Ohio Administrative Code
Title 1301:7 - Division of State Fire Marshal
Chapter 1301:7-7 - Ohio Fire Code
Section 1301:7-7-06 - Building services and systems
Current through all regulations passed and filed through September 16, 2024
(A) Section 601 General
(B) Section 602 Definitions
"Battery system, stationary lead acid."
"Battery types."
[M] "Commercial cooking appliances."
"Critical circuit."
"Emergency power system."
[M] "Hood."
"Type I."
"Type II."
"Refrigerant."
"Refrigeration system."
"Standby power system."
(C) Section 603 Fuel-fired appliances
Exception: Fuel oil storage tanks with a capacity of less than 1,100 gallons and utilized for residential purposes.
Exception: The aggregate capacity limit shall be permitted to be increased to 3,000 gallons (11 356 L) of Class II or III liquid for storage in protected aboveground tanks complying with paragraph (D)(2)(i)(vi)(5704.2.9.6) of rule 1301:7-7-57 of the Administrative Code, where all of the following conditions are met:
Exception: Protected aboveground tanks complying with paragraph (D)(2)(i)(vii)(5704.2.9.7) of rule 1301:7-7-57 of the Administrative Code shall not be required to be separated from surrounding areas.
Exceptions:
Exceptions:
Exception: As allowed in section 6.20 of NFPA 58 as listed in rule 1301:7-7-80 of the Administrative Code.
(D) Section 604 Emergency and standby power systems
Exceptions:
Exception: Where the emergency power system is used for standby power or peak load shaving, such use shall be recorded and shall be allowed to be substituted for scheduled testing of the generator set, provided that appropriate records are maintained.
(E) Section 605 Electrical equipment, wiring and hazards
Exceptions:
Exception:Temporary wiring for electrical power and lighting installations is allowed during periods of construction, remodeling, repair or demolition of buildings, structures, equipment or similar activities.
Exception:The use of portable, electric space heaters in which the heating element cannot exceed a temperature of 212°F (100° C) shall be permitted in nonsleeping staff and employee areas in Group I-2 occupancies.
Exceptions:
Exception:These requirements shall not apply to structures designed and constructed in accordance with the residential code as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: These requirements shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
Exception:This requirement shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
Exception:These requirements shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
Exception:Panels and modules shall be permitted to be located up to the roof ridge where an alternative ventilation method approved by the fire chief has been provided or where the fire chief has determined vertical ventilation techniques will not be employed.
Exception:Where it is determined by the fire code official that the roof configuration is similar to that of a Group R-3 occupancy, the residential access and ventilation requirements in paragraphs (E)(11)(a)(ii)(a)(605.11.1.2.1) to (E)(11)(a)(ii)(e)(605.11.1.2.5) of this rule shall be permitted to be used.
Exception:Where either axis of the building is 250 feet (76 200 mm) or less, the clear perimeter around the edges of the roof shall be permitted to be reduced to a minimum 4 foot wide (1290 mm).
(F) Section 606 Mechanical refrigeration
Exception:This provision shall not apply to spare parts, tools and incidental materials necessary for the safe and proper operation and maintenance of the system.
Exception:Ammonia/water absorption systems containing less than 22 pounds (10 kg) of ammonia and for which the ammonia circuit is located entirely outdoors.
Exception:Ammonia machinery rooms that are provided with ventilation in accordance with section 1106.3 of the mechanical code as listed in rule 1301:7-7-80 of the Administrative Code.
(G) Section 607 Elevator operation, maintenance and fire service keys
Exceptions:
Exception:The owner shall be permitted to place the building's nonstandardized fire service elevator keys in a key box installed in accordance with paragraph (F)(1)(b)(506.1.2) of rule 1301:7-7-05 of the Administrative Code.
(H) Section 608 Stationary storage battery systems
Table 608.1 Battery requirements
Requirement |
Nonrecombinant batteries |
Recombinant batteries |
Other batteries |
||
Vented (flooded) lead acid batteries |
Vented (flooded) nickel-cadmium (Ni-Cd) batteries |
Valve regulated lead acid (VRLA) cells |
Lithium-ion cells |
Lithium Metal cells |
|
Safety caps |
Venting caps (paragraph (H)(2)(a)(608.2.1) of this rule) |
Venting caps (paragraph (H)(2)(a)(608.2.1) of this rule) |
Self-resealing flame-arresting caps (paragraph (H)(2)(b)(608.2.2) of this rule) |
No caps |
No caps |
Thermal runaway management |
Not required |
Not required |
Required (paragraph (H)(3)( 608.3) of this rule) |
Not required |
Required (paragraph (H)(3)( 608.3) of this rule) |
Spill control |
Required (paragraph (H)(5)( 608.5) of this rule) |
Required (paragraph (H)(5)( 608.5) of this rule) |
Not required |
Not required |
Not required |
Neutralization |
Required (paragraph (H)(5)(a)(608.5.1) of this rule) |
Required (paragraph (H)(5)(a)(608.5.1) of this rule) |
Required (paragraph (H)(5)(b)(608.5.2) of this rule) |
Not required |
Not required |
Ventilation |
Required (paragraphs (H)(6)(a)(608.6.1); (H)(6)(b)(608.6.2) of this rule) |
Required (paragraphs (H)(6)(a)(608.6.1); (H)(6)(b)(608.6.2) of this rule) |
Required (paragraphs (H)(6)(a)(608.6.1); (H)(6)(b)(608.6.2) of this rule) |
Not required |
Not required |
Signage |
Required (paragraph (H)(7)( 608.7) of this rule) |
Required (paragraph (H)(7)( 608.7) of this rule) |
Required (paragraph (H)(7)( 608.7) of this rule) |
Required (paragraph (H)(7)( 608.7) of this rule) |
Required (paragraph (H)(7)( 608.7) of this rule) |
Seismic protection |
Required (paragraph (H)(8)( 608.8) of this rule) |
Required (paragraph (H)(8)( 608.8) of this rule) |
Required (paragraph (H)(8)( 608.8) of this rule) |
Required (paragraph (H)(8)( 608.8) of this rule) |
Required (paragraph (H)(8)( 608.8) of this rule) |
Smoke detection |
Required (paragraph (H)(9)( 608.9) of this rule) |
Required (paragraph (H)(9)( 608.9) of this rule) |
Required (paragraph (H)(9)( 608.9) of this rule) |
Required (paragraph (H)(9)( 608.9) of this rule) |
Required (paragraph (H)(9)( 608.9) of this rule |
Exception:VRLA, lithium-ion, lithium metal polymer or other types of sealed batteries with immobilized electrolyte shall not require spill control.
Exception:Lithium-ion and lithium metal polymer batteries shall not require neutralization.
Exception:Lithium-ion and lithium metal polymer batteries shall not require additional ventilation beyond that which would normally be required for human occupancy of the space in accordance with the mechanical code as listed in rule 1301:7-7-80 of the Administrative Code.
(I) Section 609 Commercial kitchen hoods
Exception:A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm ( 0.236 m3/s) in accordance with U L 710B as listed in rule 1301:7-7-80 of the Administrative Code.
Table 609.3.3.1 Commercial cooking system inspection frequency
Type of cooking operations |
Frequency of inspection |
High-volume cooking operations such as 24-hour cooking, charbroiling or wok cooking |
3 months |
Low-volume cooking operations such as places of religious worship, seasonal businesses and senior centers |
12 months |
Cooking operations utilizing solid-fuel burning cooking appliances |
1 month |
All other cooking operations |
6 months |
(J) Section 610 Commercial kitchen cooking oil storage
(K) Section 611 Hyperbaric facilities
Replaces: 1301:7-7-06.