Current through Supplement No. 392, April, 2024
1. Prior to
performing any hydraulic fracture stimulation, including refracs, through a
frac string run inside the casing string:
a.
Remedial work must be performed on all casing strings deemed defective pursuant
to section 43-02-03-22 prior to performance at the discretion of the
director.
b. The frac string must
be either stung into a liner with the hanger/packer located in cemented casing
or run with a packer set at a minimum depth of one hundred feet [30.48 meters]
below the top of cement or a minimum depth of one hundred feet [30.48 meters]
below the top of the Inyan Kara formation, whichever is deeper.
c. The casing-frac string annulus must be
pressurized and monitored during frac operations. If there is a suspected frac
string or casing failure, the operator of the well shall verbally notify the
director as soon as practicable.
d.
An adequately sized, function tested pressure relief valve must be utilized on
the treating lines from the pumps to the wellhead, with suitable check valves
to limit the volume of flowback fluid should the relief valve open. The relief
valve must be set to limit line pressure to no more than eighty-five percent of
the internal yield pressure of the frac string.
e. An adequately sized, function tested
pressure relief valve and an adequately sized diversion line must be utilized
to divert flow from the casing to a pit or containment vessel in case of frac
string failure. The relief valve must be set to limit annular pressure to no
more than eighty-five percent of the lowest internal yield pressure of the
casing string or no greater than the pressure test on the intermediate casing,
less one hundred pounds per square inch gauge, whichever is less.
f. The surface casing must be fully open and
connected to a diversion line rigged to a pit or containment vessel.
g. An adequately sized, function tested
remote operated frac valve must be utilized at a location on the christmas tree
that provides isolation of the well bore from the treating line and must be
remotely operated from the edge of the location or other safe
distance.
h. Notify the director
within twenty-four hours after the commencement of hydraulic fracture
stimulation operations, in an electronic format approved by the director,
identifying the subject well and verifying a frac string was run in the
well.
i. Within sixty days after
the hydraulic fracture stimulation is performed, the owner, operator, or
service company shall post on the fracfocus chemical disclosure registry all
elements made viewable by the fracfocus website.
2. Prior to performing any hydraulic fracture
stimulation, including refracs, through a casing string:
a. Remedial work must be performed on all
casing strings deemed defective pursuant to section 43-02-03-22 prior to
performance at the discretion of the director.
b. The maximum treating pressure may not be
greater than eighty-five percent of the American petroleum institute rating of
the affected casing string.
c.
Casing evaluation tools to verify adequate wall thickness of any affected
casing string must be run from the wellhead to a depth as close as practicable
to one hundred feet [30.48 meters] above the completion formation and a visual
inspection with photographs shall be made of the top joint of the casing and
the wellhead flange. The visual inspection and photograph requirement may be
waived by the director for good cause.
If the casing evaluation tool or visual inspection indicates
wall thickness is below the American petroleum institute minimum or a lighter
weight of casing than the well design called for, calculations must be made to
determine the reduced pressure rating. If the reduced pressure rating is less
than the anticipated treating pressure, a frac string must be run inside the
casing.
d. Cement evaluation
tools to verify adequate cementing of each casing string shall be run from the
wellhead to a depth as close as practicable to one hundred feet [30.48 meters]
above the completion formation.
(1) If the
cement evaluation tool indicates defective casing or cementing, a frac string
must be run inside the casing.
(2)
If the cement evaluation tool indicates the casing string cemented in the well
fails to satisfy section 43-02-03-21, a frac string must be run inside the
casing.
e. Each affected
casing string and the wellhead must be pressure tested for at least thirty
minutes with less than five percent loss to a pressure equal to or in excess of
the maximum frac design pressure.
f. If the pressure rating of the wellhead
does not exceed the maximum frac design pressure, a wellhead and blowout
preventer protection system must be utilized during the frac.
g. An adequately sized, function tested
pressure relief valve must be utilized on the treating lines from the pumps to
the wellhead, with suitable check valves to limit the volume of flowback fluid
should be the relief valve open. The relief valve must be set to limit line
pressure to no greater than the test pressure of the casing, less one hundred
pounds per square inch [689.48 kilopascals].
h. The surface casing value must be fully
open and connected to a diversion line rigged to a pit or containment
vessel.
i. An adequately sized,
function tested remote operated frac valve must be utilized between the
treating line and the wellhead.
j.
If there is a suspected casing failure, the operator of the well shall verbally
notify the director as soon as practicable.
k. Notify the director within twenty-four
hours after the commencement of hydraulic fracture stimulation operations, in
an electronic format approved by the director, identifying the subject well and
verifying all logs and pressure tests have been performed as
required.
l. Within sixty days
after the hydraulic fracture stimulation is performed, the owner, operator, or
service company shall post on the fracfocus chemical disclosure registry all
elements made viewable by the fracfocus website.
3. If during the stimulation, the pressure in
the casing-surface casing annulus exceeds three hundred fifty pounds per square
inch [2413 kilopascals] gauge, the owner or operator shall verbally notify the
director as soon as practicable but no later than twenty-four hours following
the incident.
General Authority: NDCC 38-08-04
Law Implemented: NDCC
38-08-04