Current through all regulations passed and filed through September 16, 2024
(A)
Section 801 General
(1)801.1 Scope. The
provisions of this rule shall govern interior finish, interior trim, furniture,
furnishings, decorative materials and decorative vegetation in buildings.
Existing buildings shall comply with paragraphs (C)(803) to (H) (808) of this
rule. New buildings shall comply with paragraphs (D)(804) to (H)(808) of this
rule and section 803 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(B)
Section 802
Definitions
(1)802.1 General. The following terms are defined in rule
1301:7-7-02 of the
Administrative Code.
"Flame spread."
"Flame spread index."
"Interior floor-wall
base."
"Site-fabricated stretch
system."
"Smoke-developed index."
(2)
802.2
Terms used for paragraph (E)(5)( 805.5) of this rule. The following words take
on exclusive meanings as used in paragraph (E)(5)( 805.5) of this rule only,
pursuant to section 3737.841 of the Revised
Code.
"Filling material." Means cotton, wool,
kapok, feathers, down, hair, liquid, or any other natural or manmade material
or substance that is used or can be used for stuffing in seating
furniture.
"Public occupancy." Means all of the
following:
1.
Any state correctional institution as defined in
section 2967.01 of the Revised Code and
any county, multicounty, municipal, or municipal-county jail or
workhouse;
2.
Any hospital as defined in section
3727.01 of the Revised Code, any
hospital licensed by the department of mental health under section
5119.20 of the Revised Code, and
any institution, hospital, or other place established, controlled, or
supervised by the department of mental health under Chapter 5119. of the
Revised Code;
3.
Any nursing home, residential care facility, or home
for the aging as defined in section
3721.01 of the Revised Code and
any adult care facility as defined in section
3722.01 of the Revised
Code;
4.
Any child day-care center and any type A family
day-care home as defined in section
5104.01 of the Revised
Code;
5.
Any public auditorium or stadium;
6.
Public assembly
areas of hotels and motels containing more than ten articles of seating
furniture.
"Seating furniture." Includes the
cushions or pillows belonging to or forming a part of the furniture, the
structural unit, and the filling material and its container or covering, and
any article of furniture, including children's furniture that can be used as a
support for an individual, or their limbs or feet, when sitting or resting in
an upright or reclining position and that either:
1.
Is made with loose
or attached cushions or pillows;
2.
Is stuffed or
filled in whole or in part with any filling material;
3.
Is or can be
stuffed or filled in whole or in part with any substance or material, concealed
by fabric or any other covering.
Seating furniture does not include,
except if intended for use by children or in facilities designed for the care
or treatment of humans, any of the following:
1.
Cushions or pads
intended solely for outdoor use;
2.
Any article with a
smooth surface that contains no more than one-half inch of filling material, if
that article does not have an upholstered horizontal surface meeting an
upholstered vertical surface; and
3.
Any article
manufactured solely for recreational use or physical fitness purposes,
including weight-lifting benches, gymnasium mats or pads, and sidehorses.
"Sell." Includes sell, offer, or expose
for sale, barter, trade, deliver, give away, rent, consign, lease, possess for
sale, or dispose of in any other commercial
manner.
(C)
Section 803
Interior wall and ceiling finish and trim in existing buildings
(1)803.1 General. The
provisions of this paragraph shall limit the allowable fire performance and
smoke development of interior wall and ceiling finishes and interior wall and
ceiling trim in existing buildings based on location and occupancy
classification. Interior wall and ceiling finishes shall be classified in
accordance with section 803 of the building code as listed in rule
1301:7-7-80
of the Administrative Code. Such materials shall be grouped in accordance with
ASTM E 84 as listed in rule 1301:7-7-80 of the Administrative Code, as
indicated in paragraph (C)(1)(a)(803.1.1) of this rule, or in accordance with
NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code, as indicated in paragraph (C)(1)(b)(803.1.2) of
this rule.
Exceptions:
1.
Materials having a
thickness less than 0.036 inch ( 0.9 mm) applied directly to the surface of
walls and ceilings.
2.
Exposed portions of structural members complying with
the requirements of buildings of Type IV construction in accordance with the
building code as listed in rule
1301:7-7-80
of the Administrative Code shall not be subject to interior finish
requirements.
(a)
803.1.1 Classification in accordance with ASTM E 84 as
listed in rule
1301:7-7-80
of the Administrative Code. Interior finish materials shall be grouped in the
following classes in accordance with their flame spread and smoke-developed
index where tested in accordance with ASTM E 84 as listed in rule
1301:7-7-80
of the Administrative Code.
(i)
Class A: flame spread index 0-25; smoke-developed index
0-450.
(ii)
Class B: flame spread index 26-75; smoke-developed
index 0-450.
(iii)
Class C: flame spread index 76-200; smoke-developed
index 0-450.
(b)
803.1.2 Classification in accordance with NFPA 286 as
listed in rule
1301:7-7-80
of the Administrative Code. Interior wall or ceiling finishes shall be allowed
to be tested in accordance with NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code. Finishes tested in accordance with NFPA 286 as
listed in rule 1301:7-7-80 of the Administrative Code shall comply with
paragraph (C)(1)(b)(i)(803.1.2.1) of this rule. Interior wall and ceiling
finish materials tested in accordance with NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code and meeting the acceptance criteria of paragraph
(C)(1)(b)(i)(803.1.2.1) of this rule, shall be allowed to be used where a Class
A classification in accordance with ASTM E 84 as listed in rule
1301:7-7-80
of the Administrative Code is required.
(i)
803.1.2.1
Acceptance criteria for NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code. The interior finish shall comply with the
following:
(a)
During the 40 kW exposure, flames shall not spread to the
ceiling.
(b)
The flame shall not spread to the outer extremity of
the sample on any wall or ceiling.
(c)
Flashover, as
defined in NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code, shall not occur.
(d)
The peak heat
release rate throughout the test shall not exceed 800 kW.
(e)
The total smoke
released throughout the test shall not exceed 1,000
m2.
(2)
803.2 Stability. Interior finish materials regulated by
this rule shall be applied or otherwise fastened in such a manner that such
materials will not readily become detached where subjected to room temperatures
of 200°F (93°C) for not less than 30 minutes.
(3)
803.3 Interior
finish requirements based on occupancy. Interior wall and ceiling finish shall
have a flame spread index not greater than that specified in Table 803.3 of
this rule for the group and location designated.
Table 803.3 Interior wall and ceiling
finish requirements by occupancyk
Group |
Sprinklered1
|
Nonsprinklered |
Interior exit stairways and
ramps and exit passageways a b
|
Corridors and enclosure for
exit access stairwaysand exit access ramps
|
Rooms and enclosed spacesc
|
Interior exit stairways and
ramps and exit passagewaysa,b
|
Corridors and enclosure for
stairways and exit access ramps
|
Rooms and enclosed spacesc
|
A-1 & A-2 |
B |
B |
C |
A |
Ad
|
Be
|
A-3f, A-4, A-5
|
B |
B |
C |
A |
Ad
|
C |
B, E, M, R-1, R-4
|
B |
C |
C |
A |
B |
C |
F |
C |
C |
C |
B |
C |
C |
H |
B |
B |
Cg
|
A |
A |
B |
I-1 |
B |
C |
C |
A |
B |
B |
I-2 |
B |
B |
Bh,i |
A |
A |
B |
I-3 |
A |
Ai
|
C |
A |
A |
B |
I-4 |
B |
B |
Bh,i
|
A |
A |
B |
R-2 |
C |
C |
C |
B |
B |
C |
R-3 |
C |
C |
C |
C |
C |
C |
S |
C |
C |
C |
B |
B |
C |
U |
No
restrictions |
No
restrictions |
For SI: 1 inch = 25.4 mm, 1 square foot
= 0.0929 m2.
a.
Class C interior
finish materials shall be allowed for wainscoting or paneling of not more than
1,000 square feet of applied surface area in the grade lobby where applied
directly to a noncombustible base or over furring strips applied to a
noncombustible base and fireblocked as required by section 803.11 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
b.
In exit enclosures
of buildings less than three stories in height of other than Group I-3, Class B
interior finish for nonsprinklered buildings and Class C for sprinklered
buildings shall be permitted.
c.
Requirements for
rooms and enclosed spaces shall be based upon spaces enclosed by partitions.
Where a fire-resistance rating is required for structural elements, the
enclosing partitions shall extend from the floor to the ceiling. Partitions
that do not comply with this shall be considered as enclosing spaces and the
rooms or spaces on both sides shall be considered as one. In determining the
applicable requirements for rooms and enclosed spaces, the specific occupancy
thereof shall be the governing factor regardless of the group classification of
the building or structure.
d.
Lobby areas in Group A-1, A-2 and A-3 occupancies shall
not be less than Class B materials.
e.
Class C interior
finish materials shall be allowed in Group A occupancies with an occupant load
of 300 persons or less.
f.
In places of religious worship, wood used for
ornamental purposes, trusses, paneling or chancel furnishing shall be
allowed.
g.
Class B material is required where the building exceeds
two stories.
h.
Class C interior finish materials shall be allowed in
administrative spaces.
i.
Class C interior finish materials shall be allowed in
rooms with a capacity of four persons or less.
j.
Class B materials
shall be allowed as wainscoting extending not more than 48 inches above the
finished floor in corridors.
k.
Finish materials
as provided for in other paragraphs of this code.
l.
Applies when the
vertical exits, exit passageways, corridors or rooms and spaces are protected
by an approved automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code.
(4)
803.4
Fire-retardant coatings. The required flame spread or smoke-developed index of
surfaces in existing buildings shall be allowed to be achieved by application
of approved fire-retardant coatings, paints or solutions to surfaces having a
flame spread index exceeding that allowed. Such applications shall comply with
NFPA 703 as listed in rule
1301:7-7-80
of the Administrative Code and the required fire-retardant properties shall be
maintained or renewed in accordance with the manufacturer's
instructions.
(5)
803.5 Textiles. Where used as interior wall or ceiling
finish materials, textiles, including materials having woven or nonwoven,
napped, tufted, looped or similar surface, shall comply with the requirements
of this paragraph.
(a)
803.5.1 Textile wall and ceiling coverings. Textile
wall or ceiling coverings shall comply with one of the following:
1.
The wall or
ceiling covering shall have a Class A flame spread index in accordance with
ASTM E 84 or UL 723 as listed in rule
1301:7-7-80
of the Administrative Code and be protected by automatic sprinklers installed
in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)
(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code.
2.
The wall covering
shall meet the criteria of paragraph (C)(5)(a)(i) (803.5.1.1) of this rule when
tested in the manner intended for use in accordance with NFPA 265 as listed in
rule
1301:7-7-80
of the Administrative Code using the product-mounting system, including
adhesive, of actual use.
3.
The wall or ceiling covering shall meet the criteria of
paragraph (C)(1) (b)(i)(803.1.2.1) of this rule when tested in accordance with
NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code using the product-mounting system, including
adhesive, of actual use.
(i)
803.5.1.1 Method B test protocol. During the Method B
protocol, the textile wall covering or expanded vinyl wall covering shall
comply with the following:
(a)
During the 40 kW exposure, flames shall not spread to
the ceiling.
(b)
The flame shall not spread to the outer extremities of
the samples on the 8-foot by 12-foot (203 mm by 305 mm) walls.
(c)
Flashover, as
defined in NFPA 265 as listed in rule
1301:7-7-80
of the Administrative Code, shall not occur.
(d)
For newly
introduced wall and ceiling coverings, the total smoke released throughout the
test shall not exceed 1,000 m2.
(b)
803.5.2 Newly introduced textile wall and ceiling
coverings. Newly introduced textile wall and ceiling coverings shall comply
with one of the following:
(i)
The wall or ceiling covering shall have a Class A flame
spread index in accordance with ASTM E 84 or UL 723 as listed in rule
1301:7-7-80
of the Administrative Code, and be protected by automatic sprinklers installed
in accordance with paragraph (C)(3) (a)(i)(903.3.1.1) or
(C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code. Test specimen preparation and mounting shall be in
accordance with ASTM E 2404 as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
The wall
covering shall meet the criteria of paragraph (C)(5)(a)(i) (803.5.1.1) of this
rule when tested in the manner intended for use in accordance with NFPA 265 as
listed in rule
1301:7-7-80
of the Administrative Code using the product-mounting system (including
adhesive) of actual use.
(iii)
The wall or
ceiling covering shall meet the criteria of paragraph (C)(1)(b)(i)(803.1.2.1)
of this rule when tested in accordance with NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code using the product-mounting system (including
adhesive) of actual use.
(6)
803.6 Expanded
vinyl wall or ceiling coverings. Expanded vinyl wall or ceiling coverings shall
comply with one of the following:
(a)
The wall or ceiling covering shall have a Class A flame
spread index in accordance with ASTM E 84 or UL 723 as listed in rule
1301:7-7-80
of the Administrative Code, and be protected by automatic sprinklers installed
in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)
(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code. Test specimen preparation and mounting shall be in
accordance with ASTM E 2404 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
The wall covering
shall meet the criteria of paragraph (C)(5)(a)(i) (803.5.1.1) of this rule when
tested in the manner intended for use in accordance with NFPA 265 as listed in
rule
1301:7-7-80
of the Administrative Code using the product-mounting system (including
adhesive) of actual use.
(c)
The wall or ceiling covering shall meet the criteria of
paragraph (C)(1)(b) (i)(803.1.2.1) of this rule when tested in accordance with
NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code using the product-mounting system (including
adhesive) of actual use.
(7)
803.7 Facings or
wood veneers intended to be applied on site over a wood substrate. Facings or
veneers intended to be applied on site over a wood substrate shall comply with
one of the following:
(a)
The facing or veneer shall have a Class A, B or C flame
spread index and smoke-developed index, based on the requirements of Table
803.3 of this rule, in accordance with ASTM E 84 or UL 723 as listed in rule
1301:7-7-80
of the Administrative Code. Test specimen preparation and mounting shall be in
accordance with ASTM E 2404 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
The facing or
veneer shall meet the criteria of paragraph (C)(1)(b)(i) (803.1.2.1) of this
rule when tested in accordance with NFPA 286 as listed in rule 1301:7-7-80 of
the Administrative Code using the product-mounting system, including adhesive,
described in Section 5.8.9 of NFPA 286 as listed in rule
1301:7-7-80
of the Administrative Code.
(8)
803.8 Foam
plastic materials. Foam plastic materials shall not be used as interior wall
and ceiling finish unless specifically allowed by paragraph (C)(8)(a) (803.8.1)
or (C)(8)(b)(803.8.2) of this rule. Foam plastic materials shall not be used as
interior trim unless specifically allowed by paragraph (C)(8)(c) (803.8.3) of
this rule.
(a)
803.8.1 Combustibility characteristics. Foam plastic
materials shall be allowed on the basis of fire tests that substantiate their
combustibility characteristics for the use intended under actual fire
conditions, as indicated in section 2603.9 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code. This paragraph shall apply both to exposed foam
plastics and to foam plastics used in conjunction with a textile or vinyl
facing or cover.
(b)
803.8.2 Thermal barrier. Foam plastic material shall be
allowed if it is separated from the interior of the building by a thermal
barrier in accordance with section 2603.4 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(c)
803.8.3 Trim.
Foam plastic shall be allowed for trim in accordance with paragraph (D)(2)(
804.2) of this rule.
(9)
[BF] 803.9
High-density polyethylene (HDPE) and polypropylene (PP). Where high-density
polyethylene or polypropylene is used as an interior finish it shall comply
with paragraph (C)(1)(b)(803.1.2) of this rule.
(10)
[BF] 803.10
Site-fabricated stretch systems. Where used as newly installed interior wall or
interior ceiling finish materials, site-fabricated stretch systems containing
all three components described in the definition in rule
1301:7-7-02 of the
Administrative Code shall be tested in the manner intended for use, and shall
comply with the requirements of paragraph (C)(1)(a)(803.1.1) or (C)(1)(b)
(803.1.2) of this rule. If the materials are tested in accordance with ASTM E
84 or UL 723 as listed in rule 1301:7-7-80 of the Administrative Code, specimen
preparation and mounting shall be in accordance with ASTM E 2573 as listed in
rule
1301:7-7-80
of the Administrative Code.
(D)
Section 804
Interior wall and ceiling trim and interior floor finish in new and existing
buildings
(1) 804.1 Interior trim. Material, other than foam plastic, used
as interior trim in new and existing buildings shall have minimum Class C flame
spread and smoke-developed indices, when tested in accordance with ASTM E 84 or
UL 723 as listed in rule
1301:7-7-80
of the Administrative Code, as described in paragraph (C)(1)(a)(803.1.1) of
this rule. Combustible trim, excluding handrails and guardrails, shall not
exceed 10 per cent of the specific wall or ceiling areas to which it is
attached.
(a)
804.1.1 Alternate testing. When the interior trim material
has been tested as an interior finish in accordance with NFPA 286 as listed in
rule
1301:7-7-80
of the Administrative Code and complies with the acceptance criteria in
paragraph (C)(1)(b)(i)(803.1.2.1) of this rule, it shall not be required to be
tested for flame spread index and smoke-developed index in accordance with ASTM
E 84 as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
804.2 Foam
plastic. Foam plastic used as interior trim shall comply with paragraphs
(D)(2)(a)(804.2.1) to (D)(2)(d)(804.2.4) of this rule.
(a)
804.2.1 Density.
The minimum density of the interior trim shall be 20 pounds per cubic foot (320
kg/m3).
(b)
804.2.2
Thickness. The maximum thickness of the interior trim shall be 1/2 inch ( 12.7
mm) and the maximum width shall be 8 inches (203 mm).
(c)
804.2.3 Area
limitation. The interior trim shall not constitute more than 10 per cent of the
specific wall or ceiling area to which it is attached.
(d)
804.2.4 Flame
spread. The flame spread index shall not exceed 75 where tested in accordance
with ASTM E 84 or UL 723 as listed in rule
1301:7-7-80
of the Administrative Code. The smoke-developed index shall not be
limited.
Exception: When the interior trim
material has been tested as an interior finish in accordance with NFPA 286 as
listed in rule
1301:7-7-80
of the Administrative Code and complies with the acceptance criteria in
paragraph (C)(1)(b)(i)(803.1.2.1) of this rule, it shall not be required to be
tested for flame spread index in accordance with ASTM E 84 or UL 723 as listed
in rule
1301:7-7-80
of the Administrative Code.
(3)
804.3 New
interior floor finish. New interior floor finish and floor covering materials
in new and existing buildings shall comply with paragraphs (D)(3)(a) (804.3.1)
to (D)(3)(c)(ii)(804.3.3.2) of this rule.
Exception: Floor finishes and coverings
of a traditional type, such as wood, vinyl, linoleum or terrazzo, and resilient
floor covering materials that are not composed of fibers.
(a)
804.3.1
Classification. Interior floor finish and floor covering materials required by
paragraph (D)(3)(c)(ii)(804.3.3.2) of this rule to be of Class I or II
materials shall be classified in accordance with NFPA 253 as listed in rule
1301:7-7-80
of the Administrative Code. The classification referred to herein corresponds
to the classifications determined by NFPA 253 as listed in rule 1301:7-7-80 of
the Administrative Code as follows: Class I, 0.45
watts/cm2 or greater; Class II, 0.22
watts/cm2 or greater.
(b)
804.3.2 Testing
and identification. Interior floor finish and floor covering materials shall be
tested by an approved agency in accordance with NFPA 253 as listed in rule
1301:7-7-80
of the Administrative Code and identified by a hang tag or other suitable
method so as to identify the manufacturer or supplier and style, and shall
indicate the interior floor finish or floor covering classification according
to paragraph (D) (3)(a)(804.3.1) of this rule. Carpet-type floor coverings
shall be tested as proposed for use, including underlayment. Test reports
confirming the information provided in the manufacturer's product
identification shall be furnished to the fire code official upon
request.
(c)
804.3.3 Interior floor finish requirements. New
interior floor covering materials shall comply with paragraphs
(D)(3)(c)(i)(804.3.3.1) and (D) (3)(c)(ii)(804.3.3.2) of this rule, and
interior floor finish materials shall comply with paragraph (D)(3)(a)(804.3.1)
of this rule.
(i)
804.3.3.1 Pill test. In all occupancies, new floor
covering materials shall comply with the requirements of the DOC FF-1 "pill
test" (CPSC 16 CFR Part 1630) as listed in rule
1301:7-7-80
of the Administrative Code or of ASTM D 2859 as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
804.3.3.2
Minimum critical radiant flux. In all occupancies, new interior floor finish
and floor covering materials in enclosures for stairways and ramps, exit
passageways, corridors and rooms or spaces not separated from corridors by
full-height partitions extending from the floor to the underside of the ceiling
shall withstand a minimum critical radiant flux. The minimum critical radiant
flux shall be not less than Class I in Groups I-1, I-2 and I-3 and not less
than Class II in Groups A, B, E, H, I-4, M, R-1, R-2 and S.
Exception: Where a building is equipped
throughout with an automatic sprinkler system in accordance with paragraph
(C)(3)(a) (i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule
1301:7-7-09
of the Administrative Code, Class II materials shall be permitted in any area
where Class I materials are required and materials complying with DOC FF-1
"pill test" (CPSC 16 CFR Part 1630 as listed in rule
1301:7-7-80
of the Administrative Code or with ASTM D 2859 as listed in rule
1301:7-7-80
of the Administrative Code shall be permitted in any area where Class II
material are required.
(4)
804.4 Interior
floor-wall base. Interior floor-wall base that is 6 inches (152 mm) or less in
height shall be tested in accordance with NFPA 253 as listed in rule
1301:7-7-80
of the Administrative Code and shall be not less than Class II. Where a Class I
floor finish is required, the floor-wall base shall be Class I. The
classification referred to herein corresponds to the classifications determined
by NFPA 253 as listed in rule
1301:7-7-80
of the Administrative Code as follows: Class I, 0.45
watt/cm2 or greater; Class II, 0.22
watts/cm2 or greater.
Exception: Interior trim materials that
comply with paragraph (D)(1)( 804.1) of this rule.
(E)
Section 805 Upholstered furniture and mattresses in new
and existing buildings
(1)
805.1 Group I-1, Condition 2. The requirements in
paragraphs (E)(1)(a)(805.1.1) to (E)(1)(b)(805.1.2) of this rule shall apply to
Group I-1, Condition 2.
(a)
805.1.1 Upholstered furniture. Newly introduced
upholstered furniture shall meet the requirements of paragraphs
(E)(1)(a)(i)(805.1.1.1) and (E)(1)(a) (iii)(805.1.1.3) of this rule.
(i)
805.1.1.1
Ignition by cigarettes. Newly introduced upholstered furniture shall be shown
to resist ignition by cigarettes as determined by tests conducted in accordance
with one of the following:
(a)
Mocked-up composites of the upholstered furniture shall
have a char length not exceeding 1.5 inches (38 mm) when tested in accordance
with NFPA 261 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
The components of
the upholstered furniture shall meet the requirements for Class I when tested
in accordance with NFPA 260 as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
805.1.1.2 Heat
release rate. Newly introduced upholstered furniture shall have limited rates
of heat release when tested in accordance with ASTM E 1537 or California
Technical Bulletin 133 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(a)
The peak rate of
heat release for the single upholstered furniture item shall not exceed 80
kW.
Exception: Upholstered furniture in
rooms or spaces protected by an approved automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(b)
The total energy
released by the single upholstered furniture item during the first 10 minutes
of the test shall not exceed 25 megajoules (MJ).
Exception: Upholstered furniture in
rooms or spaces protected by an approved automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(iii)
805.1.1.3
Identification. Upholstered furniture shall bear the label of an approved
agency, confirming compliance with the requirements of paragraphs
(E)(1)(a)(i)(805.1.1.1) and (E)(1)(a)(ii)(805.1.1.2) of this
rule.
(b)
805.1.2 Mattresses. Newly introduced mattresses shall
meet the requirements of paragraphs (E)(1)(b)(i)(805.1.2.1) to (E)(1)(b)(iii)
(805.1.2.3) of this rule.
(i)
805.1.2.1 Ignition by cigarettes. Newly introduced
mattresses shall be shown to resist ignition by cigarettes as determined by
tests conducted in accordance with DOC 16 CFR Part 1632 as listed in rule
1301:7-7-80
of the Administrative Code and shall have a char length not exceeding 2 inches
(51 mm).
(ii)
805.1.2.2 Heat release rate. Newly introduced
mattresses shall have limited rates of heat release when tested in accordance
with ASTM E 1590 or California Technical Bulletin 129 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(a)
The peak rate of
heat release for the single mattress shall not exceed 100 kW.
Exception: Mattresses in rooms or
spaces protected by an approved automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(b)
The total energy
released by the single mattress during the first 10 minutes of the test shall
not exceed 25 MJ.
Exception: Mattresses in rooms or
spaces protected by an approved automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(iii)
805.1.2.3
Identification. Mattresses shall bear the label of an approved agency,
confirming compliance with the requirements of paragraphs
(E)(2)(b)(i)(805.2.2.1) and (E)(2)(b)(ii)(805.2.2.2) of this rule.
(2)
805.2 Group I-2, nursing homes and hospitals. The
requirements in paragraphs (E) (2)(a)(805.2.1) to (E)(2)(b)(805.2.2) of this
rule shall apply to nursing homes and hospitals classified in Group I-2.
(a)
805.2.1
Upholstered furniture. Newly introduced upholstered furniture shall meet the
requirements of paragraphs (E)(2)(a)(i)(805.2.1.1) and (E)(2)(a)
(iii)(805.2.1.3) of this rule.
(i)
805.2.1.1 Ignition by cigarettes. Newly introduced
upholstered furniture shall be shown to resist ignition by cigarettes as
determined by tests conducted in accordance with one of the following:
(a)
mocked-up
composites of the upholstered furniture shall have a char length not exceeding
1.5 inches (38 mm) when tested in accordance with NFPA 261 as listed in rule
1301:7-7-80
of the Administrative Code or
(b)
the components of
the upholstered furniture shall meet the requirements for Class I when tested
in accordance with NFPA 260 as listed in rule
1301:7-7-80
of the Administrative Code.
Exception: Upholstered furniture
belonging to the patients in sleeping rooms of nursing homes (Group I-2),
provided that a smoke detector is installed in such rooms. Battery-powered,
single-station smoke alarms shall be allowed.
(ii)
805.2.1.2 Heat release rate. Newly introduced upholstered
furniture shall have limited rates of heat release when tested in accordance
with ASTM E 1537 or California Technical Bulletin 133 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(a)
The peak rate of
heat release for the single upholstered furniture item shall not exceed 80
kW.
Exception: Upholstered furniture in
rooms or spaces protected by an approved automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(b)
The total energy
released by the single upholstered furniture item during the first 10 minutes
of the test shall not exceed 25 MJ.
Exception: Upholstered furniture in
rooms or spaces protected by an approved automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(iii)
805.2.1.3
Identification. Upholstered furniture shall bear the label of an approved
agency, confirming compliance with the requirements of paragraphs
(E)(2)(a)(i)(805.2.1.1) and (E)(2)(a)(ii)(805.2.1.2) of this
rule.
(b)
805.2.2 Mattresses. Newly introduced mattresses shall
meet the requirements of paragraphs (E)(2)(b)(i)(805.2.2.1) to (E)(2)(b)(iii)
(805.2.2.3) of this rule.
(i)
805.2.2.1 Ignition by cigarettes. Newly introduced
mattresses shall be shown to resist ignition by cigarettes as determined by
tests conducted in accordance with DOC 16 CFR Part 1632 as listed in rule
1301:7-7-80
of the Administrative Code and shall have a char length not exceeding 2 inches
(51 mm).
(ii)
805.2.2.2 Heat release rate. Newly introduced
mattresses shall have limited rates of heat release when tested in accordance
with ASTM E 1590 or California Technical Bulletin 129 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(a)
The peak rate of
heat release for the single mattress shall not exceed 100 kW.
Exception: Mattresses in rooms or
spaces protected by an approved automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(b)
The total energy
released by the single mattress during the first 10 minutes of the test shall
not exceed 25 MJ.
Exception: Mattresses in rooms or
spaces protected by an approved automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(iii)
805.2.2.3
Identification. Mattresses shall bear the label of an approved agency,
confirming compliance with the requirements of paragraphs
(E)(2)(b)(i)(805.2.2.1) and (E)(2)(b)(ii)(805.2.2.2) of this
rule.
(3)
805.3 Group I-3,
detention and correction facilities. The requirements in paragraphs
(E)(3)(a)(805.3.1) to (E)(3)(b)(805.3.2) of this rule shall apply to detention
and correction facilities classified in Group I-3.
(a)
805.3.1
Upholstered furniture. Newly introduced upholstered furniture shall meet the
requirements of paragraphs (E)(3)(a)(i)(805.3.1.1) and (E)(3)(a)
(iii)(805.3.1.3) of this rule.
(i)
805.3.1.1 Ignition by cigarettes. Newly introduced
upholstered furniture shall be shown to resist ignition by cigarettes as
determined by tests conducted in accordance with one of the following:
(a)
Mocked-up
composites of the upholstered furniture shall have a char length not exceeding
1.5 inches (38 mm) when tested in accordance with NFPA 261 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
The components of
the upholstered furniture shall meet the requirements for Class I when tested
in accordance with NFPA 260 as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
805.3.1.2 Heat
release rate. Newly introduced upholstered furniture shall have limited rates
of heat release when tested in accordance with ASTM E 1537 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(a)
The peak rate of
heat release for the single upholstered furniture item shall not exceed 80
kW.
(b)
The total "energy released by the single upholstered
furniture item during the first 10 minutes of the test shall not exceed 25
MJ.
(iii)
805.3.1.3 Identification. Upholstered furniture shall
bear the label of an approved agency, confirming compliance with the
requirements of paragraphs (E)(3)(a)(i)(805.3.1.1) and (E)(3)(a)(ii)(805.3.1.2)
of this rule.
(b)
805.3.2 Mattresses. Newly introduced mattresses shall
meet the requirements of paragraphs (E)(3)(b)(i)(805.3.2.1) to (E)(3)(b)(iii)
(805.3.2.3) of this rule.
(i)
805.3.2.1 Ignition by cigarettes. Newly introduced
mattresses shall be shown to resist ignition by cigarettes as determined by
tests conducted in accordance with DOC 16 CFR Part 1632 as listed in rule
1301:7-7-80
of the Administrative Code and shall have a char length not exceeding 2 inches
(51 mm).
(ii)
805.3.2.2 Fire performance tests. Newly introduced
mattresses shall be tested in accordance with paragraph
(E)(3)(b)(ii)(a)(805.3.2.2.1) or (E)(3)(b)(ii)(b)(805.3.2.2.2) of this
rule.
(a)
805.3.2.2.1 Heat release rate. Newly introduced mattresses
shall have limited rates of heat release when tested in accordance with ASTM E
1590 or California Technical Bulletin 129 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(i)
The peak rate of
heat release for the single mattress shall not exceed 100 kW.
(ii)
The total energy
released by the single mattress during the first 10 minutes of the test shall
not exceed 25 MJ.
(b)
805.3.2.2.2 Mass
loss test. Newly introduced mattresses shall have a mass loss not exceeding 15
per cent of the initial mass of the mattress where tested in accordance with
the test in Annex A3 of ASTM F 1085 as listed in rule
1301:7-7-80
of the Administrative Code.
(iii)
805.3.2.3
Identification. Mattresses shall bear the label of an approved agency,
confirming compliance with the requirements of paragraphs
(E)(3)(b)(i)(805.3.2.1) and (E)(3)(b)(ii)(805.3.2.2) of this
rule.
(4)
805.4 Group R-2
college and university dormitories. The requirements in paragraphs
(E)(4)(a)(805.4.1) to (E)(4)(b)(iii)(805.4.2.3) of this rule shall apply to
college and university dormitories classified in Group R-2, including decks,
porches and balconies.
(a)
805.4.1 Upholstered furniture. Newly introduced
upholstered furniture shall meet the requirements of paragraphs
(E)(4)(a)(i)(805.4.1.1) to (E)(4)(a) (iii)(805.4.1.3) of this rule.
(i)
805.4.1.1
Ignition by cigarettes. Newly introduced upholstered furniture shall be shown
to resist ignition by cigarettes as determined by tests conducted in accordance
with one of the following:
(a)
Mocked-up composites of the upholstered furniture shall
have a char length not exceeding 11/2 inches (38 mm) when tested in accordance
with NFPA 261 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
The components of
the upholstered furniture shall meet the requirements for Class I when tested
in accordance with NFPA 260 as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
805.4.1.2 Heat
release rate. Newly introduced upholstered furniture shall have limited rates
of heat release when tested in accordance with ASTM E 1537 or California
Technical Bulletin 133 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(a)
The peak rate of
heat release for the single upholstered furniture item shall not exceed 80
kW.
Exception: Upholstered furniture in
rooms or spaces protected by an approved automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(b)
The total energy
released by the single upholstered furniture item during the first 10 minutes
of the test shall not exceed 25 MJ.
Exception: Upholstered furniture in
rooms or spaces protected by an approved automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(iii)
805.4.1.3
Identification. Upholstered furniture shall bear the label of an approved
agency, confirming compliance with the requirements of paragraphs
(E)(4)(a)(i)(805.4.1.1) and (E)(4)(a)(ii)(805.4.1.2) of this
rule.
(b)
805.4.2 Mattresses. Newly introduced mattresses shall
meet the requirements of paragraphs (E)(4)(b)(i)(805.4.2.1) to (E)(4)(b)(iii)
(805.4.2.3) of this rule.
(i)
805.4.2.1 Ignition by cigarettes. Newly introduced
mattresses shall be shown to resist ignition by cigarettes as determined by
tests conducted in accordance with DOC 16 CFR Part 1632 as listed in rule
1301:7-7-80
of the Administrative Code and shall have a char length not exceeding 2 inches
(51 mm).
(ii)
805.4.2.2 Heat release rate. Newly introduced
mattresses shall have limited rates of heat release when tested in accordance
with ASTM E 1590 or California Technical Bulletin 129 as listed in rule
1301:7-7-80
of the Administrative Code, as follows:
(a)
The peak rate of
heat release for the single mattress shall not exceed 100 kW.
Exception: Mattresses in rooms or
spaces protected by an approved automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(b)
The total energy
released by the single mattress during the first 10 minutes of the test shall
not exceed 25 MJ.
Exception: Mattresses in rooms or
spaces protected by an approved automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(iii)
805.4.2.3
Identification. Mattresses shall bear the label of an approved agency,
confirming compliance with the requirements of paragraphs
(E)(4)(b)(i)(805.4.2.1) and (E)(4)(b)(ii)(805.4.2.2) of this
rule.
(5)
805.5 Public
occupancies. The provisions of this paragraph shall apply to public occupancies
as defined in paragraph (B)(2)( 802.2) of this rule.
Exception: Upholstered furniture in
rooms and spaces protected by an approved automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
(a)
805.5.1 Requirements. No person shall sell for use in a
public occupancy or use in a public occupancy any upholstered furniture that
does not conform with the requirements of California Technical Bulletin 133 as
listed in rule
1301:7-7-80
of the Administrative Code.
(b)
805.5.2 Labeling.
The manufacturer of any seating furniture sold in this state that conforms to
the requirements of paragraph (E)(5)(a)(805.4.1) of this rule shall attach a
permanent label to the article, in plain view, no less than two inches by three
inches and the type shall be in all capital letters and no smaller than
one-eighth inch in height stating the following:
"NOTICE THIS ARTICLE IS MANUFACTURED
FOR USE IN PUBLIC OCCUPANCIES AND MEETS THE FLAMMABILITY REQUIREMENTS OF
CALIFORNIA BUREAU OF HOME FURNISHINGS AND THERMAL INSULATION TECHNICAL BULLETIN
133. HOWEVER, CARE SHOULD BE EXERCISED NEAR OPEN FLAME AND WITH BURNING
CIGARETTES."
(c)
805.5.3 Testing. The state fire marshal may inspect any
testing of seating furniture conducted to determine compliance with the
flammability standards of this rule.
(d)
805.5.4 Research
reports. When deemed necessary, the state fire marshal shall require the
submission of authenticated research reports to verify that the seating
furniture complies with the flammability standards.
(F)
Section 806 Decorative vegetation in new and existing
buildings
(1)806.1 Natural cut trees. Natural cut trees, where allowed by
this paragraph, shall have the trunk bottoms cut off not less than 0.5 inch (
12.7 mm) above the original cut and shall be placed in a support device
complying with paragraph (F)(1)(b)(806.1.2) of this rule.
(a)
806.1.1
Restricted occupancies. Natural cut trees shall be prohibited within ambulatory
care facilities and Group A, E, I-1, I-2, I-3, I-4, M, R-1, R-2 and R-4
occupancies.
Exceptions:
1.
Trees located in
areas protected by an approved automatic sprinkler system installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2)
of rule
1301:7-7-09
of the Administrative Code shall not be prohibited in Groups A, E, M, R-1 and
R-2.
2.
Trees shall be allowed within dwelling units in Group
R-2 occupancies.
(b)
806.1.2 Support
devices. The support device that holds the tree in an upright position shall be
of a type that is stable and that meets all of the following criteria:
(i)
The device shall
hold the tree securely and be of adequate size to avoid tipping over of the
tree.
(ii)
The device shall be capable of containing a minimum
two-day supply of water.
(iii)
The water
level, when full, shall cover the tree stem not less than 2 inches (51 mm). The
water level shall be maintained above the fresh cut and checked not less than
once daily.
(c)
806.1.3 Dryness. The tree shall be removed from the
building whenever the needles or leaves fall off readily when a tree branch is
shaken or if the needles are brittle and break when bent between the thumb and
index finger. The tree shall be checked daily for dryness.
(2)
806.2
Artificial vegetation. Artificial decorative vegetation shall meet the flame
propagation performance criteria of Test Method 1 or Test Method 2, as
appropriate, of NFPA 701 as listed in rule
1301:7-7-80
of the Administrative Code. Meeting the flame propagation performance criteria
of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 as listed in
rule 1301:7-7-80 of the Administrative Code shall be documented and certified
by the manufacturer in an approved manner. Alternatively, the artificial
decorative vegetation item shall be tested in accordance with NFPA 289 as
listed in rule 1301:7-7-80 of the Administrative Code, using the 20 kW ignition
source and shall have a maximum heat release rate of 100 kW.
(3)
806.3 Obstruction
of means of egress. The required width of any portion of a means of egress
shall not be obstructed by decorative vegetation. Natural cut trees shall not
be located within an exit, corridor, or a lobby or vestibule.
(4)
806.4 Open flame.
Candles and open flames shall not be used on or near decorative vegetation.
Natural cut trees shall be kept a distance from heat vents and any open flame
or heat-producing devices at least equal to the height of the
tree.
(5)
806.5 Electrical fixtures and wiring. The use of
unlisted electrical wiring and lighting on natural cut trees and artificial
decorative vegetation shall be prohibited. The use of electrical wiring and
lighting on artificial trees constructed entirely of metal shall be
prohibited.
(G)
Section 807 Decorative materials other than decorative
vegetation in new and existing buildings
(1)
807.1 General.
Combustible decorative materials, other than decorative vegetation, shall
comply with paragraphs (G)(2)( 807.2) to (G)(5)(f)(807.5.6) of this
rule.
(2)
807.2 Limitations. The following requirements shall
apply to all occupancies:
(a)
Furnishings or decorative materials of an explosive or
highly flammable character shall not be used.
(b)
Fire-retardant
coatings in existing buildings shall be maintained so as to retain the
effectiveness of the treatment under service conditions encountered in actual
use.
(c)
Furnishings or other objects shall not be placed to
obstruct exits, access thereto, egress therefrom or visibility
thereof
(d)The permissible amount of noncombustible decorative
materials shall not be limited.
(3)
807.3 Combustible
decorative materials. In other than Group I-3, curtains, draperies, fabric
hangings and other similar combustible decorative materials suspended from
walls or ceilings shall comply with paragraph (G)(4)( 807.4) of this rule and
shall not exceed 10 per cent of the specific wall or ceiling area to which they
are attached.
Fixed or movable walls and partitions,
paneling, wall pads and crash pads, applied structurally or for decoration,
acoustical correction, surface insulation or other purposes, shall be
considered interior finish, shall comply with paragraph (C)(803) of this rule
and shall not be considered decorative materials or furnishings.
Exceptions:
1.
In auditoriums of
Group A, the permissible amount of curtains, draperies, fabric hangings and
other similar combustible decorative material suspended from walls or ceilings
shall not exceed 75 per cent of the aggregate wall area where the building is
equipped throughout with an approved automatic sprinkler system in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code, and where the material is installed in accordance
with section 803.13 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
2.
In Group R-2
dormitories, within sleeping units and dwelling units, the permissible amount
of curtains, draperies, fabric hangings and other similar decorative materials
suspended from walls or ceilings shall not exceed 50 per cent of the aggregate
wall areas where the building is equipped throughout with an approved automatic
sprinkler system installed in accordance with paragraph (C)(3)(a)(903.3.1) of
rule
1301:7-7-09
of the Administrative Code.
3.
In Group B and M
occupancies, the amount of combustible fabric partitions suspended from the
ceiling and not supported by the floor shall comply with paragraph (G)(4)(
807.4) of this rule and shall not be limited.
(4)
807.4 Acceptance
criteria and reports. Where required to exhibit improved fire performance,
curtains, draperies, fabric hangings and other similar combustible decorative
materials suspended from walls or ceilings shall be tested by an approved
agency and meet the flame propagation performance criteria of Test Method 1 or
Test Method 2, as appropriate, of NFPA 701 as listed in rule
1301:7-7-80
of the Administrative Code, or exhibit a maximum rate of heat release of 100 kW
when tested in accordance with NFPA 289 as listed in rule
1301:7-7-80
of the Administrative Code, using the 20 kW ignition source. Reports of test
results shall be prepared in accordance with the test method used and furnished
to the fire code official upon request.
(5)
807.5
Occupancy-based requirements. In occupancies specified, combustible decorative
materials not complying with paragraph (G)(3)( 807.3) of this rule shall
comply with paragraphs (G)(5)(a)(807.5.1) to (G)(5)(f)(807.5.6) of this
rule.
(a)
807.5.1 Group A. In Group A occupancies, the requirements in
paragraphs (G)(5)(a)(i)(807.5.1.1) to (G)(5)(a)(iv)(807.5.1.4) of this rule
shall apply.
(i)
807.5.1.1 Foam plastics. Exposed foam plastic materials
and unprotected materials containing foam plastic used for decorative purposes
or stage scenery or exhibit booths shall have a maximum heat release rate of
100 kW when tested in accordance with UL 1975 as listed in rule
1301:7-7-80
of the Administrative Code or when tested in accordance with NFPA 289 as listed
in rule 1301:7-7-80 of the Administrative Code using the 20 kW ignition
source.
Exceptions:
1.
Individual foam
plastic items or items containing foam plastic where the foam plastic does not
exceed 1 pound ( 0.45 kg) in weight.
2.
Cellular or foam
plastic shall be allowed for trim in accordance with paragraph (D)(2)( 804.2)
of this rule.
(ii)
807.5.1.2 Motion picture screens. The screens upon
which motion pictures are projected in new and existing buildings of Group A
shall either meet the flame propagation performance criteria of Test Method 1
or Test Method 2, as appropriate, of NFPA 701 as listed in rule 1301:7-7-80 of
the Administrative Code, or shall comply with the requirements for a Class B
interior finish in accordance with section 803 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code.
(iii)
807.5.1.3 Wood
use in places of religious worship. In places of religious worship, wood used
for ornamental purposes, trusses, paneling or chancel furnishing shall not be
limited.
(iv)
807.5.1.4 Pyroxylin plastic. Imitation leather or other
material consisting of or coated with a pyroxylin or similarly hazardous base
shall not be used.
(b)
807.5.2 Group E.
Group E occupancies shall comply with paragraphs (G) (5)(b)(i)(807.5.2.1) and
(G)(5)(b)(iii)(807.5.2.3) of this rule.
(i)
807.5.2.1 Storage
in corridors and lobbies. Clothing and personal effects shall not be stored in
corridors and lobbies.
Exceptions:
1.
Corridors
protected by an approved automatic sprinkler system installed in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
2.
Corridors
protected by an approved fire alarm system installed in accordance with
paragraph (G)(907) of rule
1301:7-7-09
of the Administrative Code.
3.
Storage in metal
lockers, provided the minimum required egress width is
maintained.
(ii)
807.5.2.2 Artwork in corridors. Artwork and teaching
materials shall be limited on the walls of corridors to not more than 20 per
cent of the wall area.
(iii)
807.5.2.3 Artwork in classrooms. Artwork and teaching
materials shall be limited on walls of classrooms to not more than 50 per cent
of the specific wall area to which they are attached.
(c)
807.5.3 Group I-1 and I-2. In Group I-1 and I-2 occupancies,
combustible decorative materials shall comply with paragraphs
(G)(5)(c)(i)(807.5.3.1) to (G)(5)(c)(iv)(807.5.3.4) of this rule.
(i)
807.5.3.1 Group
I-1 and I-2 Condition 1 within units. In Group I-1 and Group I-2 Condition 1
occupancies, equipped throughout with an approved automatic sprinkler system
installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code, within sleeping units and dwelling units,
combustible decorative materials placed on walls shall be limited to not more
than 50 per cent of the wall area to which they are attached.
(ii)
807.5.3.2 In
Group I-1 and I-2 Condition 1 for areas other than within the units. In Group
I-1 and Group I-2 Condition 1 occupancies, equipped throughout with an approved
automatic sprinkler system installed in accordance with paragraph (C)(3)
(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code, combustible decorative materials placed on walls in
areas other than within dwelling and sleeping units shall be limited to not
more than 30 per cent of the wall area to which they are
attached.
(iii)
807.5.3.3 In Group I-2 Condition 2. In Group I-2
Condition 2 occupancies, equipped throughout with an approved automatic
sprinkler system installed in accordance with paragraph (C)(3)
(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code, combustible decorative materials placed on walls
shall be limited to not more than 30 per cent of the wall area to which they
are attached.
(iv)
807.5.3.4 Other areas in Groups I-1 and I-2. In Group
I-1 and I-2 occupancies, in areas not equipped throughout with an approved
automatic sprinkler system, combustible decorative materials shall be of such
limited quantities that a hazard of fire development or spread is not
present.
(d)
807.5.4 Group I-3. In Group I-3, combustible decorative
materials are prohibited.
(e)
807.5.5 Group I-4. Group I-4 occupancies shall comply
with the requirements in paragraphs (G)(5)(e)(i)(807.5.5.1) to (G)(5)(e)(iii)
(807.5.5.3) of this rule.
(i)
807.5.5.1 Storage in corridors and lobbies. Clothing
and personal effects shall not be stored in corridors and lobbies.
Exceptions:
1.
Corridors
protected by an approved automatic sprinkler system installed in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
2.
Corridors
protected by an approved fire alarm system installed in accordance with
paragraph (G)(907) of rule
1301:7-7-09
of the Administrative Code.
3.
Storage in metal
lockers, provided the minimum required egress width is
maintained.
(ii)
807.5.5.2 Artwork in corridors. Artwork and teaching
materials shall be limited on walls of corridors to not more than 20 per cent
of the wall area.
(iii)
807.5.5.3 Artwork in classrooms. Artwork and teaching
materials shall be limited on walls of classrooms to not more than 50 per cent
of the specific wall area to which they are attached.
(f)
807.5.6 Dormitories in Group R-2. In Group R-2 dormitories,
within sleeping units and dwelling units, the combustible decorative materials
shall be of limited quantities such that a hazard of fire development or spread
is not present.
(H)
Section 808
Furnishings other than upholstered furniture and mattresses or decorative
materials in new and existing buildings
(1)
808.1
Wastebaskets and linen containers in Group I-1, I-2 and I-3 occupancies.
Wastebaskets, linen containers and other waste containers, including their
lids, located in Group I-1, I-2 and I-3 occupancies shall be constructed of
noncombustible materials or of materials that meet a peak rate of heat release
not exceeding 300 kW/m2 when tested in accordance
with ASTM E 1354 as listed in rule
1301:7-7-80
of the Administrative Code at an incident heat flux of 50
kW/m2 in the horizontal orientation. Metal
wastebaskets and other metal waste containers with a capacity of 20 gallons (
75.7 L) or more shall be listed in accordance with UL 1315 as listed in rule
1301:7-7-80
of the Administrative Code and shall be provided with a noncombustible lid.
Portable containers exceeding 32 gallons (121 L) shall be stored in an area
classified as a waste and linen collection room and constructed in accordance
with Table 508.2 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
808.2 Waste
containers with a capacity of 20 gallons or more in Group R-2 college and
university dormitories. Waste containers, including their lids, located in
Group R-2 college and university dormitories, and with a capacity of 20 gallons
( 75.7 L) or more, shall be constructed of noncombustible materials or of
materials that meet a peak rate of heat release not exceeding 300
kW/m2 when tested in accordance with ASTM E 1354 as
listed in rule
1301:7-7-80
of the Administrative Code at an incident heat flux of 50
kW/m2 in the horizontal orientation. Metal
wastebaskets and other metal waste containers with a capacity of 20 gallons (
75.7 L) or more shall be listed in accordance with UL 1315 as listed in rule
1301:7-7-80
of the Administrative Code and shall be provided with a noncombustible lid.
Portable containers exceeding 32 gallons (121 L) shall be stored in an area
classified as a waste and linen collection room constructed in accordance with
Table 509 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(3)
808.3 Signs. Foam
plastic signs that are not affixed to interior building surfaces shall have a
maximum heat release rate of 150 kW when tested in accordance with UL 1975 as
listed in rule
1301:7-7-80
of the Administrative Code or when tested in accordance with NFPA 289 as listed
in rule 1301:7-7-80 of the Administrative Code using the 20 kW ignition
source.
Exception: Where the aggregate area of
foam plastic signs is less than 10 per cent of the floor area or wall area of
the room or space in which the signs are located, whichever is less, subject to
the approval of the fire code official.
(4)
808.4 Combustible
lockers. Where lockers constructed of combustible materials are used, the
lockers shall be considered interior finish and shall comply with paragraph
(C)(803) of this rule.
Exception: Lockers constructed entirely
of wood and noncombustible materials shall be permitted to be used wherever
interior finish materials are required to meet a Class C classification in
accordance with paragraph (C)(1)(a)(803.1.1) of this rule.
Replaces: 1301:7-7-08.