North Dakota Administrative Code
Title 33.1 - Department of Environmental Quality
Article 33.1-24 - Hazardous Waste Management
Chapter 33.1-24-05 - Standards for Treatment, Storage, and Disposal Facilities and for the Management of Specific Hazardous Wastes and Specific Types of Hazardous Waste Management Facilities
STANDARDS FOR FACILITIES OPERATING UNDER A STANDARDIZED PERMIT
Section 33.1-24-05-1107 - Requirements for ancillary equipment
Current through Supplement No. 395, January, 2025
An owner or operator must provide ancillary equipment with secondary containment (for example, trench, jacketing, double-walled piping) that meets the requirements of subsections 1 and 2 of section 33.1-24-05-1105, except for:
1. Aboveground piping (exclusive of flanges, joints, valves, and other connections) that are visually inspected for leaks on a daily basis;
2. Welded flanges, welded joints, and welded connections, that are visually inspected for leaks on a daily basis;
3. Sealless or magnetic coupling pumps and sealless valves, that are visually inspected for leaks on a daily basis; and
4. Pressurized aboveground piping systems with automatic shutoff devices (for example, excess flow check valves, flow metering shutdown devices, loss of pressure actuated shutoff devices) that are visually inspected for leaks on a daily basis.
General Authority: NDCC 23.1-04-03; S.L. 2017, ch. 199, § 1
Law Implemented: NDCC 23.1-04-03, 23.1-04-05, 23.1-04-08; S.L. 2017, ch. 199, § 19