling unit.
6.
Doors serving
equipment spaces not required to be accessible in accordance with section
1103.2.9 of the building code as listed in rule
1301:7-7-80
of the Administrative Code and serving an occupant load of five or
less shall be permitted to have a landing on one side to be not more than 7
inches (178 mm) above or below the landing on the egress side of the
door.
(f)
[BE] 1010.1.6 Landings at doors.
Landings shall have a width not less than the width of
the stairway or the door, whichever is greater. Doors in the fully open
position shall not reduce a required dimension by more than 7 inches (178 mm).
Where a landing serves an occupant load of 50 or more, doors in any position
shall not reduce the landing to less than one-half its required width. Landings
shall have a length measured in the direction of travel of not less than 44
inches (1118 mm).
Exception:
Landing length in the direction of travel in Groups R-3
and U and within individual units of Group R-2 need not exceed 36 inches (914
mm) when the units are not required to be accessible or Type A
units.
(g)
[BE] 1010.1.7 Thresholds.
Thresholds at doorways shall not exceed 3/4 inch ( 19.1
mm) in height above the finished floor or landing for sliding doors serving
dwelling units or 1/2 inch ( 12.7 mm) above the finished floor or landing for
other doors. Raised thresholds and floor level changes greater than 1/4 inch (
6.4 mm) at doorways shall be beveled with a slope not greater than one unit
vertical in two units horizontal (50-
per cent slope).
Exceptions:
1.
In occupancy Group
R-2 or R-3, threshold heights for sliding and side-hinged exterior doors shall
be permitted to be up to 73/4 inches (197 mm) in height if all of the following
apply:
1.1.
The
door is not part of the required means of egress.
1.2.
The door is not
part of an accessible route as required by chapter 11 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code.
1.3.
The door is not
part of an accessible unit, Type A unit or Type B
unit.
2.
In Type B units, where Exception 5 to
paragraph (J)(1)(e)(1010.1.5) of this rule
permits a 4-inch (102 mm) elevation change at the door, the threshold height on
the exterior side of the door shall not exceed 4 3/4 inches (120 mm) in height
above the exterior deck, patio or balcony for sliding doors or 4 1/2 inches (114
mm) above the exterior deck, patio or balcony for other doors.
(h)
[BE] 1010.1.8 Door arrangement. Space
between two doors in a series shall be 48 inches (1219 mm) minimum plus the
width of a door swinging into the space. Doors in a series shall swing either
in the same direction or away from the space between the doors.
Exceptions:
1.
The minimum
distance between horizontal sliding power-operated doors in a series shall be
48 inches (1219 mm).
2.
Storm and screen doors serving individual dwelling
units in Groups R-2 and R-3 need not be spaced 48 inches (1219 mm) from the
other door.
3.
Doors within individual dwelling units in Groups R-2
and R-3 other than within Type A dwelling units.
(i)
[BE]
1010.1.9 Door operations. Except as specifically permitted by this
paragraph egress doors shall be readily openable from the
egress side without the use of a key or special knowledge or effort.
Exception:
A temporary door locking device that is approved by the
building official and noted on the certificate of occupancy in accordance with
section 1010.4 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, and that is used in accordance with section
1010.4.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(i)
[BE]
1010.1.9.1 Hardware. Door handles, pulls, latches, locks and other
operating devices on doors required to be accessible by Chapter 11 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code shall not require tight grasping, tight
pinching or twisting of the wrist to operate.
Exception:
A temporary door locking device that is approved by the
building official and noted on the certificate of occupancy in accordance with
section 1010.4 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, and that is used in accordance with section
1010.4.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
[BE]
1010.1.9.2 Hardware height. Door handles, pulls, latches, locks and
other operating devices shall be installed 34 inches (864 mm) minimum and 48
inches (1219 mm) maximum above the finished floor. Locks used only for security
purposes and not used for normal operation are permitted at any height.
Exception:
Access doors or gates in barrier walls and fences
protecting pools, spas and hot tubs shall be permitted to have operable parts
of the release of latch on self-latching devices at 54 inches (1370 mm) maximum
above the finished floor or ground, provided the self-latching devices are not
also self-locking devices operated by means of a key, electronic opener or
integral combination lock.
(iii)
[BE]
1010.1.9.3 Locks and latches. Locks and latches shall be permitted to
prevent operation of doors where any of the following exist:
(a)
Places of
detention or restraint.
(b)
In buildings in occupancy Group A having an occupant
load of 300 or less, Groups B, F, M and S, and in places of religious worship,
the main door or doors are permitted to be equipped with key-operated locking
devices from the egress side provided:
(i)
The locking
device is readily distinguishable as locked.
(ii)
A readily
visible durable sign is posted on the egress side on or adjacent to the door
stating: "THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED." The sign
shall be in letters 1 inch (25 mm) high on a contrasting
background.
(iii)
The use of the key-operated locking device is revocable
by the fire code official for due cause.
(c)
Where egress
doors are used in pairs, approved automatic flush bolts shall be permitted to
be used, provided that the door leaf having the automatic flush bolts does not
have a doorknob or surface-mounted hardware.
(d)
Doors from
individual dwelling or sleeping units of Group R occupancies having an occupant
load of 10 or less are permitted to be equipped with a night latch, dead bolt
or security chain, provided such devices are openable from the inside without
the use of a key or tool.
(e)
Fire doors after the minimum elevated temperature has
disabled the unlatching mechanism in accordance with listed fire door test
procedures.
(f)
A temporary door locking device that is approved by the
building official and noted on the certificate of occupancy in accordance with
section 1010.4 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, and that is used in accordance with section
1010.4.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(iv)
[BE]
1010.1.9.4 Bolt locks. Manually operated flush bolts or surface bolts
are not permitted.
Exceptions:
1.
On doors not
required for egress in individual dwelling units or sleeping
units.
2.
Where a pair of doors serves a storage or equipment
room, manually operated edge- or surface-mounted bolts are permitted on the
inactive leaf.
3.
Where a pair of doors serves an occupant load of less
than 50 persons in a Group B, F or S occupancy, manually operated edge- or
surface-mounted bolts are permitted on the inactive leaf. The inactive leaf
shall not contain doorknobs, panic bars or similar operating
hardware.
4.
Where a pair of doors serves a Group B, F or S
occupancy, manually operated edge- or surface-mounted bolts are permitted on
the inactive leaf provided such inactive leaf is not needed to meet egress
capacity requirements and the building is equipped throughout with an automatic
sprinkler system in accordance with paragraph
(C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code. The inactive leaf shall not contain
doorknobs, panic bars or similar operating hardware.
5.
Where a pair of
doors serves patient care rooms in Group I-2 occupancies, self latching edge-
or surface-mounted bolts are permitted on the inactive leaf provided that the
inactive leaf is not needed to meet egress capacity requirements and the
inactive leaf shall not contain doorknobs, panic bars or similar operating
hardware.
(v)
[BE] 1010.1.9.5 Unlatching. The unlatching
of any door or leaf shall not require more than one operation.
Exceptions:
1.
Places of
detention or restraint.
2.
Where manually operated bolt locks are permitted by
paragraph (J)(1)(i)(iv)(1010.1.9.4) of this
rule.
3.
Doors with automatic flush bolts as permitted by
paragraph (J)(1)(i)(iii)(1010.1.9.3), item 3 of this
rule.
4.
Doors from individual dwelling units and sleeping units
of Group R occupancies as permitted by paragraph
(J)(1)(i)(iii)(1010.1.9.3), item 4 of this
rule.
5.
A temporary door locking device that is
approved by the building official and noted on the certificate of occupancy in
accordance with section 1010.4 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, and that is used in accordance with section
1010.4.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.(a)
[BE] 1010.1.9.5.1 Closet and bathroom doors in
Group R-4 occupancies. In Group I-1 and Group R-4
occupancies, closet doors that latch in the closed position shall be
operable from inside the closet, and bathroom doors that latch
in the closed position shall be capable of being unlocked from the ingress
side.
(vi)
1010.1.9.6 Controlled egress doors in Groups I-1 and I-2. Electric
locking systems, including electromechanical locking systems and
electromagnetic locking systems, shall be permitted to be locked in the means
of egress in Group I-1 or I-2 occupancies where the clinical needs of persons
receiving care require their containment. Controlled egress doors shall be
permitted in such occupancies where the building is equipped throughout with an
automatic sprinkler system in accordance with
paragraph
(C)(3)(a)(i)(903.3.1.1)
of rule
1301:7-7-09
of the Administrative Code or an approved automatic smoke or heat
detection system installed
throughout the locked space in
accordance with
paragraph (G)(907)
of rule
1301:7-7-09
of the Administrative Code, provided that the doors are installed and
operate in accordance with all of the following:
(a)
The door locks
shall unlock upon actuation of the automatic sprinkler system or automatic fire
detection system.
(b)
The door locks shall unlock upon loss of power
controlling the lock or lock mechanism.
(c)
The door locking
system shall be installed to have the capability of being unlocked by a switch
located at the fire command center, a nursing station or other approved
location. The switch shall directly break power to the lock.
(d)
A building
occupant shall not be required to pass through more than one door equipped with
a controlled egress locking system before entering an exit.
(e)
The procedures
for unlocking the doors shall be described and approved as part of the
emergency planning and preparedness required by rule
1301:7-7-04
of the Administrative Code.
(f)
All clinical
staff shall have the keys, codes or other means necessary to operate the
locking systems.
(g)
Emergency lighting shall be provided at the
door.
(h)
The door locking system units shall be listed in
accordance with UL 294 as listed in rule
1301:7-7-80
of the Administrative Code.
Exceptions:
1.
Items (a) to (d)
shall not apply to doors to areas occupied' by persons who, because of clinical
needs, require restraint or containment as part of the function of a
psychiatric treatment area.
2.
Items (a) to (d)
shall not apply to doors to areas where a listed egress control system is
utilized to reduce the risk of child abduction from nursery and obstetric areas
of a Group I-2 hospital.
(vii)
[BE]
1010.1.9.7 Delayed egress. Delayed egress locking systems, shall be
permitted to be installed on doors serving any occupancy except Group A, E and
H in buildings that are equipped throughout with an automatic sprinkler system
in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1)
of rule
1301:7-7-09
of the Administrative Code or an approved automatic smoke or heat
detection system installed in accordance with
paragraph
(G)(907)
of rule
1301:7-7-09
of the Administrative Code. The locking system shall be installed and
operated in accordance with all of the following:
(a)
The delay
electronics of the delayed egress locking system shall deactivate upon
actuation of the automatic sprinkler system or automatic fire detection system,
allowing immediate, free egress.
(b)
The delay
electronics of the delayed egress locking system shall deactivate upon loss of
power controlling the lock or lock mechanism, allowing immediate free
egress.
(c)
The delayed egress locking system shall have the
capability of being deactivated at the fire command center and other approved
locations.
(d)
An attempt to egress shall initiate an irreversible
process that shall allow such egress in not more than 15 seconds when a
physical effort to exit is applied to the egress side door hardware for not
more than 3 seconds. Initiation of the irreversible process shall activate an
audible signal in the vicinity of the door. Once the delay electronics have
been deactivated, rearming the delay electronics shall be by manual means
only.
Exception:
Where approved, a delay of not more than 30 seconds is
permitted on a delayed egress door.
(e)
The egress path
from any point shall not pass through more than one delayed egress locking
system.
Exception:
In Group I-2 or I-3 occupancies, the egress path from
any point in the building shall not pass through more than two delayed egress
locking systems provided the combined delay does not exceed 30
seconds.
(f)
A sign shall be provided on the door and shall be
located above and within 12 inches (305 mm) of the door exit hardware.
(i)
For doors that
swing in the direction of egress, the sign shall read: "PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS."
(ii)
For doors that
swing in the opposite direction of egress, the sign shall read: "PULL UNTIL
ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS."
(iii)
The sign shall
comply with the visual character requirements in ICC A 117.1
as listed
in rule
1301:7-7-80
of the Administrative Code.
Exception:
Where approved, in Group I occupancies, the
installation of a sign is not required where care recipients who, because of
clinical needs, require restraint or containment as part of the function of the
treatment area.
(g)
Emergency
lighting shall be provided on the egress side of the door.
(h)
The delayed
egress locking system units shall be listed in accordance with UL 294
as listed in rule
1301:7-7-80
of the Administrative Code.
(i)
The
procedures for the operation(s) of the unlocking system shall be described and
approved as part of the emergency planning and preparedness required by rule
1301:7-7-04
of the Administrative Code.
(j)
All
clinical staff shall have the keys, codes or other means necessary to operate
the locking devices.
(viii)
[BE]
1010.1.9.8 Sensor release of electrically locked egress doors. The
electric locks on sensor-released doors located in a means of egress in
buildings with an occupancy in Groups A, B, E, I-1, I-2, I-4, M, R-1 or R-2 and
entrance doors to tenant spaces in occupancies in Groups A, B, E, I-1, I-2,
I-4, M, R-1 or R-2 are permitted where installed and operated in accordance
with all of the following criteria:
(a)
The sensor shall be installed on the egress side,
arranged to detect an occupant approaching the doors. The doors shall be
arranged to unlock by a signal from or loss of power to the
sensor.
(b)
Loss of power to the lock or locking system shall
automatically unlock the doors.
(c)
The doors shall
be arranged to unlock from a manual unlocking device located 40 inches to 48
inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524
mm) of the secured doors. Ready access shall be provided to the manual
unlocking device and the device shall be clearly identified by a sign that
reads "PUSH TO EXIT." When operated, the manual unlocking device shall result
in direct interruption of power to the lock-independent of other
electronics-and the doors shall remain unlocked for not less than 30
seconds.
(d)
Activation of the building fire alarm system, where
provided, shall automatically unlock the doors, and the doors shall remain
unlocked until the fire alarm system has been reset.
(e)
Activation of the
building automatic sprinkler or fire detection system, where provided, shall
automatically unlock the doors. The doors shall remain unlocked until the fire
alarm system has been reset.
(f)
The door locking
system units shall be listed in accordance with UL 294 as listed in
rule
1301:7-7-80
of the Administrative Code.
(ix)
[BE]
1010.1.9.9 Electromagnetically locked egress doors. Doors in the means
of egress in buildings with an occupancy in Group A, B, E, I-1, I-2, I-4, M,
R-1 or R-2 and doors to tenant spaces in Group A, B, E, I-1, I-2, I-4, M, R-1
or R-2 shall be permitted to be locked with an electromagnetic locking system
where equipped with hardware that incorporates a built-in switch and where
installed and operated in accordance with all of the following:
(a)
The hardware that
is affixed to the door leaf has an obvious method of operation that is readily
operated under all lighting conditions.
(b)
The hardware is
capable of being operated with one hand.
(c)
Operation of the
hardware directly interrupts the power to the electromagnetic lock and unlocks
the door immediately.
(d)
Loss of power to the locking system automatically
unlocks the door.
(e)
Where panic or fire exit hardware is required by
paragraph (H)(a)(x)(1010.1.10) of this rule,
operation of the panic or fire exit hardware also releases the electromagnetic
lock.
(f)
The locking system units shall be listed in accordance
with UL 294 as listed in rule
1301:7-7-80
of the Administrative Code.
(x)
[BE]
1010.1.9.10 Locking arrangements in correctional facilities. In
occupancies in Groups A-2, A-3, A-4, B, E, F, I-2, I-3, M and S within
correctional and detention facilities, doors in means of egress serving rooms
or spaces occupied by persons whose movements are controlled for security
reasons shall be permitted to be locked where equipped with egress control
devices that shall unlock manually and by not less than one of the following
means:
(a)
Activation of an automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of
rule
1301:7-7-09
of the Administrative Code.
(b)
Activation of an
approved manual fire alarm box.
(c)
A signal from a
constantly attended location.
(xi)
[BE]
1010.1.9.11 Stairway doors. Interior stairway means of egress doors
shall be openable from both sides without the use of a key or special knowledge
or effort.
Exceptions:
1.
Stairway discharge
doors shall be openable from the egress side and shall only be locked from the
opposite side.
2.
This paragraph shall not apply to
doors arranged in accordance with section 403.5.3 of the building code
as listed in rule
1301:7-7-80
of the Administrative Code.
3.
In stairways
serving not more than four stories, doors are permitted to be locked from the
side opposite the egress side, provided they are openable from the egress side
and capable of being unlocked simultaneously without unlatching upon a signal
from the fire command center, if present, or a signal by emergency personnel
from a single location inside the main entrance to the
building.
4.
Stairway exit doors shall be openable from the egress
side and shall only be locked from the opposite side in Group B, F, M and S
occupancies where the only interior access to the tenant space is from a single
exit stair where permitted in paragraph (F)(3)(b)(1006.3.2)
of this rule.
5.
Stairway exit
doors shall be openable from the egress side and shall only be locked from the
opposite side in Group R-2 occupancies where the only interior access to the
dwelling unit is from a single exit stairway where permitted in
paragraph (F)(3)(b)(1006.3.2) of this
rule.
(j)
[BE]
1010.1.10 Panic and fire exit hardware. Doors serving a Group H
occupancy and doors serving rooms or spaces with an occupant load of 50 or more
in a Group A or E occupancy shall not be provided with a latch or lock other
than panic hardware or fire exit hardware.
Exceptions:
1.
A main exit of a
Group A occupancy shall be permitted to be locking in accordance with
paragraph (J)(1)(i)(iii)(1010.1.9.3), Item 2 of this
rule.
2.
Doors serving a Group A or E occupancy shall be
permitted to be electromagnetically locked in accordance with
paragraph (J)(1)(i)(ix)(1010.1.9.9)
of this
rule.
Electrical rooms with equipment rated
1,200 amperes or more and over 6 feet (1829 mm) wide, and that contain
over-current devices, switching devices or control devices with exit or exit
access doors, must be equipped with panic hardware or fire exit hardware. The
doors shall swing in the direction of egress travel.
(i)
[BE]
1010.1.10.1 Installation. Where panic or fire exit hardware is
installed, it shall comply with the following:
(a)
Panic hardware
shall be listed in accordance with UL 305 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
Fire exit
hardware shall be listed in accordance with UL 10C and UL 305 as listed
in rule
1301:7-7-80
of the Administrative Code.
(c)
The actuating
portion of the releasing device shall extend not less than one-half of the door
leaf width.
(d)
The maximum unlatching force shall not exceed 15 pounds
(67 N).
(ii)
[BE] 1010.1.10.2 Balanced doors. If
balanced doors are used and panic hardware is required, the panic hardware
shall be of the push-pad type and the pad shall not extend more than one-half
the width of the door measured from the latch side.
(2)
[BE] 1010.2 Gates. Gates serving the means
of egress system shall comply with the requirements of this
paragraph. Gates used as a component in a means of egress
shall conform to the applicable requirements for doors.
Exception:
Horizontal sliding or swinging gates exceeding the
4-foot (1219 mm) maximum leaf width limitation are permitted in fences and
walls surrounding a stadium.
(a)
[BE] 1010.2.1 Stadiums. Panic hardware is
not required on gates surrounding stadiums where such gates are under constant
immediate supervision while the public is present, and where safe dispersal
areas based on 3 square feet ( 0.28 m2) per occupant
are located between the fence and enclosed space. Such required safe dispersal
areas shall not be located less than 50 feet (15 240 mm) from the enclosed
space. See paragraph (BB)(5)( 1028.5) of this
rule for means of egress from safe dispersal areas.
(3)
[BE] 1010.3 Turnstiles. Turnstiles or similar
devices that restrict travel to one direction shall not be placed so as to
obstruct any required means of egress.
Exception:
Each turnstile or similar device shall be credited with
a capacity based on not more than a 50-person occupant load where all of the
following provisions are met:
1.
Each device shall turn free in the direction of egress
travel when primary power is lost, and on the manual release by an employee in
the area.
2.
Such devices are not given credit for more than 50
per cent of the required egress capacity or
width.
3.
Each device is not more than 39 inches (991 mm)
high.
4.
Each device has not less than 161/2 inches (419 mm) clear
width at and below a height of 39 inches (991 mm) and not less than 22 inches
(559 mm) clear width at heights above 39 inches (991 mm).
Where located as part of an accessible
route, turnstiles shall have not less than 36 inches (914 mm) clear at and
below a height of 34 inches (864 mm), not less than 32 inches (813 mm) clear
width between 34 inches (864 mm) and 80 inches (2032 mm) and shall consist of a
mechanism other than a revolving device.
(a)
[BE]
1010.3.1 High turnstile.
Turnstiles more
than 39 inches (991 mm) high shall meet the requirements for revolving
doors.
(b)
[BE] 1010.3.2 Additional door.
Where serving an occupant load greater than 300, each
turnstile that is not portable shall have a side-hinged swinging door that
conforms to paragraph (J)(1)( 1010.1) of this
rule within 50 feet (15 240
mm).
(K)
Section
1011 Stairways
(1)
[BE] 1011.1 General.
Stairways serving occupied portions of a building shall
comply with the requirements of
paragraphs (K)(2)( 1011.2)
to (K)(13)( 1011.13)
of this rule.
Alternating tread devices shall comply with
paragraph (K)(14)(
1011.14)
of this rule. Ships ladders shall comply with
paragraph (K)(15)( 1011.15)
of this rule.
Ladders shall comply with
paragraph (K)(16)( 1011.16
)
of this rule.
Exception:
Within rooms or spaces used for assembly purposes,
stepped aisles shall comply with paragraph (CC)(1029)
of this rule.
(2)
[BE] 1011.2
Width and capacity.
The required capacity
of stairways shall be determined as specified in
paragraph
(E)(1)( 1005.1)
of this rule, but the minimum width shall not
be less than 44 inches (1118 mm). See
paragraph (I)(3)( 1009.3
)
of this rule for accessible means of egress stairways.
Exceptions:
1.
Stairways serving
an occupant load of less than 50 shall have a width of not less than 36 inches
(914 mm).
2.
Spiral stairways as provided for in paragraph
(K)(10)( 1011.10) of this rule.
3.
Where an incline
platform lift or stairway chairlift is installed on stairways serving
occupancies in Group R-3, or within dwelling units in occupancies in Group R-2,
a clear passage width not less than 20 inches (508 mm) shall be provided. Where
the seat and platform can be folded when not in use, the distance shall be
measured from the folded position.
(3)
[BE] 1011.3
Headroom.
Stairways shall have a minimum
headroom clearance of 80 inches (2032 mm) measured vertically from a line
connecting the edge of the nosings. Such headroom shall be continuous above the
stairway to the point where the line intersects the landing below, one tread
depth beyond the bottom riser. The minimum clearance shall be maintained the
full width of the stairway and landing.
Exceptions:
1.
Spiral stairways
complying with paragraph (K)(10)( 1011.10) of this
rule are permitted a 78-inch (1981 mm) headroom
clearance.
2.
In Group R-3 occupancies; within dwelling units in
Group R-2 occupancies; and in Group U occupancies that are accessory to a Group
R-3 occupancy or accessory to individual dwelling units in Group R-2
occupancies; where the nosings of treads at the side of a flight extend under
the edge of a floor opening through which the stair passes, the floor opening
shall be allowed to project horizontally into the required headroom not more
than 43/4 inches (121 mm).
(4)
[BE] 1011.4
Walkline.
The walkline across winder
treads shall be concentric to the direction of travel through the turn and
located 12 inches (305 mm) from the side where the winders are narrower. The 12
inch (305 mm) dimension shall be measured from the widest point of the clear
stair width at the walking surface of the winder. Where winders are adjacent
within the flight, the point of the widest clear stair width of the adjacent
winders shall be used.
(5)
1011.5 Stair treads and risers.
Stair treads and risers shall comply with
paragraphs (K)(5)(a)(1011.5.1)
to
(K)(5)(e)(iii)(1011.5.53)
of this rule.
(a)
[BE]
1011.5.1 Dimension reference surfaces. For
the purpose of this paragraph, all dimensions are exclusive of
carpets, rugs, or runners.
(b)
[BE]
1011.5.2 Riser height and tread depth. Stair riser heights shall be 7 inches (178 mm) maximum and 4
inches (102 mm) minimum. The riser height shall be measured vertically between
the nosings of adjacent treads. Rectangular tread depths shall be 11 inches
(279 mm) minimum measured horizontally between the vertical planes of the
foremost protection of adjacent treads and at a right angle to the tread's
nosing. Winder treads shall have a minimum tread depth of 11 inches (279 mm)
measured between the vertical planes of the foremost projection of adjacent
treads at the intersections with the walkline and a minimum tread depth of 10
inches (254 mm) within the clear width of the stair.
Exceptions:
1.
Spiral stairways
in accordance with paragraph (K)(10)( 1011.10) of
this rule.
2.
Stairways connecting stepped aisles to cross aisles or
concourses shall be permitted to use the riser/tread dimension in
paragraph (CC)(13)(b)(1029.13.2) of this
rule.
3.
In Group R-3 occupancies, within dwelling units in
Group R-2 occupancies; and in Group U occupancies that are accessory to a Group
R-3 occupancy or accessory to individual dwelling units in Group R-2
occupancies; the maximum riser height shall be 81/4 inches
( 209.55 mm); the minimum tread depth shall be
9 inches ( 228.6 mm); the minimum winder
tread depth at the walkline shall be 10 inches (254 mm); and the minimum winder
tread depth shall be 6 inches (152 mm). A nosing projection not less than 3/4
inch ( 19.1 mm) but not more than 11/4 inches (32 mm) shall be provided on
stairways with solid risers where the tread depth is less than 11 inches (279
mm).
4.
See section 403.1 of the International Existing
Building Code as listed in rule
1301:7-7-80
of the Administrative Code for the replacement of existing
stairways.
5.
In Group I-3 facilities, stairways providing access to
guard towers, observation stations and control rooms, not more than 250 square
feet (23 m2) in area, shall be permitted to have a
maximum riser height of 8 inches (203 mm) and a minimum tread depth of 9 inches
(229 mm).
(c)
[BE] 1011.5.3 Winder treads.
Winder treads are not permitted in means of egress
stairways except within a dwelling unit.
Exceptions:
1.
Curved stairways
in accordance with paragraph (K)(9)( 1011.9) of this
rule.
2.
Spiral stairways in accordance with
paragraph (K)(10)( 1011.10) of this
rule.
(d)
[BE] 1011.5.4 Dimensional
uniformity.
Stair treads and risers shall
be of uniform size and shape. The tolerance between the largest and smallest
riser or between the largest and smallest tread shall not exceed 3/8 inch ( 9.5
mm) in any flight of stairs. The greatest winder tread depth at the walkline
within any flight of stairs shall not exceed the smallest by more than 3/8 inch
( 9.5 mm).
Exceptions:
1.
Stairways
connecting stepped aisles to cross aisles or concourses shall be permitted to
comply with the dimensional nonuniformity in paragraph
(CC)(13)(b)(1029.13.2) of this rule.
2.
Consistently
shaped winders, complying with paragraph (K)(5)( 1011.5)
of this rule, differing from rectangular treads in the same
flight of stairs.
3.
Nonuniform riser dimension complying with
paragraph (K)(5)(d)(i)(1011.5.4.1)
of this
rule.(i)
[BE] 1011.5.4.1 Nonuniform height risers.
Where the bottom or top riser adjoins a sloping public way, walkway or
driveway having an established grade and serving as a landing, the bottom or
top riser is permitted to be reduced along the slope to less than 4 inches (102
mm) in height, with the variation in height of the bottom or top riser not to
exceed one unit vertical in 12 units horizontal (8-per cent
slope) of stair width. The nosings or leading edges of treads at such
nonuniform height risers shall have a distinctive marking stripe, different
from any other nosing marking provided on the stair flight. The distinctive
marking stripe shall be visible in descent of the stair and shall have a
slip-resistant surface. Marking stripes shall have a width of not less than 1
inch (25 mm) but not more than 2 inches (51 mm).
(e)
[BE] 1011.5.5 Nosing and riser profile.
Nosings shall have a curvature or bevel of not less
than 1/16 inch ( 1.6 mm) but not more than 9/16 inch ( 14.3 mm) from the
foremost projection of the tread. Risers shall be solid and vertical or sloped
under the tread above from the underside of the nosing above at an angle not
more than 30 degrees ( 0.52 rad) from the vertical.
(i)
[BE]
1011.5.5.1 Nosing projection size. The leading edge (nosings) of treads
shall project not more than 11/4 inches (32 mm) beyond the tread
below.
(ii)
[BE] 1011.5.5.2 Nosing projection uniformity.
Nosing projections of the leading edges shall be of uniform size,
including the projections of the nosing's leading edge of the floor at the top
of a flight.
(iii)
[BE] 1011.5.5.3 Solid risers. Risers shall
be solid.
Exceptions:
1.
Solid risers are
not required for stairways that are not required to comply with
paragraph (I)(3)( 1009.3) of this rule,
provided that the opening between treads does not permit the passage of a
sphere with a diameter of 4 inches (102 mm).
2.
Solid risers are
not required for occupancies in Group I-3 or in Group F, H and S occupancies
other than areas accessible to the public. There are no restrictions on the
size of the opening in the riser.
3.
Solid risers are
not required for spiral stairways constructed in accordance with
paragraph (K)(10)( 1011.10) of this
rule.
(6)
[BE] 1011.6
Stairway landings.
There shall be a floor
or landing at the top and bottom of each stairway. The width of landings shall
be not less than the width of stairways served. Every landing shall have a
minimum width measured perpendicular to the direction of travel equal to the
width of the stairway. Where the stairway has a straight run the depth need not
exceed 48 inches (1219 mm). Doors opening onto a landing shall not reduce the
landing to less than one-half the required width. When fully open, the door
shall not project more than 7 inches (178 mm) into a landing. Where wheelchair
spaces are required on the stairway landing in accordance with
paragraph (I)(6)(c)(1009.6.3)
of this rule,
the wheelchair space shall not be located in the required width of the landing
and doors shall not swing over the wheelchair spaces.
Exception:
Where stairways connect stepped aisles to cross aisles
or concourses, stairway landings are not required at the transition between
stairways and stepped aisles constructed in accordance with
paragraph (CC)(1029) of this
rule.
(7)
[BE] 1011.7 Stairway construction.
Stairways shall be built of materials consistent with
the types permitted for the type of construction of the building, except that
wood handrails shall be permitted for all types of construction.
(a)
[BE]
1011.7.1 Stairway walking surface.
The
walking surface of treads and landings of a stairway shall not be sloped
steeper than one unit vertical in 48 units horizontal (2-
per
cent slope) in any direction. Stairway treads and landings shall have
a solid surface. Finish floor surfaces shall be securely attached.
Exceptions:
1.
Openings in stair
walking surfaces shall be a size that does not permit the passage of 1/2-inch
diameter ( 12.7 mm) sphere. Elongated openings shall be placed so that the long
dimension is perpendicular to the direction of travel.
2.
In Group F, H and
S occupancies, other than areas of parking structures accessible to the public,
openings in treads and landings shall not be prohibited provided a sphere with
a diameter of 11/8 inches (29 mm) cannot pass through the
opening.
(b)
[BE] 1011.7.2 Outdoor conditions.
Outdoor stairways and outdoor approaches to stairways
shall be designed so that water will not accumulate on walking
surfaces.
(c)
[BE] 1011.7.3 Enclosures under interior
stairways.
The walls and soffits within
enclosed usable spaces under enclosed and unenclosed stairways shall be
protected by 1-hour fire-resistance-rated construction or the fire-resistance
rating of the stairway enclosure, whichever is greater. Access to the enclosed
space shall not be directly from within the stairway enclosure.
Exception:
Spaces under stairways serving and contained within a
single residential dwelling unit in Group R-2 or R-3 shall be permitted to be
protected on the enclosed side with 1/2-inch ( 12.7 mm) gypsum
board.
(d)
[BE] 1011.7.4 Enclosure under exterior stairways.
There shall not be enclosed usable space under exterior exit stairways
unless the space is completely enclosed in 1-hour fire-resistance-rated
construction. The open space under exterior stairways shall not be used for any
purpose.
(8)
[BE] 1011.8 Vertical rise.
A flight of stairs shall not have a vertical rise
greater than 12 feet (3658 mm) between floor levels or landings.
Exception:
Spiral stairways used as a means of egress from
technical production areas.
(9)
[BE] 1011.9
Curved stairways.
Curved stairways with
winder treads shall have treads and risers in accordance with
paragraph (K)(5)( 1011.5)
of this rule and
the smallest radius shall be not less than twice the minimum width or required
capacity of the stairway.
Exception:
The radius restriction shall not apply to curved
stairways in Group R-3 and within individual dwelling units in Group
R-2.
(10)
[BE] 1011.10 Spiral stairways.
Spiral stairways are permitted to be used as a
component in the means of egress only within dwelling units or from a space not
more than 250 square feet (23 m2) in area and
serving not more than five occupants, or from technical production areas in
accordance with section 410.6 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
A spiral stairway shall have a 71/2 inch
(191 mm) minimum clear tread depth at a point 12 inches (305 mm) from the
narrow edge. The risers shall be sufficient to provide a headroom of 78 inches
(1981 mm) minimum, but riser height shall not be more than 91/2 inches (241 mm).
The minimum stairway clear width at and below the handrail shall be 26 inches
(660 mm).
(11)
[BE] 1011.11 Handrails.
Stairways shall have handrails on each side and shall
comply with
paragraph (N)(1014)
of this rule.
Where glass is used to provide the handrail, the handrail shall also comply
with section 2407 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
Exceptions:
1.
Stairways within
dwelling units and spiral stairways are permitted to have a handrail on one
side only.
2.
Decks, patios and walkways that have a single change in
elevation where the landing depth on each side of the change of elevation is
greater than what is required for a landing do not require
handrails.
3.
In Group R-3 occupancies, a change in elevation
consisting of a single riser at an entrance or egress door does not require
handrails.
4.
Changes in room elevations of three or fewer risers
within dwelling units and sleeping units in Group R-2 and R-3 do not require
handrails.
(12)
[BE] 1011.12 Stairway to roof.
In buildings four or more stories above grade plane,
one stairway shall extend to the roof surface, unless the roof has a slope
steeper than four units vertical in 12 units horizontal (33-
per
cent slope).
Exception:
In buildings without an occupied roof, access to the
roof from the top story shall be permitted to be by an alternating tread
device, a ships ladder or a permanent ladder.
(a)
[BE]
1011.12.1 Roof access. Where a stairway is provided to a roof, access to
the roof shall be provided through a penthouse complying with section 1510.2 of
the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
Exception:
In buildings without an occupied roof, access to the
roof shall be permitted to be a roof hatch or trap door not less than 16 square
feet ( 1.5 m2) in area and having a minimum
dimension of 2 feet (610 mm).
(13)
[BE]
1011.13 Guards.
Guards shall be provided
along stairways and landings where required by paragraph
(O)(1015) of this rule and shall be constructed in accordance
with paragraph (O)(1015) of this rule. Where
the roof hatch opening providing the required access is located within 10 feet
(3049 mm) of the roof edge, such roof access or roof edge shall be protected by
guards installed in accordance with paragraph (O)(1015)
of this rule.
(14)
[BE]
1011.14 Alternating tread devices.
Alternating tread devices are limited to an element of a
means of egress in buildings of Groups F, H, and S from a mezzanine not more
than 250 square feet (23 m2) in area and that serves
not more than five occupants; in buildings of Group I-3 from a guard tower,
observation station or control room not more than 250 square feet (23
m2) in area and for access to unoccupied roofs.
Alternating tread devices used as a means of egress shall not have a rise
greater than 20 feet (6096 mm) between floor levels or landings.
(a)
[BE]
1011.14.1 Handrails of alternating tread devices.
Handrails shall be provided on both sides of
alternating tread devices and shall comply with paragraph
(N)(1014) of this rule.
(b)
[BE]
1011.14.2 Treads of alternating tread devices.
Alternating tread devices shall have a minimum tread
depth of 5 inches (127 mm), a minimum tread depth of 81/2 inches (216 mm), a
minimum tread width of 7 inches (178 mm) and a maximum riser height of 91/2
inches (241 mm). The tread depth shall be measured horizontally between the
vertical planes of the foremost projections of adjacent treads. The riser
height shall be measured vertically between the leading edges of adjacent
treads. The riser height and tread depth provided shall result in an angle of
ascent from the horizontal of between 50 and 70 degrees ( 0.87 and
1.22 rad). The initial tread of
the device shall begin at the same elevation as the platform, landing or floor
surface.
Exception:
Alternating tread devices used as an element of a means
of egress in buildings from a mezzanine area not more than 250 square feet (23
m2) in area that serves not more than five occupants
shall have a minimum tread depth of 3 inches (76 mm) with a minimum projected
tread depth of 101/2 inches (267 mm). The rise to the next alternating tread
surface shall not exceed 8 inches (203 mm).
(15)
[BE]
1011.15 Ships ladders.
Ships ladders are
permitted to be used in Group I-3 as a component of a means of egress to and
from control rooms or elevated facility observation stations not more than 250
square feet (23 m2) with not more than three
occupants and for access to unoccupied roofs. The minimum clear width at and
below the handrails shall be 20 inches (508 mm).
(a)
[BE]
1011.15.1 Handrails of ships ladders.
Handrails shall be provided on both sides of ships
ladders.
(b)
[BE] 1011.15.2 Treads of ships ladders.
Ships ladders shall have a minimum tread depth of 5
inches (127 mm). The tread shall be projected such that the total of the tread
depth plus the nosing projection is not less than 81/2 inches (216 mm). The
maximum riser height shall be 91/2 inches (241 mm).
(16)
[BE]
1011.16 Ladders.
Permanent ladders shall
not serve as a part of the means of egress from occupied spaces within a
building. Permanent ladders shall be permitted to provide access to the
following areas:
(a)
Spaces frequented only by personnel for maintenance,
repair or monitoring of equipment.
(b)
Nonoccupiable
spaces accessed only by catwalks, crawl spaces, freight elevators or very
narrow passageways.
(c)
Raised areas used primarily for purposes of security,
life safety or fire safety including, but not limited to, observation
galleries, prison guard towers, fire towers or lifeguard
stands.
(d)
Elevated levels in Group U not open to the general
public.
(e)
Nonoccupied roofs that are not required to have
stairway access in accordance with paragraph (K)(12)(a)(1011.12.1) of
this rule.
(f)
Ladders shall be constructed in accordance with section
306.5 of the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
(L)
Section
1012 Ramps
(1)
[BE] 1012.1 Scope.
The
provisions of this
paragraph shall apply to ramps used as a
component of a means of egress.
Exceptions:
1.
Ramped aisles
within assembly rooms or spaces shall comply with the provisions in
paragraph (CC)(1029) of this
rule.
2.
Curb ramps shall comply with the building code
as listed in rule
1301:7-7-80
of the Administrative Code.
3.
Vehicle ramps in
parking garages for pedestrian exit access shall not be required to comply with
paragraphs (L)(3)( 1012.3) to (L)(10)(
1012.10) of this rule where they are not an accessible route
serving accessible parking spaces, other required accessible elements or part
of an accessible means of egress.
(2)
[BE] 1012.2
Slope.
Ramps used as part of a means of
egress shall have a running slope not steeper than one unit vertical in 12
units horizontal (8-per cent slope). The slope of other
pedestrian ramps shall not be steeper than one unit vertical in eight units
horizontal ( 12.5 -per cent slope).
(3)
[BE] 1012.3
Cross slope.
The slope measured
perpendicular to the direction of travel of a ramp shall not be steeper than
one unit vertical in 48 units horizontal (2-per cent
slope).
(4)
[BE] 1012.4 Vertical rise.
The rise for any ramp run shall be 30 inches (762 mm)
maximum.
(5)
[BE] 1012.5 Minimum dimensions.
The minimum dimensions of means of egress ramps shall
comply with
paragraphs (L)(5)(a)(1012.5.1)
to
(L)(5)(c)(1012.5.3)
of this rule.
(a)
[BE]
1012.5.1 Width and capacity.
The minimum
width and required capacity of a means of egress ramp shall be not less than
that required for corridors by paragraph (T)(2)( 1020.2)
of this rule. The clear width of a ramp between handrails, if
provided, or other permissible projections shall be 36 inches (914 mm)
minimum.
(b)
[BE] 1012.5.2 Headroom.
The minimum headroom in all parts of the means of egress
ramp shall be not less than 80 inches (2032 mm).
(c)
[BE]
1012.5.3 Restrictions.
Means of egress
ramps shall not reduce in width in the direction of egress travel. Projections
into the required ramp and landing width are prohibited. Doors opening onto a
landing shall not reduce the clear width to less than 42 inches (1067
mm).
(6)
[BE] 1012.6 Landings.
Ramps shall have landings at the bottom and top of each
ramp, points of turning, entrance, exits and at doors. Landings shall comply
with
paragraphs (L)(6)(a)(1012.6.1)
to
(L)(6)(e)(1012.6.5)
of this rule.
(a)
[BE]
1012.6.1 Slope.
Landings shall have a
slope not steeper than one unit vertical in 48 units horizontal (2 per
cent slope) in any direction. Changes in level are not
permitted.
(b)
[BE] 1012.6.2 Width.
The landing shall be not less than the width of the widest
ramp run adjoining the landing.
(c)
[BE]
1012.6.3 Length.
The landing length shall
be 60 inches (1525 mm) minimum.
Exceptions:
1.
In Group R-2 and
R-3 individual dwelling and sleeping units that are not required to be
Accessible units, Type A units or Type B units in accordance with section 1107
of the building code as listed in rule
1301:7-7-80
of the Administrative Code, landings are permitted to be 36 inches
(914 mm) minimum.
2.
Where the ramp is not a part of an accessible route,
the length of the landing shall not be required to be more than 48 inches (1220
mm) in the direction of travel.
(d)
[BE]
1012.6.4 Change in direction.
Where
changes in direction of travel occur at landings provided between ramp runs,
the landing shall be 60 inches by 60 inches (1524 mm by 1524 mm) minimum.
Exception:
In Group R-2 and R-3 individual dwelling or sleeping
units that are not required to be Accessible units, Type A units or Type B
units in accordance with section 1107 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code, landings are permitted to be 36 inches by
36 inches (914 mm by 914 mm) minimum.
(e)
[BE]
1012.6.5 Doorways.
Where doorways are
located adjacent to a ramp landing, maneuvering clearances required by
the building code as listed in rule
1301:7-7-80
of the Administrative Code are permitted to overlap the required
landing area.
(7)
[BE] 1012.7 Ramp construction.
Ramps shall be built of materials consistent with the
types permitted for the type of construction of the building except that wood
handrails shall be permitted for all types of construction.
(a)
[BE]
1012.7.1 Ramp surface.
The surface of
ramps shall be of slip resistant materials that are securely
attached.
(b)
[BE] 1012.7.2 Outdoor conditions.
Outdoor ramps and outdoor approaches to ramps shall be
designed so that water will not accumulate on walking surfaces.
(8)
[BE] 1012.8 Handrails.
Ramps with a rise greater than 6 inches (152 mm) shall have
handrails on both sides. Handrails shall comply with paragraph
(N)(1014) of this rule.
(9)
[BE] 1012.9
Guards.
Guards shall be provided where
required by paragraph (O)(1015) of this rule
and shall be constructed in accordance with paragraph
(O)(1015) of this rule.
(10)
[BE]
1012.10 Edge protection.
Edge protection
complying with
paragraphs (L)(10)(a)(1012.10.1) or
(L)(10)(b)(1012.10.2)
of this rule shall be provided on each
side of ramp runs and at each side of ramp landings.
Exceptions:
1.
Edge protection is
not required on ramps that are not required to have handrails, provided they
have flared sides that comply with the building code as listed in rule
1301:7-7-80
of the Administrative Code curb ramp provisions.
2.
Edge protection is
not required on the sides of ramp landings serving an adjoining ramp run or
stairway.
3.
Edge protection is not required on the sides of ramp
landings having a vertical dropoff of not more than 1/2 inch ( 12.7 mm) within 10
inches (254 mm) horizontally of the required landing area.
(a)
[BE]
1012.10.1 Curb, rail, wall or barrier. A
curb, rail, wall or barrier shall be provided to serve as edge protection. A
curb shall be not less than 4 inches (102 mm) in height. Barriers shall be
constructed so that the barrier prevents the passage of a 4-inch-diameter (102
mm) sphere, where any portion of the sphere is within 4 inches (102 mm) of the
floor or ground surface.
(b)
[BE] 1012.10.2 Extended floor or ground
surface.
The floor or ground surface of
the ramp run or landing shall extend 12 inches (305 mm) minimum beyond the
inside face of a handrail complying with paragraph (N)(1014)
of this rule.
(M)
Section
1013 Exit signs
(1)
[BE] 1013.1 Where required.
Exits and exit access doors shall be marked by an
approved exit sign readily visible from any direction of egress travel. The
path of egress travel to exits and within exits shall be marked by readily
visible exit signs to clearly indicate the direction of egress travel in cases
where the exit or the path of egress travel is not immediately visible to the
occupants. Intervening means of egress doors within exits shall be marked by
exit signs. Exit sign placement shall be such that no point in an exit access
corridor or exit passageway is more than 100 feet (30 480 mm) or the listed
viewing distance for the sign, whichever is less, from the nearest visible exit
sign.
Exceptions:
1.
Exit signs are not
required in rooms or areas that require only one exit or exit
access.
2.
Main exterior exit doors or gates that are obviously
and clearly identifiable as exits need not have exit signs where approved by
the fire code official pursuant to paragraph (A)(1)( 1001.1)
of this rule. At locations or in structures not regulated by the
building code as listed in rule
1301:7-7-80
of the Administrative Code, main exterior exit doors or gates which obviously
and clearly are identifiable as exits need not have exit signs where approved
by the fire code official.
3.
Exit signs are not
required in occupancies in Group U and individual sleeping units or dwelling
units in Group R-1, R-2 or R-3.
4.
Exit signs are not
required in dayrooms, sleeping rooms or dormitories in occupancies in Group
I.
5.
In occupancies in Groups A-4 and A-5 exits signs are not
required on the seating side of vomitories or openings into seating areas where
exit signs are provided in the concourse that are readily apparent from the
vomitories. Egress lighting is provided to identify each vomitory or opening
within the seating area in an emergency.
(2)
[BE] 1013.2
Floor-level exit signs in Group R-1. Where
exit signs are required in Group R-1 occupancies by
paragraph
(M)(1)( 1013.1)
of this rule, additional low-level exit signs
shall be provided in all areas serving guestrooms in Group R-1 occupancies and
shall comply with
paragraph (M)(5)( 1013.5)
of this
rule.
The bottom of the sign shall be not
less than 10 inches (254 mm) nor more than 12 inches (305 mm) above the floor
level. The sign shall be flush mounted to the door or wall. Where mounted on
the wall, the edge of the sign shall be within 4 inches (102 mm) of the door
frame on the latch side.
(3)
[BE] 1013.3
Illumination.
Exit signs shall be
internally or externally illuminated.
Exception:
Tactile signs required by paragraph
(M)(4)( 1013.4) of this rule need not be provided with
illumination.
(4)
[BE] 1013.4 Raised character and braille exit
signs.
A sign stating "EXIT" in visual
characters, raised characters and braille and complying with the
building code as listed in rule
1301:7-7-80
of the Administrative Code shall be provided adjacent to each door to
an area of refuge, an exterior area for assisted rescue, an exit stairway or
ramp, an exit passageway and the exit discharge.
(5)
[BE] 1013.5
Internally illuminated exit signs.
Electrically powered, self-luminous and photoluminescent
exit signs shall be listed and labeled in accordance with UL 924 as
listed in rule
1301:7-7-80
of the Administrative Code and shall be installed in accordance with
the manufacturer's instructions and paragraph (D)(604)
of rule
1301:7-7-06
of the Administrative Code. Exit signs shall be illuminated at all
times.
(6)
1013.6 Externally illuminated exit signs.
Externally illuminated exit signs shall comply with
paragraphs (M)(6)(a)(1013.6.1)
to
(M)(6)(c)(1013.6.3)
of this rule.
(a)
[BE]
1013.6.1 Graphics.
Every exit sign and
directional exit sign shall have plainly legible letters not less than 6 inches
(152 mm) high with the principal strokes of the letters not less than
3/4 inch ( 19.1 mm) wide. The word "EXIT" shall have letters
having a width not less than 2 inches (51 mm) wide, except the letter "I," and
the minimum spacing between letters shall be not less than 3/8 inch ( 9.5 mm).
Signs larger than the minimum established in this
paragraph
shall have letter widths, strokes and spacing in proportion to their
height.
The word "EXIT" shall be in high
contrast with the background and shall be clearly discernible when the means of
exit sign illumination is or is not energized. If chevron directional indicator
is provided as part of the exit sign, the construction shall be such that the
direction of the chevron directional indicator cannot be readily
changed.
(b)
[BE] 1013.6.2 Exit sign
illumination.
The face of an exit sign
illuminated from an external source shall have an intensity of not less than 5
footcandles (54 lux).
(c)
[BE] 1013.6.3 Power source.
Exit signs shall be illuminated at all times. To ensure
continued illumination for a duration of not less than 90 minutes in case of
primary power loss, the sign illumination means shall be connected to an
emergency power system provided from storage batteries, unit equipment or an
on-site generator. The installation of the emergency power system shall be in
accordance with
paragraph (D)(604)
of rule
1301:7-7-06
of the Administrative Code.
Exceptions:
1.
Approved exit sign
illumination means that provide continuous illumination independent of external
power sources for a duration of not less than 90 minutes, in case of primary
power loss, are not required to be connected to an emergency electrical
system.
2.
Group I-2 Condition 2 exit sign illumination shall not
be provided by unit equipment battery only.
(N)
Section 1014 Handrails
(1)
[BE] 1014.1
Where required. Handrails serving stairways, ramps, stepped aisles and
ramped aisles shall be adequate in strength and attachment in accordance with
section 1607.8 of the building code as listed in rule
1301:7-7-80
of the Administrative Code. Handrails required for stairways by
paragraph (K)(11)( 1011.11) of this rule
shall comply with paragraphs (N)(2)( 1014.2)
to (N)(9)( 1014.9) of this rule. Handrails
required for ramps by paragraph (L)(8)( 1012.8) of
this rule shall comply with paragraphs (N)(2)( 1014.2
) to (N)(8)( 1014.8) of this rule. Handrails
for stepped aisles and ramped aisles required by paragraph
(CC)(15)( 1029.15) of this rule shall comply with
paragraphs (N)(2)( 1014.2) to (N)(8)( 1014.8
) of this rule.
(2)
[BE] 1014.2
Height.
Handrail height, measured above
stair tread nosings, or finish surface of ramp slope, shall be uniform, not
less than 34 inches (864 mm) and not more than 38 inches (965 mm). Handrail
height of alternating tread devices and ships ladders, measured above tread
nosings, shall be uniform, not less than 30 inches (762 mm) and not more than
34 inches (864 mm).
Exceptions:
1.
Where handrail
fittings or bendings are used to provide continuous transition between flights,
the fittings or bendings shall be permitted to exceed the maximum
height.
2.
In Group R-3 occupancies; within dwelling units in
Group R-2 occupancies; and in Group U occupancies that are associated with a
Group R-3 occupancy or associated with individual dwelling units in Group R-2
occupancies; where handrail fittings or bendings are used to provide continuous
transition between flights, transition at winder treads, transition from
handrail to guard, or where used at the start of a flight, the handrail height
at the fittings or bendings shall be permitted to exceed the maximum
height.
3.
Handrails on top of a guard where permitted along
stepped aisles and ramped aisles in accordance with paragraph
(CC)(15)( 1029.15) of this rule.
(3)
[BE] 1014.3
Handrail graspability.
Required handrails
shall comply with
paragraph (N)(3)(a)(1014.3.1)
of
this rule or shall provide equivalent graspability.
Exception:
In Group R-3 occupancies; within dwelling units in
Group R-2 occupancies; and in Group U occupancies that are accessory to a Group
R-3 occupancy or accessory to individual dwelling units in Group R-2
occupancies; handrails shall be Type I in accordance with
paragraph (N)(3)(a)(1014.3.1) of this rule,
Type II in accordance with paragraph (N)(3)(b)(1014.3.2)
of this rule or shall provide equivalent
graspability.
(a)
[BE] 1014.3.1 Type I.
Handrails with a circular cross section shall have an
outside diameter of not less than 11/4 inches (32 mm) and not
greater than 2 inches (51 mm). Where the handrail is not circular, it shall
have a perimeter dimension of not less than 4 inches (102 mm) and not greater
than 61/4 inches (160 mm) with a maximum cross-sectional
dimension of 21/4 inches (57 mm) and minimum cross-sectional
dimension of 1 inch (25 mm). Edges shall have a minimum radius of 0.01 inch (
0.25 mm).
(b)
[BE] 1014.3.2 Type II.
Handrails with a perimeter greater than 61/4
inches (160 mm) shall provide a graspable finger recess area on both sides of
the profile. The finger recess shall begin within a distance of
3/4 inch (19 mm) measured vertically from the tallest portion of
the profile and achieve a depth of not less than 5/16 inch (8 mm) within 7/8
inch (22 mm) below the widest portion of the profile. This required depth shall
continue for not less than 3/8 inch (10 mm) to a level that is not less than
13/4 inches (45 mm) below the tallest portion of the profile.
The minimum width of the handrail above the recess shall be not less than
11/4 inches (32 mm) to a maximum of 23/4 inches
(70 mm). Edges shall have a minimum radius of 0.01 inch ( 0.25
mm).
(4)
[BE] 1014.4 Continuity.
Handrail-gripping surfaces shall be continuous, without
interruption by newel posts or other obstructions.
Exceptions:
1.
Handrails within
dwelling units are permitted to be interrupted by a newel post at a turn or
landing.
2.
Within a dwelling unit, the use of a volute, turnout,
starting easing or starting newel is allowed over the lowest
tread.
3.
Handrail brackets or balusters attached to the bottom
surface of the handrail that do not project horizontally beyond the sides of
the handrail within 11/2 inches (38 mm) of the bottom of the handrail shall not
be considered to be obstructions. For each 1/2 inch ( 12.7 mm) of additional
handrail perimeter dimension above 4 inches (102 mm), the vertical clearance
dimension of 11/2 inches (38 mm) shall be permitted to be reduced by 1/8 inch (3
mm).
4.
Where handrails are provided along walking surfaces
with slopes not steeper than 1:20, the bottoms of the handrail gripping
surfaces shall be permitted to be obstructed along their entire length where
they are integral to crash rails or bumper guards.
5.
Handrails serving
stepped aisles or ramped aisles are permitted to be discontinuous in accordance
with paragraph (CC)(15)(a)(1029.15.1) of this
rule.
(5)
[BE] 1014.5 Fittings.
Handrails shall not rotate within their
fittings.
(6)
[BE] 1014.6 Handrail extensions.
Handrails shall return to a wall, guard or the walking
surface or shall be continuous to the handrail of an adjacent flight of stairs
or ramp run. Where handrails are not continuous between flights, the handrails
shall extend horizontally not less than 12 inches (305 mm) beyond the top riser
and continue to slope for the depth of one tread beyond the bottom riser. At
ramps where handrails are not continuous between runs, the handrails shall
extend horizontally above the landing 12 inches (305 mm) minimum beyond the top
and bottom of ramp runs. The extensions of handrails shall be in the same
direction of the flights of stairs at stairways and the ramp runs at
ramps.
Exceptions:
1.
Handrails within a
dwelling unit that is not required to be accessible need extend only from the
top riser to the bottom riser.
2.
Handrails serving
aisles in rooms or spaces used for assembly purposes are permitted to comply
with the handrail extensions in accordance with paragraph
(CC)(15)( 1029.15) of this rule.
3.
Handrails for
alternating tread devices and ships ladders are permitted to terminate at a
location vertically above the top and bottom risers. Handrails for alternating
tread devices are not required to be continuous between flights or to extend
beyond the top or bottom risers.
(7)
[BE] 1014.7
Clearance.
Clear space between a handrail
and a wall or other surface shall be not less than 11/2 inches (38 mm). A
handrail and a wall or other surface adjacent to the handrail shall be free of
any sharp or abrasive elements.
(8)
[BE] 1014.8
Projections.
On ramps and on ramped aisles
that are part of an accessible route, the clear width between handrails shall
be 36 inches (914 mm) minimum. Projections into the required width of aisles,
stairways and ramps at each side shall not exceed 41/2 inches (114 mm) at or
below the handrail height. Projections into the required width shall not be
limited above the minimum headroom height required in
paragraph (K)(3)( 1011.3) of this rule.
Projections due to intermediate handrails shall not constitute a reduction in
the egress width. Where a pair of intermediate handrails are provided within
the stairway width without a walking surface between the pair of intermediate
handrails and the distance between the pair of intermediate handrails is
greater than 6 inches (152 mm), the available egress width shall be reduced by
the distance between the closest edges of each such intermediate pair of
handrails that is greater than 6 inches (152 mm).
(9)
[BE] 1014.9
Intermediate handrails. Stairways shall have intermediate handrails
located in such a manner that all portions of the stairway minimum width or
required capacity are within 30 inches (762 mm) of a handrail. On monumental
stairs, handrails shall be located along the most direct path of egress
travel.
(O)
Section 1015 Guards
(1)
[BE] 1015.1
General.
Guards shall comply with the
provisions of paragraphs (O)(2)( 1015.2) to
(O)(7)( 1015.7) of this rule. Operable windows with sills
located more than 72 inches (1829 mm) above finished grade or other surface
below shall comply with paragraph (O)(8)( 1015.8) of
this rule.
(2)
[BE] 1015.2 Where required.
Guards shall be located along open sided walking
surfaces, including mezzanines, equipment platforms, aisles, stairs, ramps and
landings that are located more than 30 inches (762 mm) measured vertically to
the floor or grade below at any point within 36 inches (914 mm) horizontally to
the edge of the open side. Guards shall be adequate in strength and attachment
in accordance with section 1607.8 of the
building code as listed in
rule
1301:7-7-80
of the Administrative Code.
Exception:
Guards are not required for the following
locations:
1.
On the loading side of loading docks or
piers.
2.
On the audience side of stages and raised platforms,
including stairs leading up to the stage and raised platforms.
3.
On raised stage
and platform floor areas, such as runways, ramps and side stages used for
entertainment or presentations.
4.
At vertical
openings in the performance area of stages and platforms.
5.
At elevated
walking surfaces appurtenant to stages and platforms for access to and
utilization of special lighting or equipment.
6.
Along vehicle
service pits not accessible to the public.
7.
In assembly
seating areas at cross aisles in accordance with
paragraph
(CC)(16)(b)(1029.16.2)
of this rule.
(a)
[BE]
1015.2.1 Glazing. Where glass is used to provide a guard or as a portion
of the guard system, the guard shall comply with section 2407 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code. Where the glazing provided does not meet
the strength and attachment requirements in section 1607.8 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code, complying guards shall be located along
glazed sides of open-sided walking surfaces.
(3)
[BE] 1015.3 Height.
Required guards shall be not less than 42 inches (1067 mm)
high, measured vertically as follows:
(a)
From the adjacent
walking surfaces.
(b)
On stairways and stepped aisles, from the line
connecting the leading edges of the tread nosings.
(c)
On ramps and
ramped aisles, from the ramp surface at the guard.
Exceptions:
1.
For occupancies in
Group R-3 not more than three stories above grade in height and within
individual dwelling units in occupancies in Group R-2 not more than three
stories above grade in height with separate means of egress, required guards
shall be not less than 36 inches (914 mm) in height measured vertically above
the adjacent walking surfaces or adjacent fixed seating.
2.
For occupancies in
Group R-3, and within individual dwelling units in occupancies in Group R-2,
guards on the open sides of stairs shall have a height not less than 34 inches
(864 mm) measured vertically from a line connecting the leading edges of the
treads.
3.
For occupancies in Group R-3, and within individual
dwelling units in occupancies in Group R-2, where the top of the guard also
serves as a handrail on the open sides of stairs, the top of the guard shall be
not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured
vertically from a line connecting the leading edges of the
treads.
4.
The guard height in assembly seating areas shall comply
with paragraph (CC)(16)( 1029.16) of this
rule.
5.
Along alternating tread device and ships ladders,
guards where the top rail also serves as a handrail, shall have height not less
than 30 inches (762 mm) and not more than 34 inches (864 mm), measured
vertically from the leading edge of the device tread nosing.
(4)
[BE] 1015.4 Opening limitations.
Required guards shall not have openings that allow
passage of a sphere 4 inches (102 mm) in diameter from the walking surface to
the required guard height.
Exceptions:
1.
From a height of
36 inches (914 mm) to 42 inches (1067 mm), guards shall not have openings that
allow passage of a sphere 43/8 inches (111 mm) in diameter.
2.
The triangular
openings at the open sides of a stair, formed by the riser, tread and bottom
rail shall not allow passage of a sphere 6 inches (152 mm) in
diameter.
3.
At elevated walking surfaces for access to and use of
electrical, mechanical or plumbing systems or equipment, guards shall not have
openings that allow passage of a sphere 21 inches (533 mm) in
diameter.
4.
In areas that are not open to the public within
occupancies in Group I-3, F, H or S, and for alternating tread devices and
ships ladders, guards shall not have openings that allow passage of a sphere 21
inches (533 mm) in diameter.
5.
In assembly
seating areas, guards required at the end of aisles in accordance with
paragraph (CC)(16)(d)(1029.16.4) of this rule
shall not have openings that allow passage of a sphere 4 inches (102 mm) in
diameter up to a height of 26 inches (660 mm). From a height of 26 inches (660
mm) to 42 inches (1067 mm) above the adjacent walking surfaces, guards shall
not have openings that allow passage of a sphere 8 inches (203 mm) in
diameter.
6.
Within individual dwelling units and sleeping units in
Group R-2 and R-3 occupancies, guards on the open sides of stairs shall not
have openings that allow passage of a sphere 43/8 (111 mm) inches in
diameter.
(5)
[BE] 1015.5 Screen porches.
Porches and decks that are enclosed with insect
screening shall be provided with guards where the walking surface is located
more than 30 inches (762 mm) above the floor or grade below.
(6)
[BE] 1015.6
Mechanical equipment, systems and devices.
Guards shall be provided where various components that
require service are located within 10 feet (3048 mm) of a roof edge or open
side of a walking surface and such edge or open side is located more than 30
inches (762 mm) above the floor, roof or grade below. The guard shall extend
not less than 30 inches (762 mm) beyond each end of such components. The guard
shall be constructed so as to prevent the passage of a sphere 21 inches (533
mm) in diameter.
Exception:
Guards are not required where permanent fall
arrest/restraint anchorage connector devices that comply with ANSI/ASSE Z
359.1as listed in rule
1301:7-7-80
of the Administrative Code are affixed for use during the entire roof
covering lifetime. The devices shall be re-evaluated for possible replacement
when the entire roof covering is replaced. The devices shall be placed not more
than 10 feet (3048 mm) on center along hip and ridge lines and placed not less
than 10 feet (3048 mm) from the roof edge or open side of the walking
surface.
(7)
[BE] 1015.7 Roof access.
Guards shall be provided where the roof hatch opening
is located within 10 feet (3048 mm) of a roof edge or open side of a walking
surface and such edge or open side is located more than 30 inches (762 mm)
above the floor, roof or grade below. The guard shall be constructed so as to
prevent the passage of a sphere 21 inches (533 mm) in diameter.
Exception:
Guards are not required where permanent fall
arrest/restraint anchorage connector devices that comply with ANSI/ASSE Z
359.1as listed in rule
1301:7-7-80
of the Administrative Code are affixed for use during the entire roof
covering lifetime. The devices shall be re-evaluated for possible replacement
when the entire roof covering is replaced. The devices shall be placed not more
than 10 feet (3048 mm) on center along hip and ridge lines and placed not less
than 10 feet (3048 mm) from the roof edge or open side of the walking
surface.
(8)
[BE] 1015.8 Window openings.
Windows in Group R-2 and R-3 buildings including
dwelling units, where the top of the sill of an operable window opening is
located less than 36 inches above the finished floor and more than 72 inches
(1829 mm) above the finished grade or other surface below on the exterior of
the building, shall comply with one of the following:
1.
Operable windows
where the top of the sill of the opening is located more than 75 feet (22 860
mm) above the finished grade or other surface below and that are provided with
window fall prevention devices that comply with ASTM F 2006 as listed
in rule
1301:7-7-80
of the Administrative Code.
2.
Operable windows
where the openings will not allow a 4-inch-diameter (102 mm) sphere to pass
through the opening when the window is in its largest opened
position.
3.
Operable windows where the openings are provided with
window fall prevention devices that comply with ASTM F 2090 as listed
in rule
1301:7-7-80
of the Administrative Code.
4.
Operable windows
that are provided with window opening control devices that comply with
paragraph (O)(8)(a)(1015.8.1)
of this
rule.
(a)
[BE] 1015.8.1 Window opening control
devices. Window opening control devices shall comply with ASTM F 2090
as listed in rule
1301:7-7-80
of the Administrative Code. The window opening control device, after
operation to release the control device allowing the window to fully open,
shall not reduce the minimum net clear opening area of the window unit to less
than the area required by paragraph (DD)(2)( 1030.2)
of this rule.
(P)
Section
1016 Exit access
(1)
[BE] 1016.1 General.
The exit access shall comply with the applicable provisions
of paragraphs (C)(1003) to (O)(1015)
of this rule. Exit access arrangement shall comply with
paragraphs (P)(1016) to (U)(1021) of
this rule.
(2)
[BE] 1016.2 Egress through intervening spaces.
Egress through intervening spaces shall
comply with this
paragraph.
1.
Exit access
through an enclosed elevator lobby is permitted. Access to not less than one of
the required exits shall be provided without travel through the enclosed
elevator lobbies required by section 3006.2, 3007 or 3008 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code. Where the path of exit access travel
passes through an enclosed elevator lobby the level of protection required for
the enclosed elevator lobby is not required to be extended to the exit unless
direct access to an exit is required by other paragraphs of
this code.
2.
Egress from a room or space shall not pass through
adjoining or intervening rooms or areas, except where such adjoining rooms or
areas and the area served are accessory to one or the other, are not a Group H
occupancy and provide a discernible path of egress travel to an exit.
Exception:
Means of egress are not prohibited through adjoining or
intervening rooms or spaces in a Group H, S or F occupancy where the adjoining
or intervening rooms or spaces are the same or a lesser hazard occupancy
group.
3.
An exit access shall not pass through a room that can
be locked to prevent egress.
4.
Means of egress
from dwelling units or sleeping areas shall not lead through other sleeping
areas, toilet rooms or bathrooms.
5.
Egress shall not
pass through kitchens, storage rooms, closets or spaces used for similar
purposes.
Exceptions:
1.
Means of egress
are not prohibited through a kitchen area serving adjoining rooms constituting
part of the same dwelling unit or sleeping unit.
2.
Means of egress
are not prohibited through stockrooms in Group M occupancies where all of the
following are met:
2.1
The stock is of the same hazard classification as that
found in the main retail area.
2.2
Not more than 50
per cent of the exit access is through the
stockroom.
2.3
The stockroom is not subject to locking from the egress
side.
2.4
There is a demarcated, minimum 44-inch-wide (1118 mm)
aisle defined by full- or partial-height fixed walls or similar construction
that will maintain the required width and lead directly from the retail area to
the exit without obstructions.
(a)
[BE] 1016.2.1 Multiple tenants. Where more
than one tenant occupies any one floor of a building or structure, each tenant
space, dwelling unit and sleeping unit shall be provided with access to the
required exits without passing through adjacent tenant spaces, dwelling units
and sleeping units.
Exception:
The means of egress from a smaller tenant space shall
not be prohibited from passing through a larger adjoining tenant space where
such rooms or spaces of the smaller tenant occupy less than 10 per
cent of the area of the larger tenant space through which they pass;
are the same or similar occupancy group; a discernible path of egress travel to
an exit is provided; and the means of egress into the adjoining space is not
subject to locking from the egress side. A required means of egress serving the
larger tenant space shall not pass through the smaller tenant space or
spaces.
(Q)
Section
1017 Exit access travel distance
(1)
[BE] 1017.1
General.
Travel distance within the exit
access portion of the means of egress system shall be in accordance with this
paragraph.
(2)
[BE] 1017.2
Limitations.
Exit access travel distance
shall not exceed the values given in Table 1017.2
of this
rule.
Table 1017.2
Exit access travel
distancea
Occupancy
|
Without sprinkler system
(feet)
|
With sprinkler system
(feet)
|
A, E, F-1, M, R,
S-1
|
200
|
250b
|
I-1
|
Not permitted
|
250c
|
B
|
200
|
300c
|
F-2, S-2, U
|
300
|
400c
|
H-1
|
Not permitted
|
75d
|
H-2
|
Not permitted
|
100d
|
H-3
|
Not permitted
|
150d
|
H-4
|
Not permitted
|
175d
|
H-5
|
Not permitted
|
200c
|
I-2, I-3, I-4
|
Not permitted
|
200c
|
For SI: 1 foot = 304.8 mm.
a. See the following sections for
modifications to exit access travel distance requirements:
Section 402.8 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code: For the distance limitation in
malls.
Section 404.9 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code: For the distance limitation through an
atrium space.
Section 407.4 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code: For the distance limitation in Group
I-2.
Section 408.6.1 and 408.8.1 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code: For the distance limitations
in
Group I-3. Section 411.4 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code: For the distance limitation in special
amusement buildings.
Section 412.7 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code: For the distance limitation in aircraft
manufacturing facilities.
Paragraph
(F)(2)(b)(ii)(1006.2.2.2) of this rule: For the distance
limitation in refrigeration machinery rooms.
Paragraph
(F)(2)(b)(iii)(1006.2.2.3) of this rule: For the distance
limitation in refrigerated rooms and spaces.
Paragraph
(F)(3)(b)(1006.3.2) of this rule: For buildings with one
exit.
Paragraph
(Q)(2)(b)(1017.2.2) of this rule: For
increased distance limitation in Groups F-1 and S-1.
Paragraph (CC)(7)(
1029.7) of this rule: For increased limitation in assembly
seating.
Section 3103.4 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code: For temporary structures.
Section 3104.9 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code: For pedestrian walkways.
b. Buildings equipped throughout with
an automatic sprinkler system in accordance with paragraph
(C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code. See paragraph (C)(903)
of rule
1301:7-7-09
of the Administrative Code for occupancies where automatic sprinkler
systems are permitted in accordance with paragraph
(C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code.
c. Buildings equipped throughout with
an automatic sprinkler system in accordance with paragraph
(C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
d. Group H occupancies equipped
throughout with an automatic sprinkler system in accordance with
paragraph (C)(2)(e)(i)(903.2.5.1) of rule
1301:7-7-09
of the Administrative Code.
(a)
[BE]
1017.2.1 Exterior egress balcony increase. Exit access travel distances
specified in Table 1017.2of this rule shall be increased up to
an additional 100 feet (30 480 mm) provided the last portion of the exit access
leading to the exit occurs on an exterior egress balcony constructed in
accordance with paragraph (U)(1021) of this
rule. The length of such balcony shall be not less than the amount of
the increase taken.
(b)
[BE] 1017.2.2 Group F-1 and S-1 increase.
The maximum exit access travel distance shall be 400 feet (122 m) in Group F-1
or S-1 occupancies where all of the following conditions are met:
(i)
The portion of
the building classified as Group F-1 or S-1 is limited to one story in
height.
(ii)
The minimum height from the finished floor to the
bottom of the ceiling or roof slab or deck is 24 feet (7315
mm).
(iii)
The building is equipped throughout with an automatic
sprinkler system in accordance with paragraph
(C)(3)(a)(i)(9033.1.1) of rule
1301:7-7-09
of the Administrative Code.
(iv)
The
portion of the building classified as Group F-1 or S-1 is equipped throughout
with an early suppression fast response (ESFR) automatic fire sprinkler system
in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code; and
(v)
The
portion of the building classified as Group F-1 or S-1 is equipped with a
normally activated smoke exhaust system complying with paragraph
(J)(5)( 910.5) of rule
1301:7-7-09
of the Administrative Code.
(3)
[BE] 1017.3
Measurement. Exit access travel distance shall be measured from the most
remote point within a story along the natural and unobstructed path of
horizontal and vertical egress travel to the entrance to an exit.
Exception:
In open parking garages, exit access travel distance is
permitted to be measured to the closest riser of an exit access stairway or the
closest slope of an exit access ramp.
(a)
[BE]
1017.3.1 Exit access stairways and ramps. Travel distance on exit access
stairways or ramps shall be included in the exit access travel distance
measurement. The measurement along stairways shall be made on a plane parallel
and tangent to the stair tread nosings in the center of the stair and landings.
The measurement along ramps shall be made on the walking surface in the center
of the ramp and landings.
(R)
Section
1018 Aisles
(1)
[BE] 1018.1 General.
Aisles and aisle accessways serving as a portion of the exit
access in the means of egress system shall comply with the requirements of this
paragraph. Aisles or aisle accessways shall be provided from
all occupied portions of the exit access that contain seats, tables,
furnishings, displays and similar fixtures or equipment. The minimum width or
required capacity of aisles shall be unobstructed.
Exception:
Encroachments complying with paragraph
(E)(7)( 1005.7) of this rule.
(2)
[BE] 1018.2
Aisles in assembly spaces.
Aisles and
aisle accessways serving a room or space used for assembly purposes shall
comply with paragraph (CC)(1029) of this
rule.
(3)
[BE] 1018.3 Aisles in Groups B and M.
In Group B and M occupancies, the minimum clear aisle
width shall be determined by
paragraph (E)(1)( 1005.1)
of this rule for the occupant load served, but shall be not
less than that required for corridors by
paragraph (T)(2)(
1020.2)
of this rule.
Exception:
Nonpublic aisles serving less than 50 people and not
required to be accessible by chapter 11 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code need not exceed 28 inches (711 mm) in
width.
(4)
[BE] 1018.4 Aisle accessways in Group M.
An aisle accessway shall be provided on not less than
one side of each element within the merchandise pad. The minimum clear width
for an aisle accessway not required to be accessible shall be 30 inches (762
mm). The required clear width of the aisle accessway shall be measured
perpendicular to the elements and merchandise within the merchandise pad. The
30-inch (762 mm) minimum clear width shall be maintained to provide a path to
an adjacent aisle or aisle accessway. The common path of egress travel shall
not exceed 30 feet (9144 mm) from any point in the merchandise pad.
Exception:
For areas serving not more than 50 occupants, the
common path of egress travel shall not exceed 75 feet (22 880 mm).
(5)
[BE] 1018.5 Aisles in other than assembly spaces and
Groups B and M. In other than rooms or spaces used for assembly purposes
and Group B and M occupancies, the minimum clear aisle capacity shall be
determined by
paragraph (E)(1)( 1005.1)
of this
rule for the occupant load served, but the width shall be not less
than that required for corridors by
paragraph (T)(2)( 1020.2)
of this rule.
Exception:
Nonpublic aisles serving less than 50 people and not
required to be accessible by chapter 11 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code need not exceed 28 inches (711 mm) in
width.
(S)
Section 1019 Exit access stairways and
ramps
(1)
[BE]
1019.1 General.
Exit access stairways and
ramps serving as an exit access component in a means of egress system shall
comply with the requirements of this paragraph. The number of
stories connected by exit access stairways and ramps shall include basements,
but not mezzanines.
(2)
[BE] 1019.2 All occupancies.
Exit access stairways and ramps that serve floor levels
within a single story are not required to be enclosed.
(3)
[BE] 1019.3
Occupancies other than Groups I-2 and I-3.
In other than Group I-2 and I-3 occupancies, floor openings
containing exit access stairways or ramps that do not comply with one of the
conditions listed in this
paragraph shall be enclosed with a
shaft enclosure constructed in accordance with section 713 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.(a)
Exit access stairways and ramps that serve, or
atmospherically communicate between, only two stories. Such interconnected
stories shall not be open to other stories.
(b)
In Group R-1, R-2
or R-3 occupancies, exit access stairways and ramps connecting four stories or
less serving and contained within an individual dwelling unit or sleeping unit
or live/work unit.
(c)
Exit access stairways serving and contained within a
Group R-3 congregate residence or a Group R-4 facility are not required to be
enclosed.
(d)
Exit access stairways and ramps in buildings equipped
throughout with an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code, where the area of the vertical opening
between stories does not exceed twice the horizontal projected area of the
stairway or ramp, and the opening is protected by a draft curtain and closely
spaced sprinklers in accordance with NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code. In other than Group B and M occupancies,
this provision is limited to openings that do not connect more than four
stories.
(e)
Exit access stairways and ramps within an atrium
complying with the provisions of section 404 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code.
(f)
Exit access
stairways and ramps in open parking garages that serve only the parking
garage.
(g)
Exit access stairways and ramps serving open-air
seating complying with the exit access travel distance requirements of
paragraph (CC)(7)( 1029.7) of this
rule.
(h)
Exit access stairways and ramps serving the balcony,
gallery or press box and the main assembly floor in occupancies such as
theaters, places of religious worship, auditoriums and sports
facilities.
(4)
[BE] 1019.4 Group I-2 and I-3 occupancies.
In Group I-2 and I-3 occupancies, floor openings between stories containing
exit access stairways or ramps are required to be enclosed with a shaft
enclosure constructed in accordance with section 713 of the
building
code as listed in rule
1301:7-7-80
of the Administrative Code.
Exception:
In Group I-3 occupancies, exit access stairways or
ramps constructed in accordance with section 408 of the building code
as listed in rule
1301:7-7-80
of the Administrative Code are not required to be
enclosed.
(T)
Section
1020 Corridors
(1)
[BE] 1020.1 Construction. Corridors shall
be fire-resistance rated in accordance with Table 1020.1
of this
rule. The corridor walls required to be fire-resistance rated shall
comply with section 708 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code for fire partitions.
Exceptions:
1.
A fire-resistance
rating is not required for corridors in an occupancy in Group E where each room
that is used for instruction has not less than one door opening directly to the
exterior and rooms for assembly purposes have not less than one-half of the
required means of egress doors opening directly to the exterior. Exterior doors
specified in this exception are required to be at ground level.
2.
A fire-resistance
rating is not required for corridors contained within a dwelling unit or
sleeping unit in an occupancy in Groups I-1 and R.
3.
A fire-resistance
rating is not required for corridors in open parking garages.
4.
A fire-resistance
rating is not required for corridors in an occupancy in Group B that is a space
requiring only a single means of egress complying with
paragraph (F)(2)( 1006.2) of this
rule.
5.
Corridors adjacent to the exterior walls of buildings
shall be permitted to have unprotected openings on unrated exterior walls where
unrated walls are permitted by Table 602 of the
building code as listed
in rule
1301:7-7-80
of the Administrative Code and unprotected openings are permitted by
Table 705.8 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
[BE] Table
1020.1
Corridor fire-resistance
rating
Occupancy
|
Occupant load served by
corridor
|
Required fire-resistance
rating (hours)
|
Without sprinkler
system
|
With sprinkler
systemc
|
H-1, H-2, H-3
|
All
|
Not permitted
|
1
|
H-4, H-5
|
Greater than 30
|
Not permitted
|
1
|
A, B, E, F, M, S,
U
|
Greater than 30
|
1
|
0
|
R
|
Greater than 10
|
Not permitted
|
0.5
|
I-2a, I-4
|
All
|
Not permitted
|
0
|
I-1, I-3
|
All
|
Not permitted
|
1b
|
a. For requirements for occupancies in
Group I-2, see sections 407.2 and 407.3 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code.
b. For a reduction in the
fire-resistance rating for occupancies in Group I-3, see section 408.8 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
c. Buildings equipped throughout with
an automatic sprinkler system in accordance with paragraph
(C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code where allowed.
d. One hour when design
qualifies in accordance with paragraph (C)(2)(h)(903.2.8), exception 3 of rule
1301:7-7-09
of the Administrative Code.
(2)
[BE] 1020.2
Width and capacity. The required capacity of corridors shall be
determined as specified in
paragraph (E)(1)( 1005.1)
of this rule, but the minimum width shall be not less than
that specified in Table 1020.2
of this rule.
Exception:
In Group I-2 occupancies, corridors are not required to
have a clear width of 96 inches (2438 mm) in areas where there will not be
stretcher or bed movement for access to care or as part of the defend-in-place
strategy.
[BE] Table
1020.2
Minimum corridor
width
Occupancy
|
Minimum width
(inches)
|
Any facilities not listed
below
|
44
|
Access to a utilization of
mechanical, plumbing or electrical systems or equipment
|
24
|
With an occupant load of less
than 50
|
36
|
Within a dwelling
unit
|
36
|
In Group E with a corridor
having an occupant load of 100 or more
|
72
|
In corridors and areas serving
stretcher traffic in ambulatory care facilities
|
72
|
Group I-2 in areas where
required for bed movement
|
96
|
For SI: 1 inch = 25.4 mm.
(3)
[BE] 1020.3 Obstruction.
The minimum width or required capacity of corridors
shall be unobstructed.
Exception: Encroachments
complying with paragraph (E)(7)( 1005.7) of this
rule.
(4)
[BE] 1020.4 Dead ends.
Where more than one exit or exit access doorway is
required, the exit access shall be arranged such that there are no dead ends in
corridors more than 20 feet (6096 mm) in length.
Exceptions:
1.
In occupancies in
Group I-3 of Occupancy Condition 2, 3 or 4 the dead end in a corridor shall not
exceed 50 feet (15 240 mm).
2.
In occupancies in
Groups B, E, F, I-1, M, R-1, R-2, R-4, S and U, where the building is equipped
throughout with an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code, the length of the dead end corridors shall
not exceed 50 feet (15 240 mm).
3.
A dead-end
corridor shall not be limited in length where the length of the dead-end
corridor is less than 2.5 times the least width of the dead-end
corridor.
(5)
[BE] 1020.5 Air movement in
corridors.
Corridors shall not serve as
supply, return, exhaust, relief or ventilation air ducts.
Exceptions:
1.
Use of a corridor
as a source of makeup air for exhaust systems in rooms that open directly onto
such corridors, including toilet rooms, bathrooms, dressing rooms, smoking
lounges and janitor closets, shall be permitted, provided that each such
corridor is directly supplied with outdoor air at a rate greater than the rate
of makeup air taken from the corridor.
2.
Where located
within a dwelling unit, the use of corridors for conveying return air shall not
be prohibited.
3.
Where located within tenant spaces of 1,000 square feet
(93 m2) or less in area, utilization of corridors
for conveying return air is permitted.
4.
Incidental air
movement from pressurized rooms within healthcare facilities, provided that the
corridor is not the primary source of supply or return air to the room.
(a)
[BE]
1020.5.1 Corridor ceiling. Use of the space between the corridor ceiling
and the floor or roof structure above as a return air plenum is permitted for
one or more of the following conditions:
(i)
The corridor is
not required to be of fire-resistance-rated construction.
(ii)
The corridor is
separated from the plenum by fire-resistance-rated
construction.
(iii)
The air-handling system serving the corridor is shut
down upon activation of the air handling unit smoke detectors required by the
mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
(iv)
The air-handling
system serving the corridor is shut down upon detection of sprinkler waterflow
where the building is equipped throughout with an automatic sprinkler
system.
(v)
The space between the corridor ceiling and the floor or
roof structure above the corridor is used as a component of an approved
engineered smoke control system.
(6)
[BE] 1020.6
Corridor continuity. Fire-resistance-rated corridors shall be continuous
from the point of entry to an exit and shall not be interrupted by intervening
rooms. Where the path of egress travel within a fire-resistance-rated corridor
to the exit includes travel along unenclosed exit access stairways or ramps,
the fire resistance-rating shall be continuous for the length of the stairway
or ramp and for the length of the connecting corridor on the adjacent floor
leading to the exit.
Exceptions:
1.
Foyers, lobbies or
reception rooms constructed as required for corridors shall not be construed as
intervening rooms.
2.
Enclosed elevator lobbies as permitted by item 1 of
paragraph (P)(2)( 1016.2) of this rule shall
not be construed as intervening rooms.
(U)
Section
1021 Egress balconies
(1)
[BE] 1021.1 General.
Balconies used for egress purposes shall conform to the
same requirements as corridors for minimum width, required capacity, headroom,
dead ends and projections.
(2)
[BE] 1021.2
Wall separation.
Exterior egress balconies
shall be separated from the interior of the building by walls and opening
protectives as required for corridors.
Exception:
Separation is not required where the exterior egress
balcony is served by not less than two stairways and a dead-end travel
condition does not require travel past an unprotected opening to reach a
stairway.
(3)
[BE] 1021.3 Openness.
The long side of an egress balcony shall be at least 50
per cent open, and the open area above the guards shall be so
distributed as to minimize the accumulation of smoke or toxic
gases.
(4)
[BE] 1021.4 Location.
Exterior egress balconies shall have a minimum fire
separation distance of 10 feet (3048 mm) measured at right angles from the
exterior edge of the egress balcony to the following:
(a)
Adjacent lot
lines.
(b)
Other portions of the building.
(c)
Other buildings
on the same lot unless the adjacent building exterior walls and openings are
protected in accordance with section 705 of the
building code as listed
in rule
1301:7-7-80
of the Administrative Code based on fire separation distance.
For the purposes of this
paragraph, other portions of the building shall be treated as
separate buildings.
(V)
Section
1022 Exits
(1)
[BE] 1022.1 General.
Exits shall comply with paragraphs
(V)(1022) to (AA)(1027) of this rule and the
applicable requirements of paragraphs (C)(1003)
to (O)(1015) of this rule. An exit shall not
be used for any purpose that interferes with its function as a means of egress.
Once a given level of exit protection is achieved, such level of protection
shall not be reduced until arrival at the exit discharge. Exits shall be
continuous from the point of entry into the exit to the exit
discharge.
(2)
[BE] 1022.2 Exterior exit doors.
Buildings or structures used for human occupancy shall
have not less than one exterior door that meets the requirements
of
paragraph (J)(1)(a)(1010.1.1)
of this rule.
(a)
[BE]
1022.2.1 Detailed requirements.
Exterior
exit doors shall comply with the applicable requirements of
paragraph (J)(1)( 1010.1) of this
rule.
(b)
[BE] 1022.2.2 Arrangement.
Exterior exit doors shall lead directly to the exit
discharge or the public way.
(W)
Section
1023 Interior exit stairways and ramps
(1)
[BE] 1023.1
General.
Interior exit stairways and ramps
serving as an exit component in a means of egress system shall comply with the
requirements of this paragraph. Interior exit stairways and
ramps shall be enclosed and lead directly to the exterior of the building or
shall be extended to the exterior of the building with an exit passageway
conforming to the requirements of paragraph (X)(1024)
of this rule, except as permitted in
paragraph (BB)(1)( 1028.1) of this rule. An
interior exit stairway or ramp shall not be used for any purpose other than as
a means of egress and a circulation path.
(2)
[BE] 1023.2
Construction.
Enclosures for interior exit
stairways and ramps shall be constructed as fire barriers in accordance with
section 707 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code or horizontal assemblies constructed in
accordance with section 711 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code, or both. Interior exit stairway and ramp
enclosures shall have a fire-resistance rating of not less than 2 hours where
connecting four stories or more and not less than 1 hour where connecting less
than four stories. The number of stories connected by the interior exit
stairways or ramps shall include any basements, but not any mezzanines.
Interior exit stairways and ramps shall have a fire-resistance rating not less
than the floor assembly penetrated, but need not exceed 2 hours.
Exceptions:
1.
Interior exit
stairways and ramps in Group I-3 occupancies in accordance with the provisions
of section 408.3.8 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
2.
Interior exit
stairways within an atrium enclosed in accordance with section 404.6 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(3)
[BE] 1023.3
Termination.
Interior exit stairways and
ramps shall terminate at an exit discharge or a public way.
Exception:
A combination of interior exit stairways, interior exit
ramps and exit passageways, constructed in accordance with paragraphs (W)(2)(
1023.2), (W)(3)(a)(1023.3.1) and (X)(1024) of this rule, respectively, and
forming a continuous protected enclosure, shall be permitted to extend an
interior exit stairway or ramp to the exit discharge or a public
way.
(a)
[BE] 1023.3.1 Extension. Where interior exit
stairways and ramps are extended to an exit discharge or a public way by an
exit passageway, the interior exit stairway and ramp shall be separated from
the exit passageway by a fire barrier constructed in accordance with section
707 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code or a horizontal assembly constructed in
accordance with section 711 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code, or both. The fire-resistance rating shall
be not less than that required for the interior exit stairway and ramp. A fire
door assembly complying with section 716.5 of the
building code as
listed in rule
1301:7-7-80
of the Administrative Code shall be installed in the fire barrier to
provide a means of egress from the interior exit stairway and ramp to the exit
passageway. Openings in the fire barrier other than the fire door assembly are
prohibited. Penetrations of the fire barrier are prohibited.
Exceptions:
1.
Penetrations of
the fire barrier in accordance with paragraph (W)(5)( 1023.5)
of this rule shall be permitted.
2.
Separation between
an interior exit stairway or ramp and the exit passageway extension shall not
be required where there are no openings into the exit passageway
extension.
(4)
[BE] 1023.4
Openings.
Interior exit stairway and ramp
opening protectives shall be in accordance with the requirements of section 716
of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
Openings in interior exit stairways and
ramps other than unprotected exterior openings shall be limited to those
necessary for exit access to the enclosure from normally occupied spaces and
for egress from the enclosure.
Elevators shall not open into interior
exit stairways and ramps.
(5)
[BE] 1023.5
Penetrations.
Penetrations into or through
interior exit stairways and ramps are prohibited except for equipment and
ductwork necessary for independent ventilation or pressurization, sprinkler
piping, standpipes, electrical raceway for fire department communication
systems and electrical raceway serving the interior exit stairway and ramp and
terminating at a steel box not exceeding 16 square inches ( 0.010
m2). Such penetrations shall be protected in
accordance with section 714 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code. There shall not be penetrations or
communication openings, whether protected or not, between adjacent interior
exit stairways and ramps.
Exception:
Membrane penetrations shall be permitted on the outside
of the interior exit stairway and ramp. Such penetrations shall be protected in
accordance with section 714.3.2 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(6)
[BE] 1023.6
Ventilation.
Equipment and ductwork for
interior exit stairway and ramp ventilation as permitted by
paragraph (W)(5)( 1023.5)
of this rule shall
comply with one of the following items:
(a)
Such equipment
and ductwork shall be located exterior to the building and shall be directly
connected to the interior exit stairway and ramp by ductwork enclosed in
construction as required for shafts.
(b)
Where such
equipment and ductwork is located within the interior exit stairway and ramp,
the intake air shall be taken directly from the outdoors and the exhaust air
shall be discharged directly to the outdoors, or such air shall be conveyed
through ducts enclosed in construction as required for shafts.
(c)
Where located
within the building, such equipment and ductwork shall be separated from the
remainder of the building, including other mechanical equipment, with
construction as required for shafts.
In each case, openings into the
fire-resistance rated construction shall be limited to those needed for
maintenance and operation and shall be protected by opening protectives in
accordance with section 716 of the building code as listed in rule
1301:7-7-80
of the Administrative Code for shaft enclosures.
The interior exit stairway and ramp
ventilation systems shall be independent of other building ventilation
systems.
(7)
[BE] 1023.7 Interior exit stairway and ramp
exterior walls.
Exterior walls of the
interior exit stairway or ramp shall comply with the requirements of section
705 of the building code as listed in rule
1301:7-7-80
of the Administrative Code for exterior walls. Where nonrated walls or
unprotected openings enclose the exterior of the stairway or ramps and the
walls or openings are exposed by other parts of the building at an angle of
less than 180 degrees (3.14 rad), the building exterior
walls within 10 feet (3048 mm) horizontally of a nonrated wall or unprotected
opening shall have a fire-resistance rating of not less than 1-hour. Openings
within such exterior walls shall be protected by opening protectives having a
fire protection rating of not less than 3/4 hour. This
construction shall extend vertically from the ground to a point 10 feet (3048
mm) above the topmost landing of the stairway or ramp or to the roof line,
whichever is lower.
(8)
[BE] 1023.8 Discharge
identification.
An interior exit stairway
and ramp shall not continue below its level of exit discharge unless an
approved barrier is provided at the level of exit discharge to prevent persons
from unintentionally continuing into levels below. Directional exit signs shall
be provided as specified in paragraph (M(1013) of this
rule.
(9)
[BE] 1023.9 Stairway identification signs.
A sign shall be provided at each floor landing in an
interior exit stairway and ramp connecting more than three stories designating
the floor level, the terminus of the top and bottom of the interior exit
stairway and ramp and the identification of the stairway or ramp. The signage
shall also state the story of, and the direction to, the exit discharge and the
availability of roof access from the interior exit stairway and ramp for the
fire department. The sign shall be located 5 feet (1524 mm) above the floor
landing in a position that is readily visible when the doors are in the open
and closed positions. In addition to the stairway identification sign a floor
level sign in visual characters, raised characters and braille complying with
accessibility requirements as set forth in chapter 11 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code, shall be located at each floor level
landing adjacent to the door leading from the interior exit stairway and ramp
into the corridor to identify the floor level.
(a)
[BE]
1023.9.1 Signage requirements. Stairway identification signs shall
comply with
chapter 11 of the building code as listed in rule
1301:7-7-80
of the Administrative Code and all of the following
requirements:
(i)
The signs shall be a minimum size of 18 inches (457 mm)
by 12 inches (305 mm).
(ii)
The letters designating the identification of the stair
interior exit stairway and ramp shall be not less than 11/2 inches (38 mm) in
height.
(iii)
The number designating the floor level shall be not
less than 5 inches (127 mm) in height and located in the center of the
sign.
(iv)
Other lettering and numbers shall be not less than 1
inch (25 mm) in height.
(v)
Characters and their background shall have a nonglare
finish. Characters shall contrast with their background, with either light
characters on a dark background or dark characters on a light
background.
(vi)
Where signs required by paragraph
(W)(9)(1023.9) of this rule are installed in interior exit
stairways and ramps of buildings subject to paragraph
(Y)(1025) of this rule, the signs shall be made of the same
materials as required by paragraph (Y)(4)( 1025.4) of
this rule.
(10)
[BE]
1023.10 Elevator lobby identification signs.
At landings in interior exit stairways where two or
more doors lead to the floor level, any door with direct access to an enclosed
elevator lobby shall be identified by signage located on the door or directly
adjacent to the door stating "Elevator Lobby." Signage shall be in accordance
with paragraph (W)(9)(a)(1023.9.1), items (iv), (v) and (vi)
of this rule.
(11)
[BE]
1023.11 Smokeproof enclosures.
Where
required by section 403.5.4 or 405.7.2 of the
building code as listed
in rule
1301:7-7-80
of the Administrative Code, interior exit stairways and ramps shall be
smokeproof enclosures in accordance with
paragraph (I)(20)(
909.20)
of rule
1301:7-7-09
of the Administrative Code.(a)
[BE] 1023.11.1 Termination and extension.
A smokeproof enclosure shall terminate at
an exit discharge or a public way. The smokeproof enclosure shall be permitted
to be extended by an exit passageway in accordance with
paragraph (W)(3)( 1023.3)
of this rule. The
exit passageway shall be without openings other than the fire door assembly
required by
paragraph (W)(3)(a)(1023.3.1)
of this
rule and those necessary for egress from the exit passageway. The exit
passageway shall be separated from the remainder of the building by 2-hour fire
barriers constructed in accordance with section 707 of the
building
code as listed in rule
1301:7-7-80
of the Administrative Code or horizontal assemblies constructed in
accordance with section 711 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code, or both.
Exceptions:
1.
Openings in the
exit passageway serving a smokeproof enclosure are permitted where the exit
passageway is protected and pressurized in the same manner as the smokeproof
enclosure, and openings are protected as required for access from other
floors.
2.
The fire barrier separating the smokeproof enclosure
from the exit passageway is not required, provided the exit passageway is
protected and pressurized in the same manner as the smokeproof
enclosure.
3.
A smokeproof enclosure shall be permitted to egress
through areas on the level of exit discharge or vestibules as permitted by
paragraph (BB)(1028) of this
rule.
(b)
[BE] 1023.11.2 Enclosure access.
Access to the stairway or ramp within a
smokeproof enclosure shall be by way of a vestibule or an open exterior
balcony.
Exception:
Access is not required by way of a vestibule or
exterior balcony for stairways and ramps using the pressurization alternative
complying with section 909.20.5 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(X)
Section 1024 Exit passageways
(1)
[BE] 1024.1
Exit passageways.
Exit passageways serving
as an exit component in a means of egress system shall comply with the
requirements of this paragraph. An exit passageway shall not
be used for any purpose other than as a means of egress and a circulation
path.
(2)
[BE] 1024.2 Width.
The
required capacity of exit passageways shall be determined as specified in
paragraph (E)(1)( 1005.1)
of this rule but
the minimum width shall be not less than 44 inches (1118 mm), except that exit
passageways serving an occupant load of less than 50 shall be not less than 36
inches (914 mm) in width. The minimum width or required capacity of exit
passageways shall be unobstructed.
Exception:
Encroachments complying with paragraph
(E)(7)( 1005.7) of this rule.
(3)
[BE] 1024.3
Construction.
Exit passageway enclosures
shall have walls, floors and ceilings of not less than 1-hour fire-resistance
rating, and not less than that required for any connecting interior exit
stairway or ramp. Exit passageways shall be constructed as fire barriers in
accordance with section 707 of the building code as listed in rule
1301:7-7-80
of the Administrative Code or horizontal assemblies constructed in
accordance with section 711 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, or both.
(4)
[BE] 1024.4
Termination.
Exit passageways on the level
of exit discharge shall terminate at an exit discharge. Exit passageways on
other levels shall terminate at an exit.
(5)
[BE] 1024.5
Openings.
Exit passageway opening
protectives shall be in accordance with the requirements of section 716 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
Except as permitted in section 402.8.7
of the building code as listed in rule
1301:7-7-80
of the Administrative Code, openings in exit passageways other than
unprotected exterior openings shall be limited to those necessary for exit
access to the exit passageway from normally occupied spaces and for egress from
the exit passageway.
Where an interior exit stairway or ramp
is extended to an exit discharge or a public way by an exit passageway, the
exit passageway shall comply with paragraph
(W)(3)(a)(1023.3.1) of this rule.
Elevators shall not open into an exit
passageway.
(6)
[BE] 1024.6 Penetrations.
Penetrations into or through an exit passageway are
prohibited except for equipment and ductwork necessary for independent
pressurization, sprinkler piping, standpipes, electrical raceway for fire
department communication and electrical raceway serving the exit passageway and
terminating at a steel box not exceeding 16 square inches ( 0.010
m2). Such penetrations shall be protected in
accordance with section 714 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code. There shall not be penetrations or
communicating openings, whether protected or not, between adjacent exit
passageways.
Exception:
Membrane penetrations shall be permitted on the outside
of the exit passageway. Such penetrations shall be protected in accordance with
section 714.3.2 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(7)
[BE] 1024.7
Ventilation.
Equipment and ductwork for
exit passageway ventilation as permitted by
paragraph (X)(6)(
1024.6)
of this rule shall comply with one of the
following:
(a)
The equipment and ductwork shall be located exterior to the
building and shall be directly connected to the exit passageway by ductwork
enclosed in construction as required for shafts.
(b)
Where the
equipment and ductwork is located within the exit passageway, the intake air
shall be taken directly from the outdoors and the exhaust air shall be
discharged directly to the outdoors, or the air shall be conveyed through ducts
enclosed in construction as required for shafts.
(c)
Where located
within the building, the equipment and ductwork shall be separated from the
remainder of the building, including other mechanical equipment, with
construction as required for shafts.
In each case, openings into the
fire-resistance-rated construction shall be limited to those needed for
maintenance and operation and shall be protected by opening protectives in
accordance with section 716 of the building code as listed in rule
1301:7-7-80
of the Administrative Code for shaft enclosures.
Exit passageway ventilation systems
shall be independent of other building ventilation systems.
(Y)
Section 1025 Luminous egress path
markings
(1)
[BE] 1025.1 General.
Approved luminous egress path markings delineating the exit
path shall be provided in high-rise buildings of Group A, B, E, I, M and R-1
occupancies in accordance with
paragraphs (Y)(1)( 1025.1)
to (Y)(5)( 1025.5)
of this rule.
Exception:
Luminous egress path markings shall not be required on
the level of exit discharge in lobbies that serve as part of the exit path in
accordance with paragraph (BB)(1)( 1028.1) of this
rule, exception 1.
(2)
[BE] 1025.2
Markings within exit components.
Egress
path markings shall be provided in interior exit stairways, interior exit ramps
and exit passageways, in accordance with
paragraphs
(Y)(2)(a)(1025.2.1)
to (Y)(2)(f)(1025.2.6)
of this
rule.(a)
[BE] 1025.2.1 Steps.
A
solid and continuous stripe shall be applied to the horizontal leading edge of
each step and shall extend for the full length of the step. Outlining stripes
shall have a minimum horizontal width of 1 inch (25 mm) and a maximum width of
2 inches (51 mm). The leading edge of the stripe shall be placed not more than
1/2 inch ( 12.7 mm) from the leading edge of the step and the stripe shall not
overlap the leading edge of the step by not more than 1/2 inch ( 12.7 mm) down
the vertical face of the step.
Exception:
The minimum width of 1 inch (25 mm) shall not apply to
outlining stripes listed in accordance with UL 1994 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
[BE]
1025.2.2 Landings.
The leading edge of
landings shall be marked with a stripe consistent with the dimensional
requirements for steps.
(c)
[BE] 1025.2.3 Handrails.
Handrails and handrail extensions shall be marked with
a solid and continuous stripe having a minimum width of 1 inch (25 mm). The
stripe shall be placed on the top surface of the handrail for the entire length
of the handrail, including extensions and newel post caps. Where handrails or
handrail extensions bend or turn corners, the stripe shall not have a gap of
more than 4 inches (102 mm).
Exception:
The minimum width of 1 inch (25 mm) shall not apply to
outlining stripes listed in accordance with UL 1994 as listed in rule
1301:7-7-80
of the Administrative Code.
(d)
[BE]
1025.2.4 Perimeter demarcation lines.
Stair landings and other floor areas within interior exit
stairways, interior exit ramps and exit passageways, with the exception of the
sides of steps, shall be provided with solid and continuous demarcation lines
on the floor or on the walls or a combination of both. The stripes shall be 1
to 2 inches (25 mm to 51 mm) wide with interruptions not exceeding 4 inches
(102 mm).
Exception:
The minimum width of 1 inch (25 mm) shall not apply to
outlining stripes listed in accordance with UL 1994 as listed in rule
1301:7-7-80
of the Administrative Code.
(i)
[BE]
1025.2.4.1 Floor mounted demarcation lines. Perimeter demarcation lines
shall be placed within 4 inches (102 mm) of the wall and shall extend to within
2 inches (51 mm) of the markings on the leading edge of landings. The
demarcation lines shall continue across the floor in front of all doors.
Exception:
Demarcation lines shall not extend in front of exit
discharge doors that lead out of an exit and through which occupants must
travel to complete the exit path.
(ii)
[BE]
1025.2.4.2 Wall-mounted demarcation lines. Perimeter demarcation lines
shall be placed on the wall with the bottom edge of the stripe not more than 4
inches (102 mm) above the finished floor. At the top or bottom of the stairs,
demarcation lines shall drop vertically to the floor within 2 inches (51 mm) of
the step or landing edge. Demarcation lines on walls shall transition
vertically to the floor and then extend across the floor where a line on the
floor is the only practical method of outlining the path. Where the wall line
is broken by a door, demarcation lines on walls shall continue across the face
of the door or transition to the floor and extend across the floor in front of
such door.
Exception:
Demarcation lines shall not extend in front of exit
discharge doors that lead out of an exit and through which occupants must
travel to complete the exit path.
(iii)
[BE]
1025.2.4.3 Transition. Where a wall-mounted demarcation line transitions
to a floor-mounted demarcation line, or vice versa, the wall-mounted
demarcation line shall drop vertically to the floor to meet a complimentary
extension of the floor-mounted demarcation line, thus forming a continuous
marking.
(e)
[BE] 1025.2.5 Obstacles.
Obstacles at or below 6 feet 6 inches (1981 mm) in
height and projecting more than 4 inches (102 mm) into the egress path shall be
outlined with markings not less than 1 inch (25 mm) in width comprised of a
pattern of alternating equal bands, of luminescent luminous material and black,
with the alternating bands not more than 2 inches (51 mm) thick and angled at
45 degrees ( 0.79 rad). Obstacles shall include, but are not limited to,
standpipes, hose cabinets, wall projections and restricted height areas.
However, such markings shall not conceal any required information or indicators
including, but not limited to instructions to occupants for the use of
standpipes.
(f)
[BE] 1025.2.6 Doors within the exit path.
Doors through which occupants must pass in order to
complete the exit path shall be provided with markings complying with
paragraphs (Y)(2)(f)(i)(1025.2.6.1)
to
(Y)(2)(f)(iii)(1025.2.6.3)
of this rule.
(i)
[BE]
1025.2.6.1 Emergency exit symbol. The doors shall be identified by a
low-location luminous emergency exit symbol complying with NFPA 170 as
listed in rule
1301:7-7-80
of the Administrative Code. The exit symbol shall be not less than 4
inches (102 mm) in height and shall be mounted on the door, centered
horizontally, with the top of the symbol not higher than 18 inches (457 mm)
above the finished floor.
(ii)
[BE]
1025.2.6.2 Door hardware markings. Door hardware shall be marked with
not less than 16 square inches (406 mm2) of luminous
material. This marking shall be located behind, immediately adjacent to or on
the door handle or escutcheon. Where a panic bar is installed, such material
shall be not less than 1 inch (25 mm) wide for the entire length of the
actuating bar or touchpad.
(iii)
[BE]
1025.2.6.3 Door frame markings. The top and sides of the door frame
shall be marked with a solid and continuous 1-inch- to 2-inch-wide (25 mm to 51
mm) stripe. Where the door molding does not provide sufficient flat surface on
which to locate the stripe, the stripe shall be permitted to be located on the
wall surrounding the frame.
(3)
[BE] 1025.3
Uniformity. Placement and dimensions of markings shall be consistent and
uniform throughout the same enclosure.
(4)
[BE] 1025.4
Self-luminous and photoluminescent.
Luminous egress path markings shall be permitted to be made
of any material, including paint, provided that an electrical charge is not
required to maintain the required luminance. Such materials shall include, but
not be limited to, self-luminous materials and photoluminescent materials.
Materials shall comply with either of the following standards:
(a)
UL 1994
as listed in rule
1301:7-7-80
of the Administrative Code, or
(b)
ASTM E 2072
as listed in rule
1301:7-7-80
of the Administrative Code, except that the charging source shall be 1
footcandle (11 lux) of fluorescent illumination for 60 minutes, and the minimum
luminance shall be 30 milicandelas per square meter at 10 minutes and 5
milicandelas per square meter after 90 minutes.
(5)
[BE] 1025.5
Illumination.
Where photoluminescent exit
path markings are installed, they shall be provided with not less than 1
footcandle (11 lux) of illumination for not less than 60 minutes prior to
periods when the building is occupied and continuously during the building
occupancy.
(Z)
Section 1026 Horizontal exits
(1)
[BE] 1026.1
Horizontal exits.
Horizontal exits serving
as an exit in a means of egress system shall comply with the requirements of
this
paragraph. A horizontal exit shall not serve as the only
exit from a portion of a building, and where two or more exits are required,
not more than one-half of the total number of exits or total exit minimum width
or required capacity shall be horizontal exits.
Exceptions:
1.
Horizontal exits
are permitted to comprise two-thirds of the required exits from any building or
floor area for occupancies in Group I-2.
2.
Horizontal exits
are permitted to comprise 100 per cent of the exits required
for occupancies in Group I-3. Not less than 6 square feet ( 0.6
m2) of accessible space per occupant shall be
provided on each side of the horizontal exit for the total number of people in
adjoining compartments.
(2)
[BE] 1026.2
Separation.
The separation between
buildings or refuge areas connected by a horizontal exit shall be provided by a
fire wall complying with section 706 of the
building code as listed in
rule
1301:7-7-80
of the Administrative Code; or by a fire barrier complying with
section 707 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code or a horizontal assembly complying with
section 711 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code, or both. The minimum fire-resistance
rating of the separation shall be 2 hours. Opening protectives in horizontal
exits shall also comply with section 716 of the
building code as listed
in rule
1301:7-7-80
of the Administrative Code. Duct and air transfer openings in a fire
wall or fire barrier that serves as a horizontal exit shall also comply with
section 717 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code. The horizontal exit separation shall
extend vertically through all levels of the building unless floor assemblies
have a fire resistance rating of not less than 2 hours with no unprotected
openings.
Exception:
A fire-resistance rating is not required at horizontal
exits between a building area and an above-grade pedestrian walkway constructed
in accordance with section 3104 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, provided that the distance between
connected buildings is more than 20 feet (6096 mm).
Horizontal exits constructed as fire
barriers shall be continuous from exterior wall to exterior wall so as to
divide completely the floor served by the horizontal exit.
(3)
[BE] 1026.3 Opening protectives.
Fire doors in horizontal exits shall be self-closing or
automatic-closing when activated by a smoke detector in accordance with section
716.5.9.3 of the building code as listed in rule
1301:7-7-80
of the Administrative Code. Doors, where located in a cross-corridor
condition, shall be automatic-closing by activation of a smoke detector
installed in accordance with section 716.5.9.3 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code.
(4)
[BE] 1026.4
Refuge area. The refuge area of a horizontal exit shall be a space
occupied by the same tenant or a public area and each such refuge area shall be
adequate to accommodate the original occupant load of the refuge area plus the
occupant load anticipated from the adjoining compartment. The anticipated
occupant load from the adjoining compartment shall be based on the capacity of
the horizontal exit doors entering the refuge area.
(a)
[BE]
1026.4.1 Capacity.
The capacity of the
refuge area shall be computed based on a net floor area allowance of 3 square
feet ( 0.2787 m2) for each occupant to be
accommodated therein.
Exceptions:
The net floor area allowable per occupant shall be as
follows for the indicated occupancies:
1.
Six square feet (
0.6 m2) per occupant for occupancies in Group
I-3.
2.
Fifteen square feet ( 1.4
m2) per occupant for ambulatory occupancies in Group
I-2.
3.
Thirty square feet ( 2.8 m2)
per occupant for nonambulatory occupancies in Group
I-2.
(b)
[BE] 1026.4.2 Number of exits.
The refuge area into which a horizontal exit leads
shall be provided with exits adequate to meet the occupant requirements of this
rule, but not including the added occupant load imposed by
persons entering it through horizontal exits from other areas. Not less than
one refuge area exit shall lead directly to the exterior or to an interior exit
stairway or ramp.
Exception:
The adjoining compartment shall not be required to have
a stairway or door leading directly outside, provided the refuge area into
which a horizontal exit leads has stairways or doors leading directly outside
and are so arranged that egress shall not require the occupants to return
through the compartment from which egress
originates.
(AA)
Section
1027 Exterior exit stairways and ramps
(1)
[BE] 1027.1
Exterior exit stairways and ramps.
Exterior exit stairways and ramps serving as an element of a
required means of egress shall comply with this
paragraph.
(2)
[BE] 1027.2
Use in a means of egress.
Exterior exit
stairways shall not be used as an element of a required means of egress for
Group I-2, I-4 and daycare facilities in Group E occupancies.
For occupancies in other than Group I-2, I-4 and daycare facilities in
Group E occupancies, exterior exit stairways and ramps shall be
permitted as an element of a required means of egress for buildings not
exceeding six stories above grade plane or that are not high-rise
buildings.
(3)
[BE] 1027.3 Open side.
Exterior exit stairways and ramps serving as an element of a
required means of egress shall be open on not less than one side, except for
required structural columns, beams, handrails and guards. An open side shall
have not less than 35 square feet ( 3.3 m2) of
aggregate open area adjacent to each floor level and the level of each
intermediate landing. The required open area shall be located not less than 42
inches (1067 mm) above the adjacent floor or landing level.
(4)
[BE] 1027.4
Side yards.
The open areas adjoining
exterior exit stairways or ramps shall be either yards, courts or public ways;
the remaining sides are permitted to be enclosed by the exterior walls of the
building.
(5)
[BE] 1027.5 Location.
Exterior exit stairways and ramps shall have a minimum fire
separation distance of 10 feet (3048 mm) measured at right angles from the
exterior edge of the stairway or ramps, including landings, to:
(a)
Adjacent lot
lines.
(b)
Other portions of the building.
(c)
Other buildings
on the same lot unless the adjacent building exterior walls and openings are
protected in accordance with section 705 of the
building code as listed
in rule
1301:7-7-80
of the Administrative Code based on fire separation distance.
For the purposes of this
paragraph, other portions of the building shall be treated as
separate buildings.
(6)
[BE] 1027.6
Exterior exit stairway and ramp protection. Exterior exit stairways and
ramps shall be separated from the interior of the building as required in
paragraph (W)(2)( 1023.2)
of this rule.
Openings shall be limited to those necessary for egress from normally
occupied spaces. Where a vertical plane projecting from the edge of an exterior
exit stairway or ramp and landings is exposed by other parts of the building at
an angle of less than 180 degrees (3.14 rad), the exterior wall
shall be rated in accordance with
paragraph (W)(7)( 1023.7)
of this rule.
Exceptions:
1.
Separation from
the interior of the building is not required for occupancies, other than those
in Group R-1 or R-2, in buildings that are not more than two stories above
grade plane where a level of exit discharge serving such occupancies is the
first story above grade plane.
2.
Separation from
the interior of the building is not required where the exterior stairway or
ramp is served by an exterior ramp or balcony that connects two remote exterior
stairways or other approved exits, with a perimeter that is not less than 50
per cent open. To be considered open, the opening shall be not
less than 50 per cent of the height of the enclosing wall,
with the top of the openings not less than 7 feet (2134 mm) above the top of
the balcony.
3.
Separation from the open-ended corridor of the building
is not required for exterior exit stairways or ramps, provided that items
3.1
to3.5 are met:
3.1.
The building, including open-ended corridors, stairways
and ramps, shall be equipped throughout with an automatic sprinkler system in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) or
(C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code.
3.2.
The open-ended
corridors comply with paragraph (T)(1020) of this
rule.
3.3.
The open-ended corridors are connected on each end to
an exterior exit stairway or ramp complying with paragraph
(AA)(1027) of this rule.
3.4.
The exterior
walls and openings adjacent to the exterior exit stairway or ramp comply with
paragraph (W)(7)( 1023.7) of this
rule.
3.5.
At any location in an open-ended corridor where a
change of direction exceeding 45 degrees ( 0.79 rad) occurs, a clear opening of
not less than 35 square feet ( 3.3 m2) or an
exterior stairway or ramp shall be provided. Where clear openings are provided,
they shall be located so as to minimize the accumulation of smoke or toxic
gases.
(BB)
Section
1028 Exit discharge
(1)
[BE] 1028.1 General. Exits shall discharge
directly to the exterior of the building. The exit discharge shall be at grade
or shall provide a direct path of egress travel to grade. The exit discharge
shall not reenter a building. The combined use of exceptions 1 and 2 below
shall not exceed 50
per cent of the number and minimum width
or required capacity of the required exits.
Exceptions:
1.
Not more than 50
per cent of the number and minimum width or required capacity
of interior exit stairways and ramps is permitted to egress through areas on
the level of discharge provided all of the following conditions are met:
1.1
Discharge of
interior exit stairways and ramps shall be provided with a free and
unobstructed path of travel to an exterior exit door and such exit is readily
visible and identifiable from the point of termination of the
enclosure.
1.2
The entire area of the level of exit discharge is
separated from areas below by construction conforming to the fire-resistance
rating for the enclosure.
1.3
The egress path from the interior stairway and ramp on
the level of exit discharge is protected throughout by an approved automatic
sprinkler system. Portions of the level of exit discharge with access to the
egress path shall either be equipped throughout with an automatic sprinkler
system installed in accordance with paragraph
(C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code or separated from the egress path in
accordance with the requirements for the enclosure of interior exit stairways
or ramps.
1.4.
Where a required interior exit stairway or ramp and an
exit access stairway or ramp serve the same floor level and terminate at the
same level of exit discharge, the termination of the exit access stairway or
ramp and the exit discharge door of the interior exit stairway or ramp shall be
separated by a distance of not less than 30 feet (9144 mm) or not less than
one-fourth the length of the maximum overall diagonal dimension of the
building, whichever is less. The distance shall be measured in a straight line
between the exit discharge door from the interior exit stairway or ramp and the
last tread of the exit access stairway or termination of slope of the exit
access ramp.
2.
Not more than 50
per cent of the
number and minimum width or required capacity of the interior exit stairways
and ramps is permitted to egress through a vestibule provided all of the
following conditions are met:
2.1
The entire area of the vestibule is separated from
areas below by construction conforming to the fire-resistance rating of the
interior exit stairway or ramp enclosure.
2.2
The depth from
the exterior of the building is not greater than 10 feet (3048 mm) and the
length is not greater than 30 feet (9144 mm).
2.3
The area is
separated from the remainder of the level of exit discharge by a fire partition
constructed in accordance with section 708 of the
building code as
listed in rule
1301:7-7-80
of the Administrative Code.
Exception:
The maximum transmitted temperature rise is not
required.
2.4
The area is used only for means of egress and exits
directly to the outside.
3.
Horizontal exits
complying with paragraph (Z)(1026) of this
rule shall not be required to discharge directly to the exterior of
the building.
(2)
[BE] 1028.2 Exit discharge width or
capacity.
The minimum width or required
capacity of the exit discharge shall be not less than the minimum width or
required capacity of the exits being served.
(3)
[BE] 1028.3
Exit discharge components.
Exit discharge
components shall be sufficiently open to the exterior so as to minimize the
accumulation of smoke and toxic gases.
(4)
[BE] 1028.4
Egress courts.
Egress courts serving as a
portion of the exit discharge in the means of egress system shall comply with
the requirements of
paragraphs (BB)(4)(a)(1028.4.1) and
(BB)(4)(b)(1028.4.2)
of this rule.
(a)
[BE]
1028.4.1 Width or capacity.
The required
capacity of egress courts shall be determined as specified in
paragraph (E)(1)( 1005.1)
of this rule, but
the minimum width shall be not less than 44 inches (1118 mm), except as
specified herein. Egress courts serving Group R-3 and U occupancies shall be
not less than 36 inches (914 mm) in width. The required capacity and width of
egress courts shall be unobstructed to a height of 7 feet (2134 mm).
Exception:
Encroachments complying with paragraph
(E)(7)( 1005.7) of this rule.
Where an egress court exceeds the
minimum required width and the width of such egress court is then reduced along
the path of exit travel, the reduction in width shall be gradual. The
transition in width shall be affected by a guard not less than 36 inches (914
mm) in height and shall not create an angle of more than 30 degrees ( 0.52 rad)
with respect to the axis of the egress court along the path of egress travel.
The width of the egress court shall not be less than the required
capacity.
(b)
[BE] 1028.4.2 Construction and
openings.
Where an egress court serving a
building or portion thereof is less than 10 feet (3048 mm) in width, the egress
court walls shall have not less than 1-hour fire-resistance rated construction
for a distance of 10 feet (3048 mm) above the floor of the egress court.
Openings within such walls shall be protected by opening protectives having a
fire protection rating of not less than 3/4 hour.
Exceptions:
1.
Egress courts
serving an occupant load of less than 10.
2.
Egress courts
serving Group R-3.
(5)
[BE] 1028.5
Access to a public way.
The exit discharge
shall provide a direct and unobstructed access to a public way.
Exception:
Where access to a public way cannot be provided, a safe
dispersal area shall be provided where all of the following are
met:
1.
The area shall be of a size to accommodate not less than 5 square feet ( 0.46
m2) for each person.
2.
The area shall be
located on the same lot not less than 50 feet (15 240 mm) away from the
building requiring egress.
3.
The area shall be permanently maintained and identified
as a safe dispersal area.
4.
The area shall be provided with a safe and unobstructed
path of travel from the building.
(CC)
Section
1029 Assembly
(1)
[BE] 1029.1 General. A room or space used
for assembly purposes that contains seats, tables, displays, equipment or other
material shall comply with this
paragraph.
(a)
[BE]
1029.1.1 Bleachers. Bleachers, grandstands and folding and telescopic
seating, that are not building elements, shall comply with ICC 300
as
listed in rule
1301:7-7-80
of the Administrative Code.
(i)
[BE]
1029.1.1.1 Spaces under grandstands and bleachers. Where spaces under
grandstands or bleachers are used for purposes other than ticket booths less
than 100 square feet (9.29
m2) and toilet rooms, such spaces shall be separated
by fire barriers complying with section 707 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code and horizontal assemblies complying with
section 711 of the building code as listed in rule
1301:7-7-80
of the Administrative Code with not less than 1-hour
fire-resistance-rated construction.
(2)
[BE] 1029.2
Assembly main exit.
A building, room or
space used for assembly purposes that has an occupant load of greater than 300
and is provided with a main exit, that main exit shall be of sufficient
capacity to accommodate not less than one-half of the occupant load, but such
capacity shall not be not less than the total required capacity of all means of
egress leading to the exit. Where the building is classified as a Group A
occupancy, the main exit shall front on not less than one street or an
unoccupied space of not less than 10 feet (3048 mm) in width that adjoins a
street or public way. In a building, room or space used for assembly purposes
where there is not a well-defined main exit or where multiple main exits are
provided, exits shall be permitted to be distributed around the perimeter of
the building provided that the total capacity of egress is not less than 100
per cent of the required capacity.
(3)
[BE] 1029.3
Assembly other exits.
In addition to
having access to a main exit, each level in a building used for assembly
purposes having an occupant load greater than 300 and provided with a main
exit, shall be provided with additional means of egress that shall provide an
egress capacity for not less than one-half of the total occupant load served by
that level and shall comply with paragraph (G)(1)( 1007.1)
of this rule. In a building used for assembly purposes where
there is not a well-defined main exit or where multiple main exits are
provided, exits for each level shall be permitted to be distributed around the
perimeter of the building, provided that the total width of egress is not less
than 100 per cent of the required width.
(4)
[BE] 1029.4
Foyers and lobbies.
In Group A-1
occupancies, where persons are admitted to the building at times when seats are
not available, such persons shall be allowed to wait in a lobby or similar
space, provided such lobby or similar space shall not encroach upon the minimum
width or required capacity of the means of egress. Such foyer, if not directly
connected to a public street by all the main entrances or exits, shall have a
straight and unobstructed corridor or path of travel to every such main
entrance or exit.
(5)
[BE] 1029.5 Interior balcony and gallery means of
egress.
For balconies, galleries or press
boxes having a seating capacity of 50 or more located in a building, room or
space used for assembly purposes, not less than two means of egress shall be
provided, with one from each side of every balcony, gallery or press
box.
(6)
[BE] 1029.6 Capacity of aisle for assembly.
The required capacity of aisles shall be not less than
that determined in accordance with
paragraph
(CC)(6)(a)(1029.6.1)
of this rule where smoke-protected
assembly seating is not provided and with
paragraph
(CC)(6)(b)(1029.6.2) or (CC)(6)(c)(1029.6.3)
of this rule
where smoke-protected assembly seating is provided.
(a)
[BE]
1029.6.1 Without smoke protection. The required capacity in inches (mm)
of the aisles for assembly seating without smoke protection shall be not less
than the occupant load served by the egress element in accordance with all of
the following, as applicable:
(i)
Not less than 0.3 inch ( 7.6 mm) of aisle capacity for
each occupant served shall be provided on stepped aisles having riser heights 7
inches (178 mm) or less and tread depths 11 inches (279 mm) or greater,
measured horizontally between tread nosings.
(ii)
Not less than
0.005 inch ( 0.127 mm) of additional aisle capacity for each occupant shall be
provided for each 0.10 inch ( 2.5 mm) of riser height above 7 inches (178
mm).
(iii)
Where egress requires stepped aisle descent, not less
than 0.075 inch ( 1.9 mm) of additional aisle capacity for each occupant shall
be provided on those portions of aisle capacity having no handrail within a
horizontal distance of 30 inches (762 mm).
(iv)
Ramped aisles,
where slopes are steeper than one unit vertical in 12 units horizontal
(8-per cent slope), shall have not less than 0.22 inch ( 5.6
mm) of clear aisle capacity for each occupant served. Level or ramped aisles,
where slopes are not steeper than one unit vertical in 12 units horizontal
(8-per cent slope), shall have not less than 0.20 inch ( 5.1
mm) of clear aisle capacity for each occupant served.
(b)
[BE] 1029.6.2 Smoke-protected assembly seating.
The required capacity in inches (mm) of the aisle for smoke-protected assembly
seating shall be not less than the occupant load served by the egress element
multiplied by the appropriate factor in Table 1029.6.2
of this
rule. The total number of seats specified shall be those within the
space exposed to the same smoke-protected environment. Interpolation is
permitted between the specific values shown. A life safety evaluation,
complying with
section 12.4.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code or section 13.4.1 of NFPA 101
as
listed in rule
1301:7-7-80
of the Administrative Code or other approved method, shall be done for
a facility utilizing the reduced width requirements of Table 1029.6.2
of this rule for smoke-protected assembly seating.
Exception:
For outdoor smoke-protected assembly seating with an
occupant load not greater than 18,000, the required capacity in inches (mm)
shall be determined using the factors in paragraph
(CC)(6)(c)(1029.6.3) of this rule.
[BE] Table
1029.6.2
Capacity for aisles for
smoke-protected assembly
Total number of seats in
the smoke-protected assembly seating
|
Inches of capacity per
seat served
|
Stepped aisles with
handrails within 30 inches
|
Stepped aisles without
handrails within 30 inches
|
Level aisles or ramped
aisles not steeper than 1 in 10 in slope
|
Ramped aisles steeper
than 1 in 10 in slope
|
Equal to or less than
5,000
|
0.200
|
0.250
|
0.150
|
0.165
|
10,000
|
0.130
|
0.163
|
0.100
|
0.110
|
15,000
|
0.096
|
0.120
|
0.070
|
0.077
|
20,000
|
0.076
|
0.095
|
0.056
|
0.062
|
Equal to or greater than
25,000
|
0.060
|
0.075
|
0.044
|
0.048
|
For SI: 1 inch = 25.4 mm.
(i)
[BE]
1029.6.2.1 Smoke control. Aisles and aisle accessways serving a
smoke-protected assembly seating area shall be provided with a smoke control
system complying with paragraph (I)(909) of rule
1301:7-7-09
of the Administrative Code or natural ventilation designed to maintain
the smoke level not less than 6 feet (1829 mm) above the floor of the means of
egress.
(ii)
[BE] 1029.6.2.2 Roof height. A
smoke-protected assembly seating area with a roof shall have the lowest portion
of the roof deck not less than 15 feet (4572 mm) above the highest aisle or
aisle accessway.
Exception:
A roof canopy in an outdoor stadium shall be permitted
to be less than 15 feet (4572 mm) above the highest aisle or aisle accessway
provided that there are no objects less than 80 inches (2032 mm) above the
highest aisle or aisle accessway.
(iii)
[BE]
1029.6.2.3 Automatic sprinklers. Enclosed areas with walls and ceilings
in buildings or structures containing smoke-protected assembly seating shall be
protected with an approved automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1)
of rule
1301:7-7-09
of the Administrative Code.
Exceptions:
1.
The floor area
used for the contests, performances or entertainment provided the roof
construction is more than 50 feet (15 240 mm) above the floor level and the use
is restricted to low fire hazard uses.
2.
Press boxes and
storage facilities less than 1,000 square feet (93
m2) in area.
3.
Outdoor seating
facilities where seating and the means of egress in the seating area are
essentially open to the outside.
(c)
[BE]
1029.6.3 Outdoor smoke-protected assembly seating. The required capacity
in inches (mm) of aisles shall be not less than the total occupant load served
by the egress element multiplied by 0.08 ( 2.0 mm) where egress is by stepped
aisle and multiplied by 0.06 (1.52 mm) where egress is by
level aisles and ramped aisles.
Exception:
The required capacity in inches (mm) of aisles shall be
permitted to comply with paragraph (CC)(6)(b)(1029.6.2)
of this rule for the number of seats in the outdoor
smoke-protected assembly seating where paragraph
(CC)(6)(b)(1029.6.2) of this rule permits less
capacity.
(7)
[BE] 1029.7
Travel distance.
Exits and aisles shall be
so located that the travel distance to an exit door shall be not greater than
200 feet (60 960 mm) measured along the line of travel in nonsprinklered
buildings. Travel distance shall be not more than 250 feet (76 200 mm) in
sprinklered buildings. Where aisles are provided for seating, the distance
shall be measured along the aisles and aisle accessways without travel over or
on the seats.
Exceptions:
1.
Smoke-protected
assembly seating: The travel distance from each seat to the nearest entrance to
a vomitory or concourse shall not exceed 200 feet (60 960 mm). The travel
distance from the entrance to the vomitory or concourse to a stairway, ramp or
walk on the exterior of the building shall not exceed 200 feet (60 960
mm).
2.
Open air seating: The travel distance from each seat to
the building exterior shall not exceed 400 feet (122 m). The travel distance
shall not be limited in facilities of Type I or II
construction.
(8)
[BE] 1029.8 Common path of egress
travel.
The common path of egress travel
shall not exceed 30 feet (9144 mm) from any seat to a point where an occupant
has a choice of two paths of egress travel to two exits.
Exceptions:
1.
For areas serving
less than 50 occupants, the common path of egress travel shall not exceed 75
feet (22 860 mm).
2.
For smoke-protected assembly seating, the common path
of egress travel shall not exceed 50 feet (15 240 mm).
(a)
[BE]
1029.8.1 Path through adjacent row. Where one of the two paths of travel
is across the aisle through a row of seats to another aisle, there shall be not
more than 24 seats between the two aisles, and the minimum clear width between
rows for the row between the two aisles shall be 12 inches (305 mm) plus 0.6
inch ( 15.2 mm) for each additional seat above seven in the row between
aisles.
Exception:
For smoke-protected assembly seating there shall be not
more than 40 seats between the two aisles and the minimum clear width shall be
12 inches (305 mm) plus 0.3 inch ( 7.6 mm) for each additional
seat.
(9)
[BE] 1029.9
Assembly aisles are required. Every occupied portion of any building,
room or space used for assembly purposes that contains seats, tables, displays,
similar fixtures or equipment shall be provided with aisles leading to exits or
exit access doorways in accordance with this
paragraph.
(a)
[BE]
1029.9.1 Minimum aisle width.
The minimum
clear width for aisles shall comply with one of the following:
(i)
Forty-eight
inches (1219 mm) for stepped aisles having seating on each side.
Exception:
Thirty-six inches (914 mm) where the stepped aisles
serve less than 50 seats.
(ii)
Thirty-six
inches (914 mm) for stepped aisles having seating on only one side.
Exception:
Twenty-three inches (584 mm) between a stepped aisle
handrail and seating where a stepped aisle does not serve more than five rows
on one side.
(iii)
Twenty-three inches (584 mm) between a stepped aisle
handrail or guard and seating where the stepped aisle is subdivided by a
mid-aisle handrail.
(iv)
Forty-two inches (1067 mm) for level or ramped aisles
having seating on both sides.
Exceptions:
1.
Thirty-six inches
(914 mm) where the aisle serves less than 50 seats.
2.
Thirty inches (762
mm) where the aisle does not serve more than 14 seats.
(v)
Thirty-six inches (914 mm) for level or ramped aisles having
seating on only one side.
Exception:
For other than ramped aisles that serve as part of an
accessible route, 30 inches (762 mm) where the ramped aisle does not serve more
than 14 seats.
(b)
[BE]
1029.9.2 Aisle catchment area.
The aisle
shall provide sufficient capacity for the number of persons accommodated by the
catchment area served by the aisle. The catchment area served by an aisle is
that portion of the total space served by that section of the aisle. In
establishing catchment areas, the assumption shall be made that there is a
balanced use of all means of egress, with the number of persons in proportion
to egress capacity.
(c)
[BE] 1029.9.3 Converging aisles.
Where aisles converge to form a single path of egress
travel, the required capacity of that path shall be not less than the combined
required capacity of the converging aisles.
(d)
[BE]
1029.9.4 Uniform width and capacity.
Those
portions of aisles, where egress is possible in either of two directions, shall
be uniform in minimum width or required capacity.
(e)
[BE]
1029.9.5 Dead end aisles.
Each end of an
aisle shall be continuous to a cross aisle, foyer, doorway, vomitory, concourse
or stairway in accordance with
paragraph (CC)(9)(g)(1029.9.7)
of this rule having access to an exit.
Exceptions:
1.
Dead-end aisles
shall not be greater than 20 feet (6096 mm) in length.
2.
Dead-end aisles
longer than 16 rows are permitted where seats beyond the
16th row dead-end aisle are not more than 24 seats
from another aisle, measured along a row of seats having a minimum clear width
of 12 inches (305 mm) plus 0.6 inch ( 15.2 mm) for each additional seat above
seven in the row where seats have backrests or beyond 10 where seats are
without backrests in the row.
3.
For
smoke-protected assembly seating, the dead-end aisle length of vertical aisles
shall not exceed a distance of 21 rows.
4.
For
smoke-protected assembly seating, a longer dead-end aisle is permitted where
seats beyond the 21-row dead-end aisle are not more than 40 seats from another
aisle, measured along a row of seats having an aisle accessway with a minimum
clear width of 12 inches (305 mm) plus 0.3 inch ( 7.6 mm) for each additional
seat above seven in the row where seats have backrests or beyond 10 where seats
are without backrests in the row.
(f)
[BE]
1029.9.6 Aisle measurement.
The clear
width for aisles shall be measured to walls, edges of seating and tread edges
except for permitted projections.
Exception:
The clear width of aisles adjacent to seating at tables
shall be permitted to be measured in accordance with paragraph
(CC)(12)(a)(1029.12.1) of this rule.
(i)
[BE]
1029.9.6.1 Assembly aisle obstructions. There shall not be obstructions
in the minimum width or required capacity of aisles.
Exception:
Handrails are permitted to project into the required
width of stepped aisles and ramped aisles in accordance with
paragraph (N)(8)( 1014.8) of this
rule.
(g)
[BE]
1029.9.7 Stairways connecting to stepped aisles.
A stairway that connects a stepped aisle to a cross
aisle or concourse shall be permitted to comply with the assembly aisle walking
surface requirements of paragraph (CC)(13)( 1029.13)
of this rule. Transitions between stairways and stepped aisles
shall comply with paragraph (CC) (10)( 1029.10) of this
rule.
(h)
[BE] 1029.9.8 Stairways connecting to
vomitories. A stairway that connects a vomitory to a cross aisle or
concourse shall be permitted to comply with the assembly aisle walking surface
requirements of paragraph (CC)(13)( 1029.13) of this
rule. Transitions between stairways and stepped aisles shall comply
with paragraph (CC)(10)( 1029.10) of this
rule.
(10)
[BE] 1029.10 Transitions. Transitions
between stairways and stepped aisles shall comply with either
paragraph (CC)(10)(a)(1029.10.1) or (CC)(10)(b)(1029.10.2)
of this rule.
(a)
[BE] 1029.10.1 Transitions and stairways that
maintain stepped aisle riser and tread dimensions. Stepped aisles,
transitions and stairways that maintain riser and tread dimensions shall comply
with paragraph (CC)(13)( 1029.13) of this
rule as one exit access component.
(b)
[BE]
1029.10.2 Transitions to stairways that do not maintain stepped aisle riser and
tread dimensions.
Transitions between
stepped aisles with riser and tread dimensions that differ from the stairways
shall comply with
paragraphs (CC)(10)(b)(i)(1029.10.2.1) and
(CC)(10)(c)(1029.10.3)
of this rule.
(i)
[BE]
1029.10.2.1 Stairways and stepped aisles in a straight run. Transitions
where the stairway is a straight run from the stepped aisle shall have a
minimum depth of 22 inches (559 mm) where the treads on the descending side of
the transition have greater depth and 30 inches (762 mm) where the treads on
the descending side of the transition have lesser depth.
(ii)
[BE]
1029.10.2.2 Stairways and stepped aisles that change direction.
Transitions where the stairway changes direction from the stepped aisle shall
have a minimum depth of 11 inches (280 mm) or the stepped aisle tread depth,
whichever is greater, between the stepped aisle and
stairway.
(c)
[BE] 1029.10.3 Transition marking.
A distinctive marking stripe shall be provided at each
nosing or leading edge adjacent to the transition. Such stripe shall be not
less than 1 inch (25 mm), and not more than 2 inches (51 mm), wide. The edge
marking stripe shall be distinctively different from the stepped aisle
contrasting marking stripe.
(11)
[BE]
1029.11 Construction.
Aisles, stepped
aisles and ramped aisles shall be built of materials consistent with the types
permitted for the type of construction of the building.
Exception:
Wood handrails shall be permitted for all types of
construction.
(a)
[BE] 1029.11.1 Walking surface.
The surface of aisles, stepped aisles and ramped aisles
shall be of slip-resistant materials that are securely attached. The surface
for stepped aisles shall comply with paragraph
(K)(7)(a)(1011.7.1) of this rule.
(b)
[BE]
1029.11.2 Outdoor conditions.
Outdoor
aisles, stepped aisles and ramped aisles and outdoor approaches to aisles,
stepped aisles and ramped aisles shall be designed so that water will not
accumulate on the walking surface.
(12)
[BE]
1029.12 Aisle accessways.
Aisle accessways
for seating at tables shall comply with
paragraph
(CC)(12)(a)(1029.12.1)
of this rule. Aisle accessways for
seating in rows shall comply with
paragraph
(CC)(12)(b)(1029.12.2)
of this rule.
(a)
1029.12.1
Seating at tables. Where seating is located at a table or counter and is
adjacent to an aisle or aisle accessway, the measurement of required clear
width of the aisle or aisle accessway shall be made to a line 19 inches (483
mm) away from and parallel to the edge of the table or counter. The 19-inch
(483 mm) distance shall be measured perpendicular to the side of the table or
counter. In the case of other side boundaries for aisles or aisle accessways,
the clear width shall be measured to walls, edges of seating and tread
edges.
Exception:
Where tables or counters are served by fixed seats, the
width of the aisle or aisle accessway shall be measured from the back of the
seat.
(i)
1029.12.1.1 Aisle accessway capacity and width
for seating at tables. Aisle accessways serving arrangements of seating
at tables or counters shall comply with the capacity requirements of
paragraph (E)(1)( 1005.1)
of this rule but
shall not have less than 12 inches (305 mm) of width plus 1/2 inch ( 12.7 mm) of
width for each additional 1 foot (305 mm), or fraction thereof, beyond 12 feet
(3658 mm) of aisle accessway length measured from the center of the seat
farthest from an aisle.
Exception:
Portions of an aisle accessway having a length not
exceeding 6 feet (1829 mm) and used by a total of not more than four
persons.
(ii)
[BE] 1029.12.1.2 Seating at table aisle accessway
length. The length of travel along the aisle accessway shall not exceed
30 feet (9144 mm) from any seat to the point where a person has a choice of two
or more paths of egress travel to separate exits.
(b)
[BE]
1029.12.2 Clear width of aisle accessways serving seating in rows. Where
seating rows have 14 or fewer seats, the minimum clear aisle accessway width
shall be not less than 12 inches (305 mm) measured as the clear horizontal
distance from the back of the row ahead and the nearest projection of the row
behind. Where chairs have automatic or self-rising seats, the measurement shall
be made with seats in the raised position. Where any chair in the row does not
have an automatic or self-rising seat, the measurements shall be made with the
seat in the down position. For seats with folding tablet arms, row spacing
shall be determined with the tablet arm in the used position.
Exception:
For seats with folding tablet arms, row spacing is
permitted to be determined with the tablet arm in the stored position where the
tablet arm when raised manually to vertical position in one motion
automatically returns to the stored position by force of gravity.
(i)
[BE]
1029.12.2.1 Dual access. For rows of seating served by aisles or
doorways at both ends, there shall be not more than 100 seats per row. The
minimum clear width of 12 inches (305 mm) between rows shall be increased by
0.3 inch ( 7.6 mm) for every additional seat beyond 14 seats where seats have
backrests or beyond 21 where seats are without backrests. The minimum clear
width is not required to exceed 22 inches (559 mm).
Exception:
For smoke-protected assembly seating, the row length
limits for a 12-inch-wide (305 mm) aisle accessway, beyond which the aisle
accessway minimum clear width shall be increased, are in Table
1029.12.2.1of this rule.
Table [BE]
1029.12.2.1
Smoke-protected assembly aisle
accessways
Total number of seats in
the smoke-protected assembly seating
|
Maximum number of seats
per row permitted to have a minimum 12-inch clear width aisle
accessway
|
Aisle or doorway at both
ends of row
|
Aisle or doorway at one
end of row only
|
Seats with
backrests
|
Seats without
backrests
|
Seats with
backrests
|
Seats without
backrests
|
Less than 4,000
|
14
|
21
|
7
|
10
|
4,000
|
15
|
22
|
7
|
10
|
7,000
|
16
|
23
|
8
|
11
|
10,000
|
17
|
24
|
8
|
11
|
13,000
|
18
|
25
|
9
|
12
|
16,000
|
19
|
26
|
9
|
12
|
19,000
|
20
|
27
|
10
|
13
|
22,000 and greater
|
21
|
28
|
11
|
14
|
For SI: 1 inch = 25.4 mm.
(ii)
[BE] 1029.12.2.2 Single access. For rows of
seating served by an aisle or doorway at only one end of the row, the minimum
clear width of 12 inches (305 mm) between rows shall be increased by 0.6 inch (
15.2 mm) for every additional seat beyond seven seats where seats have
backrests or beyond 10 where seats are without backrests. The minimum clear
width is not required to exceed 22 inches (559 mm).
Exception:
For smoke-protected assembly seating, the row length
limits for a 12-inch-wide (305 mm) aisle accessway, beyond which the aisle
accessway minimum clear width shall be increased, are in Table 1029.12.2.1
of this rule.
(13)
[BE]
1029.13 Assembly aisle walking surfaces. Ramped aisles shall comply with
paragraphs (CC)(13)(a)(1029.13.1)
to
(CC)(13)(a)(iii)(1029.13.1.3)
of this rule. Stepped aisles
shall comply with
paragraphs (CC)(13)(b)(1029.13.2)
to (CC)(13)(b)(iv)(1029.13.2.4)
of this
rule.
(a)
[BE] 1029.13.1 Ramped aisles.
Aisles that are sloped more than one unit vertical in
20 units horizontal (5-
per cent slope) shall be considered a
ramped aisle. Ramped aisles that serve as part of an accessible route in
accordance with
paragraph (I)(1009)
of this
rule and section 1108.2 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code shall have a maximum slope of one unit
vertical in 12 units horizontal (8-
per cent slope). The slope
of other ramped aisles shall not exceed one unit vertical in 8 units horizontal
( 12.5 -
per cent slope).
(i)
[BE]
1029.13.1.1 Cross slope. The slope measured perpendicular to the
direction of travel of a ramped aisle shall not be steeper than one unit
vertical in 48 units horizontal (2-per cent
slope).
(ii)
[BE] 1029.13.1.2 Landings. Ramped aisles
shall have landings in accordance with paragraphs (L)(6)(
1012.6) to (L)(6)(e)(1012.6.5) of this rule.
Landings for ramped aisles shall be permitted to overlap required aisles or
cross aisles.
(iii)
[BE] 1029.13.1.3 Edge protection. Ramped
aisles shall have edge protection in accordance with
paragraphs (L)(10)( 1012.10) and (L)(10)(a)(1012.10.1)
of this rule.
Exception:
In assembly spaces with fixed seating, edge protection
is not required on the sides of ramped aisles where the ramped aisles provide
access to the adjacent seating and aisle accessways.
(b)
[BE] 1029.13.2 Stepped aisles.
Aisles with a slope exceeding one unit vertical in
eight units horizontal ( 12.5 -
per cent slope) shall consist
of a series of risers and treads that extends across the full width of aisles
and complies with
paragraphs (CC)(13)(b)(i)(1029.13.2.1)
to (CC)(13)(b)(iv)(1029.13.2.4)
of this
rule.
(i)
[BE] 1029.13.2.1 Treads. Tread depths
shall be not less than 11 inches (279 mm) and shall have dimensional
uniformity.
Exception:
The tolerance between adjacent treads shall not exceed
3/16 inch ( 4.8 mm).
(ii)
[BE]
1029.13.2.2 Risers. Where the gradient of stepped aisles is to be the
same as the gradient of adjoining seating areas, the riser height shall be not
less than 4 inches (102 mm) nor more than 8 inches (203 mm) and shall be
uniform within each flight.
Exceptions:
1.
Riser height
nonuniformity shall be limited to the extent necessitated by changes in the
gradient of the adjoining seating area to maintain adequate sightlines. Where
nonuniformities exceed 3/16 inch ( 4.8 mm) between adjacent risers, the exact
location of such nonuniformities shall be indicated with a distinctive marking
stripe on each tread at the nosing or leading edge adjacent to the nonuniform
risers. Such stripe shall be not less than 1 inch (25 mm), and not more than 2
inches (51 mm) wide. The edge marking stripe shall be distinctively different
from the contrasting marking stripe.
2.
Riser heights not
exceeding 9 inches (229 mm) shall be permitted where they are necessitated by
the slope of the adjacent seating areas to maintain sightlines.
(a)
[BE]
1029.13.2.2.1 Construction tolerances. The tolerance between adjacent
risers on a stepped aisle that were designed to be equal height shall not
exceed 3/16 inch ( 4.8 mm). Where the stepped aisle is designed in accordance
with exception 1 of paragraph (CC)(3)(b)(ii)(1029.3.2.2)
of this rule, the stepped aisle shall be constructed so that
each riser of unequal height, determined in the direction of descent, is not
more than 3/8inch ( 9.5 mm) in height different from adjacent risers where
stepped aisle treads are less than 22 inches (560 mm) in depth and 3/4 inch (
19.1 mm) in height different from adjacent risers where stepped aisle treads
are 22 inches (560 mm) or greater in depth.
(iii)
[BE]
1029.13.2.3 Tread contrasting marking stripe. A contrasting marking
stripe shall be provided on each tread at the nosing or leading edge such that
the location of each tread is readily apparent when viewed in descent. Such
stripe shall be not less than 1 inch (25 mm), and not more than 2 inches (51
mm), wide.
Exception:
The contrasting marking stripe is permitted to be
omitted where tread surfaces are such that the location of each tread is
readily apparent when viewed in descent.
(iv)
[BE]
1029.13.2.4 Nosing and profile. Nosing and riser profile shall comply
with paragraphs (K)(5)(e)(1011.5.5) to
(K)(5)(e)(iii)(1011.5.5.3) of this
rule.
(14)
[BE]
1029.14 Seat stability.
In a building,
room or space used for assembly purposes, the seats shall be securely fastened
to the floor.
Exceptions:
1.
In a building,
room or space used for assembly purposes or portions thereof without ramped or
tiered floors for seating and with 200 or fewer seats, the seats shall not be
required to be fastened to the floor.
2.
In a building,
room or space used for assembly purposes or portions thereof with seating at
tables and without ramped or tiered floors for seating, the seats shall not be
required to be fastened to the floor.
3.
In a building,
room or space used for assembly purposes or portions thereof without ramped or
tiered floors for seating and with greater than 200 seats, the seats shall be
fastened together in groups of not less than three or the seats shall be
securely fastened to the floor.
4.
In a building,
room or space used for assembly purposes where flexibility of the seating
arrangement is an integral part of the design and function of the space and
seating is on tiered levels, not more than 200 seats shall not be required to
be fastened to the floor. Plans showing seating, tiers and aisles shall be
submitted for approval.
5.
Groups of seats within a building, room or space used
for assembly purposes separated from other seating by railings, guards, partial
height walls or similar barriers with level floors and having not more than 14
seats per group shall not be required to be fastened to the
floor.
6.
Seats intended for musicians or other performers and
separated by railings, guards, partial height walls or similar barriers shall
not be required to be fastened to the floor.
(15)
[BE]
1029.15 Handrails.
Ramped aisles having a
slope exceeding one unit vertical in 15 units horizontal ( 6.7 -
per
cent slope) and stepped aisles shall be provided with handrails in
compliance with
paragraph (N)(1014)
of this
rule located either at one or both sides of the aisle or within the
aisle width.
Exceptions:
1.
Handrails are not
required for ramped aisles with seating on both sides.
2.
Handrails are not
required where, at the side of the aisle, there is a guard with a top surface
that complies with the graspability requirements of handrails in accordance
with paragraph (N)(3)( 1014.3) of this
rule.
3.
Handrail extensions are not required at the top and
bottom of stepped aisles and ramped aisles to permit crossovers within the
aisles.
(a)
[BE] 1029.15.1 Discontinuous handrails.
Where there is seating on both sides of the aisle, the
mid-aisle handrails shall be discontinuous with gaps or breaks at intervals not
exceeding five rows to facilitate access to seating and to permit crossing from
one side of the aisle to the other. These gaps or breaks shall have a clear
width of not less than 22 inches (559 mm) and not greater than 36 inches (914
mm), measured horizontally, and the mid-aisle handrail shall have rounded
terminations or bends.
(b)
[BE] 1029.15.2 Handrail termination.
Handrails located on the side of stepped aisles shall
return to a wall, guard or the walking surfaces or shall be continuous to the
handrail of an adjacent stepped aisle flight.
(c)
[BE]
1029.15.3 Mid-aisle termination.
Mid-aisle
handrails shall not extend beyond the lowest riser and shall terminate within
18 inches (381 mm), measured horizontally, from the lowest riser. Handrail
extensions are not required.
Exception:
Mid-aisle handrails shall be permitted to extend beyond
the lowest riser where the handrail extensions do not obstruct the width of the
cross aisle.
(d)
[BE] 1029.15.4 Rails.
Where mid-aisle handrails are provided in stepped
aisles, there shall be an additional rail located approximately 12 inches (305
mm) below the handrail. The rail shall be adequate in strength and attachment
in accordance with section 1607.8.1.2 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(16)
[BE]
1029.16 Assembly guards. Guards adjacent to seating in a building, room
or space used for assembly purposes shall be provided where required by
paragraph (O)(1015)
of this rule and shall be
constructed in accordance with
paragraph (O)(1015)
of
this rule except where provided in accordance with
paragraphs (CC)(16)(a)(1029.16.1)
to
(CC)(16)(d)(1029.16.4)
of this rule. At bleachers, grandstands
and folding and telescopic seating, guards must be provided where required by
ICC 300
as listed in rule
1301:7-7-80
of the Administrative Code and
paragraph
(CC)(16)(a)(1029.16.1)
of this rule.
(a)
[BE]
1029.16.1 Perimeter guards.
Perimeter
guards shall be provided where the footboards or walking surface of seating
facilities are more than 30 inches (762 mm) above the floor or grade below.
Where the seatboards are adjacent to the perimeter, guard height shall be 42
inches (1067 mm) high minimum, measured from the seatboard. Where the seats are
self-rising, guard height shall be 42 inches (1067 mm) high minimum, measured
from the floor surface. Where there is an aisle between the seating and the
perimeter, the guard height shall be measured in accordance with
paragraph (O)(2)( 1015.2)
of this
rule.
Exceptions:
1.
Guards that impact
sightlines shall be permitted to comply with paragraph
(CC)(16)(c)(1029.16.3) of this rule.
2.
Bleachers,
grandstands and folding and telescopic seating shall not be required to have
perimeter guards where the seating is located adjacent to a wall and the space
between the wall and the seating is less than 4 inches (102 mm)
(b)
[BE] 1029.16.2 Cross aisles.
Cross aisles located more than 30 inches (762 mm) above
the floor or grade below shall have guards in accordance with
paragraph (O)(1015)
of this rule.
Where an elevation change of 30 inches
(762 mm) or less occurs between a cross aisle and the adjacent floor or grade
below, guards not less than 26 inches (660 mm) above the aisle floor shall be
provided.
Exception:
Where the backs of seats on the front of the cross
aisle project 24 inches (610 mm) or more above the adjacent floor of the aisle,
a guard need not be provided.
(c)
[BE]
1029.16.3 Sightline-constrained guard heights.
Unless subject to the requirements of
paragraph (CC)(16)(d)(1029.16.4) of this
rule, a fascia or railing system in accordance with the guard
requirements of paragraph (O)(1015) of this
rule and having a minimum height of 26 inches (660 mm) shall be
provided where the floor or footboard elevation is more than 30 inches (762 mm)
above the floor or grade below and the fascia or railing would otherwise
interfere with the sightlines of immediately adjacent seating.
(d)
[BE]
1029.16.4 Guards at the end of aisles.
A
fascia or railing system complying with the guard requirements of
paragraph (O)(1015) of this rule shall be
provided for the full width of the aisle where the foot of the aisle is more
than 30 inches (762 mm) above the floor or grade below. The fascia or railing
shall be a minimum of 36 inches (914 mm) high and shall provide a minimum 42
inches (1067 mm) measured diagonally between the top of the rail and the nosing
of the nearest tread.
(DD)
Section
1030 Emergency escape and rescue
(1)
[BE] 1030.1
General.
In addition to the means of
egress required by this
rule, provisions shall be made for
emergency escape and rescue openings in Group R-2 occupancies in accordance
with Tables 1006.3.2(1) and 1006.3.2(2)
of this rule and Group
R-3 occupancies. Basements and sleeping rooms below the fourth story above
grade plane shall have at least one exterior emergency escape and rescue
opening in accordance with this
paragraph. Where basements
contain one or more sleeping rooms, emergency escape and rescue openings shall
be required in each sleeping room, but shall not be required in adjoining areas
of the basement. Such openings shall open directly into a public way or to a
yard or court that opens to a public way.
Exceptions:
1.
Basements with
ceiling height of less than 80 inches (2032 mm) shall not be required to have
emergency escape and rescue openings.
2.
Emergency escape
and rescue openings are not required from basements or sleeping rooms that have
an exit door or exit access door that opens directly into a public way or to a
yard, court or exterior exit balcony that opens to a public
way.
3.
Basements without habitable spaces and having not more
than 200 square feet ( 18.6 m2) in floor area shall
not be required to have emergency escape and rescue
openings.
(2)
[BE] 1030.2 Minimum size.
Emergency escape and rescue openings shall have a
minimum net clear opening of 5.7 square feet ( 0.53
m2).
Exception:
The minimum net clear opening for grade-floor emergency
escape and rescue openings shall be 5 square feet ( 0.46
m2).
(a)
[BE]
1030.2.1 Minimum dimensions. The minimum net clear opening height
dimension shall be 24 inches (610 mm). The minimum net clear opening width
dimension shall be 20 inches (508 mm). The net clear opening dimensions shall
be the result of normal operation of the opening.
(3)
[BE] 1030.3
Maximum height from floor.
Emergency
escape and rescue openings shall have the bottom of the clear opening not
greater than 44 inches (118 mm) measured from the floor.
(4)
[BE] 1030.4
Operational constraints.
Emergency escape
and rescue openings shall be operational from the inside of the room without
the use of keys or tools. Bars, grilles, grates or similar devices are
permitted to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with paragraph
(DD)(2)( 1030.2) of this rule and such devices shall be
releasable or removable from the inside without the use of a key, tool or force
greater than that which is required for normal operation of the escape and
rescue opening. Where such bars, grilles, grates or similar devices are
installed in existing buildings, smoke alarms shall be installed in accordance
with paragraph (G)(2)(k)(907.2.11) of rule
1301:7-7-09
of the Administrative Code regardless of the valuation of the
alteration.
(5)
[BE] 1030.5 Window wells. An emergency
escape and rescue opening with a finished sill height below the adjacent ground
level shall be provided with a window well in accordance with
paragraphs (DD)(5)(a)(1030.5.1) and (DD)(5)(b)(1030.5.2)
of this rule.
(a)
[BE] 1030.5.1 Minimum size.
The minimum horizontal area of the window well shall be
9 square feet ( 0.84 m2), with a minimum dimension
of 36 inches (914 mm). The area of the window well shall allow the emergency
escape and rescue opening to be fully opened.
(b)
[BE]
1030.5.2 Ladders or steps.
Window wells
with a vertical depth of more than 44 inches (1118 mm) shall be equipped with
an approved permanently affixed ladder or steps. Ladders or rungs shall have an
inside width of at least 12 inches (305 mm), shall project at least 3 inches
(76 mm) from the wall and shall be spaced not more than 18 inches (457 mm) on
center (o.c.) vertically for the full height of the window well. The ladder or
steps shall not encroach into the required dimensions of the window well by
more than 6 inches (152 mm). The ladder or steps shall not be obstructed by the
emergency escape and rescue opening. Ladders or steps required by this
paragraph are exempt from the stairway requirements of
paragraph (K)(1011) of this
rule.
(EE)
Section
1031 Maintenance of the means of egress
(1)
1031.1
General.
The means of egress for buildings
or portions thereof shall be maintained in accordance with this
paragraph.
(2)
1031.2 Reliability.
Required exit accesses, exits or exit discharges shall
be continuously maintained free from obstructions or impediments to full
instant use in the case of fire or other emergency where the building area
served by the means of egress is occupied. An exit or exit passageway shall not
be used for any purpose that interferes with a means of egress.
(a)
1031.2.1 Security device.
Any security device or system that emits any medium that could obscure
a means of egress in any building, structure or premise shall be
prohibited.
(3)
1031.3
Obstructions.
A means of egress shall be
free from obstructions that would prevent its use, including the accumulation
of snow and ice.
(a)
1031.3.1 Group I-2. In Group I-2, the
required clear width for aisles, corridors and ramps that are part of the
required means of egress shall comply with
paragraph (T)(2)(
1020.2)
of this rule. The facility shall have a plan to
maintain the required clear width during emergency situations.
Exception:
In areas required for bed movement, equipment shall be
permitted in the required width where all the following provisions are
met:
1.
The equipment is low hazard and wheeled.
2.
The equipment does
not reduce the effective clear width for the means of egress to less than 5
feet (1525 mm).
3.
The equipment is limited to:
3.1
Equipment and
carts in use.
3.2
Medical emergency equipment.
3.3
Infection control
carts.
3.4
Patient lift and transportation equipment.
4.
Medical emergency equipment and patient lift and
transportation equipment, when not in use, is required to be located on one
side of the corridor.
5.
The equipment is limited in number to a maximum of one
per patient sleeping room or patient care room within each smoke
compartment.
(4)
[BE] 1031.4
Exit signs.
Exit signs shall be installed
and maintained in accordance with paragraph (M)(1013)
of this rule. Decorations, furnishings, equipment or adjacent
signage that impairs the visibility of exit signs, creates confusion or
prevents identification of the exit shall not be allowed.
(5)
1031.5
Nonexit identification.
Where a door is
adjacent to, constructed similar to and can be confused with a means of egress
door, that door shall be identified with an approved sign that identifies the
room name or use of the room.
(6)
1031.6
Finishes, furnishings and decorations.
Means of egress doors shall be maintained in such a manner
as to be distinguishable from the adjacent construction and finishes such that
the doors are easily recognizable as doors. Furnishings, decorations or other
objects shall not be placed so as to obstruct exits, access thereto, egress
therefrom, or visibility thereof. Hangings and draperies shall not be placed
over exit doors or otherwise be located to conceal or obstruct an exit. Mirrors
shall not be placed on exit doors. Mirrors shall not be placed in or adjacent
to any exit in such a manner as to confuse the direction of
exit.
(7)
1031.7 Emergency escape and rescue openings.
Required emergency escape and rescue openings shall be
maintained in accordance with the code in effect at the time of construction,
and the following: Required emergency escape and rescue openings shall be
operational from the inside of the room without the use of keys or tools. Bars,
grilles, grates or similar devices are allowed to be placed over emergency
escape and rescue openings provided the minimum net clear opening size complies
with the code that was in effect at the time of construction and such devices
shall be releasable or removable from the inside without the use of a key, tool
or force greater than that which is required for normal operation of the
emergency escape and rescue opening.
(8)
1031.8
Inspection, testing and maintenance.
All
two-way communication systems for areas of refuge shall be inspected and tested
on a yearly basis to verify that all components are operational. When required,
the tests shall be conducted in the presence of the fire code official. Records
of inspection, testing and maintenance shall be maintained.
(9)
1031.9
Floor identification signs.
The floor
identification signs required by
paragraphs (W)(9)( 1023.9)
of this rule and (D)(24)( 1104.24)
of rule
1301:7-7-11
of the Administrative Code shall be maintained in an approved
manner.
Replaces: 1301:7-7-10