Current through Supplement No. 395, January, 2025
1. The provisions
of this section apply to the control of air pollutant emissions from tanks for
which subsection 2 of section
33.1-24-05-452 references the
use of this section for such air emission control.
2. The owner or operator shall control air
pollutant emissions from each tank subject to this section in accordance with
the following requirements as applicable:
a.
For a tank that manages hazardous waste that meets all of the conditions
specified in paragraphs 1 through 3, the owner or operator shall control air
pollutant emissions from the tank in accordance with the tank level 1 controls
specified in subsection 3 or the tank level 2 controls specified in subsection
4.
(1) The hazardous waste in the tank has a
maximum organic vapor pressure which is less than the maximum organic vapor
pressure limit for the tank's design capacity category as follows:
(a) For a tank design capacity equal to or
greater than 5,330 feet3 [151
meters3], the maximum organic vapor pressure limit
for the tank is 5.2 kilopascals.
(b) For a tank design capacity equal to or
greater than 2,650 feet3 [75
meters3] but less than 5,330
feet3 [151 meters3], the
maximum organic vapor pressure limi t for the tank is 27.6
kilopascals.
(c) For a tank design
capacity less than 2,650 feet3 [75
meters3], the maximum organic vapor pressure limit
for the tank is 76.6 kilopascals.
(2) The hazardous waste in the tank is not
heated by the owner or operator to a temperature that is greater than the
temperature at which the maximum organic vapor pressure of the hazardous waste
is determined for the purpose of complying with paragraph 1.
(3) The hazardous waste in the tank is not
treated by the owner or operator using a waste stabilization process, as
defined in section
33.1-24-05-451.
b. For a tank that manages hazardous waste
that does not meet all of the conditions specified in paragraphs 1 through 3 of
subdivision a, the owner or operator shall control air pollutant emissions from
the tank by using tank level 2 controls in accordance with the requirements of
subsection 4. Examples of tanks required to use tank level 2 controls include a
tank used for a waste stabilization process; and a tank for which the hazardous
waste in the tank has a maximum organic vapor pressure that is equal to or
greater than the maximum organic vapor pressure limit for the tank's design
capacity category as specified in paragraph 1 of subdivision a.
3. Owners and operators
controlling air pollutant emissions from a tank using tank level 1 controls
shall meet the requirements specified in subdivisions a through d:
a. The owner or operator shall determine the
maximum organic vapor pressure for a hazardous waste to be managed in the tank
using tank level 1 controls before the first time the hazardous waste is placed
in the tank. The maximum organic vapor pressure must be determined using the
procedures specified in subsection 3 of section
33.1-24-05-453. Thereafter, the
owner or operator shall perform a new determination whenever changes to the
hazardous waste managed in the tank could potentially cause the maximum organic
vapor pressure to increase to a level that is equal to or greater than the
maximum organic vapor pressure limit for the tank design capacity category
specified in paragraph 1 of subdivision a of subsection 2, as applicable to the
tank.
b. The tank must be equipped
with a fixed roof designed to meet the following specifications:
(1) The fixed roof and its closure devices
must be designed to form a continuous barrier over the entire surface area of
the hazardous waste in the tank. The fixed roof may be a separate cover
installed on the tank (for example, a removable cover mounted on an open-top
tank) or may be an integral part of the tank structural design (for example, a
horizontal cylindrical tank equipped with a hatch).
(2) The fixed roof must be installed in a
manner such that there are no visible cracks, holes, gaps, or other open spaces
between roof section joints or between the interface of the roof edge and the
tank wall.
(3) Each opening in the
fixed roof, and any manifold system associated with the fixed roof, must be
either:
(a) Equipped with a closure device
designed to operate such that when the closure device is secured in the closed
position there are no visible cracks, holes, gaps, or other open spaces in the
closure device or between the perimeter of the opening and the closure device;
or
(b) Connected by a closed-vent
system that is vented to a control device. The control device must remove or
destroy organics in the vent stream, and must be operating whenever hazardous
waste is managed in the tank, except as provided for in items 1 and 2.
[1] During periods when it is necessary to
provide access to the tank for performing the activities of item 2, venting of
the vapor headspace underneath the fixed roof to the control device is not
required, opening of closure devices is allowed, and removal of the fixed roof
is allowed. Following completion of the activity, the owner or operator shall
promptly secure the closure device in the closed position or reinstall the
cover, as applicable, and resume operation of the control device.
[2] During periods of routine inspection,
maintenance, or other activities needed for normal operations, and for removal
of accumulated sludge or other residues from the bottom of the tank.
(4) The fixed roof and
its closure devices must be made of suitable materials that will minimize
exposure of the hazardous waste to the atmosphere, to the extent practical, and
will maintain the integrity of the fixed roof and closure devices throughout
their intended service life. Factors to be considered when selecting the
materials for and designing the fixed roof and closure devices include organic
vapor permeability, the effects of any contact with the hazardous waste or its
vapors managed in the tank; the effects of outdoor exposure to wind, moisture,
and sunlight; and the operating practices used for the tank on which the fixed
roof is installed.
c.
Whenever a hazardous waste is in the tank, the fixed roof must be installed
with each closure device secured in the closed position except as follows:
(1) Opening of closure devices or removal of
the fixed roof is allowed at the following times:
(a) To provide access to the tank for
performing routine inspection, maintenance, or other activities needed for
normal operations. Examples of such activities include those times when a
worker needs to open a port to sample the liquid in the tank, or when a worker
needs to open a hatch to maintain or repair equipment. Following completion of
the activity, the owner or operator shall promptly secure the closure device in
the closed position or reinstall the cover, as applicable, to the
tank.
(b) To remove accumulated
sludge or other residues from the bottom of the tank.
(2) Opening of a spring-loaded
pressure-vacuum relief valve, conservation vent, or similar type of pressure
relief device which vents to the atmosphere is allowed during normal operations
for the purpose of maintaining the tank internal pressure in accordance with
the tank design specifications. The device must be designed to operate with no
detectable organic emissions when the device is secured in the closed position.
The settings at which the device opens must be established such that the device
remains in the closed position whenever the tank internal pressure is within
the internal pressure operating range determined by the owner or operator based
on the tank manufacturer recommendations, applicable regulations, fire
protection and prevention codes, standard engineering codes and practices, or
other requirements for the safe handling of flammable, ignitable, explosive,
reactive, or hazardous materials. Examples of normal operating conditions that
may require these devices to open are during those times when the tank internal
pressure exceeds the internal pressure operating range for the tank as a result
of loading operations or diurnal ambient temperature fluctuations.
(3) Opening of a safety device, as defined in
section 33.1-24-05-451, is allowed at
any time conditions require doing so to avoid an unsafe
condition.
d. The owner
or operator shall inspect the air emission control equipment in accordance with
the following requirements:
(1) The fixed
roof and its closure devices must be visually inspected by the owner or
operator to check for defects that could result in air pollutant emissions.
Defects include visible cracks, holes, or gaps in the roof sections or between
the roof and the tank wall; broken, cracked, or otherwise damaged seals or
gaskets on closure devices; and broken or missing hatches, access covers, caps,
or other closure devices.
(2) The
owner or operator shall perform an initial inspection of the fixed roof and its
closure devices on or before the date that the tank becomes subject to this
section. Thereafter, the owner or operator shall perform the inspections at
least once every year except under the special conditions provided for in
subsection 12.
(3) In the event
that a defect is detected, the owner or operator shall repair the defect in
accordance with the requirements of subsection 11.
(4) The owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in
subsection 2 of section
33.1-24-05-459.
4. Owners and operators controlling air
pollutant emissions from a tank using tank level 2 controls shall use one of
the following tanks:
a. A fixed-roof tank
equipped with an internal floating roof in accordance with the requirements
specified in subsection 5;
b. A
tank equipped with an external floating roof in accordance with the
requirements specified in subsection 6;
c. A tank vented through a closed-vent system
to a control device in accordance with the requirements specified in subsection
7;
d. A pressure tank designed and
operated in accordance with the requirements specified in subsection 8;
or
e. A tank located inside an
enclosure that is vented through a closed-vent system to an enclosed combustion
control device in accordance with the requirements specified in subsection
9.
5. The owner or
operator who controls air pollutant emissions from a tank using a fixed-roof
with an internal floating roof shall meet the requirements specified in
subdivisions a through c.
a. The tank must be
equipped with a fixed roof and an internal floating roof in accordance with the
following requirements:
(1) The internal
floating roof must be designed to float on the liquid surface except when the
floating roof must be supported by the leg supports.
(2) The internal floating roof must be
equipped with a continuous seal between the wall of the tank and the floating
roof edge that meets either of the following requirements:
(a) A single continuous seal that is either a
liquid-mounted seal or a metallic shoe seal, as defined in section
33.1-24-05-451; or
(b) Two continuous seals mounted one above
the other. The lower seal may be a vapor-mounted seal.
(3) The internal floating roof must meet the
following specifications:
(a) Each opening in
a noncontact internal floating roof except for automatic bleeder vents (vacuum
breaker vents) and the rim space vents is to provide a projection below the
liquid surface.
(b) Each opening in
the internal floating roof must be equipped with a gasketed cover or a gasketed
lid except for leg sleeves, automatic bleeder vents, rim space vents, column
wells, ladder wells, sample wells, and stub drains.
(c) Each penetration of the internal floating
roof for the purpose of sampling must have a slit fabric cover that covers at
least ninety percent of the opening.
(d) Each automatic bleeder vent and rim space
vent must be gasketed.
(e) Each
penetration of the internal floating roof that allows for passage of a ladder
must have a gasketed sliding cover.
(f) Each penetration of the internal floating
roof that allows for passage of a column supporting the fixed roof must have a
flexible fabric sleeve seal or a gasketed sliding
cover.
b. The
owner or operator shall operate the tank in accordance with the following
requirements:
(1) When the floating roof is
resting on the leg supports, the process of filling, emptying, or refilling
shall be continuous and must be completed as soon as practical.
(2) Automatic bleeder vents are to be set
closed at all times when the roof is floating, except when the roof is being
floated off or is being landed on the leg supports.
(3) Prior to filling the tank, each cover,
access hatch, gauge float well, or lid on any opening in the internal floating
roof must be bolted or fastened closed (for example, no visible gaps). Rim
space vents are to be set to open only when the internal floating roof is not
floating or when the pressure beneath the rim exceeds the manufacturer's
recommended setting.
c.
The owner or operator shall inspect the internal floating roof in accordance
with the procedures specified as follows:
(1)
The floating roof and its closure devices must be visually inspected by the
owner or operator to check for defects that could result in air pollutant
emissions. Defects include the internal floating roof is not floating on the
surface of the liquid inside the tank; liquid has accumulated on top of the
internal floating roof; any portion of the roof seals have detached from the
roof rim; holes, tears, or other openings are visible in the seal fabric; the
gaskets no longer close off the hazardous waste surface from the atmosphere; or
the slotted membrane has more than ten percent open area.
(2) The owner or operator shall inspect the
internal floating roof components as follows except as provided in paragraph 3:
(a) Visually inspect the internal floating
roof components through openings on the fixed roof (for example, manholes and
roof hatches) at least once every twelve months after initial fill;
and
(b) Visually inspect the
internal floating roof, primary seal, secondary seal (if one is in service),
gaskets, slotted membranes, and sleeve seals (if any) each time the tank is
emptied and degassed and at least every ten years.
(3) As an alternative to performing the
inspection specified in paragraph 2 for an internal floating roof equipped with
two continuous seals mounted one above the other, the owner or operator may
visually inspect the internal floating roof, primary and secondary seals,
gaskets, slotted membranes, and sleeve seals (if any) each time the tank is
emptied and degassed and at least every five years.
(4) Prior to each inspection required by
paragraph 2 or 3, the owner or operator shall notify the department in advance
of each inspection to provide the department with the opportunity to have an
observer present during the inspection. The owner or operator shall notify the
department of the date and location of the inspection as follows:
(a) Prior to each visual inspection of an
internal floating roof in a tank that has been emptied and degassed, written
notification must be prepared and sent by the owner or operator so that it is
received by the department at least thirty calendar days before refilling the
tank except when an inspection is not planned as provided for in subparagraph
b.
(b) When a visual inspection is
not planned and the owner or operator could not have known about the inspection
thirty calendar days before refilling the tank, the owner or operator shall
notify the department as soon as possible, but no later than seven calendar
days before refilling of the tank. This notification may be made by telephone
and immediately followed by a written explanation for why the inspection is
unplanned. Alternatively, written notification, including the explanation for
the unplanned inspection, may be sent so that it is received by the department
at least seven calendar days before refilling the tank.
(5) In the event that a defect is detected,
the owner or operator shall repair the defect in accordance with the
requirements of subsection 11.
(6)
The owner or operator shall maintain a record of the inspection in accordance
with the requirements specified in subsection 2 of section
33.1-24-05-459.
d. Safety devices, as defined in section
33.1-24-05-451, may be installed
and operated as necessary on any tank complying with the requirements of this
subsection.
6. The owner
or operator who controls air pollutant emissions from a tank using an external
floating roof shall meet the requirements specified in subdivisions a through
c.
a. The owner or operator shall design the
external floating roof in accordance with the following requirements:
(1) The external floating roof must be
designed to float on the liquid surface except when the floating roof must be
supported by the leg supports.
(2)
The floating roof must be equipped with two continuous seals, one above the
other, between the wall of the tank and the roof edge. The lower seal is
referred to as the primary seal, and the upper seal is referred to as the
secondary seal.
(a) The primary seal must be
a liquid-mounted seal or a metallic shoe seal, as defined in section
33.1-24-05-451. The total area
of the gaps between the tank wall and the primary seal may not exceed 10.0
inches2 per foot [212 square centimeters per meter]
of tank diameter, and the width of any portion of these gaps may not exceed 1.5
inches [3.8 centimeters]. If a metallic shoe seal is used for the primary seal,
the metallic shoe seal must be designed so that one end extends into the liquid
in the tank and the other end extends a vertical distance of at least sixty-one
centimeters above the liquid surface.
(b) The secondary seal must be mounted above
the primary seal and cover the annular space between the floating roof and the
wall of the tank. The total area of the gaps between the tank wall and the
secondary seal may not exceed 1.0 inches2 per foot
[21.2 square centimeters per meter] of tank diameter, and the width of any
portion of these gaps must not exceed 0.5 inches [1.3
centimeters].
(3) The
external floating roof must meet the following specifications:
(a) Except for automatic bleeder vents
(vacuum breaker vents) and rim space vents, each opening in a noncontact
external floating roof must provide a projection below the liquid
surface.
(b) Except for automatic
bleeder vents, rim space vents, roof drains, and leg sleeves, each opening in
the roof must be equipped with a gasketed cover, seal, or lid.
(c) Each access hatch and each gauge float
well must be equipped with a cover designed to be bolted or fastened when the
cover is secured in the closed position.
(d) Each automatic bleeder vent and each rim
space vent must be equipped with a gasket.
(e) Each roof drain that empties into the
liquid managed in the tank must be equipped with a slotted membrane fabric
cover that covers at least ninety percent of the area of the opening.
(f) Each unslotted and slotted guide pole
well must be equipped with a gasketed sliding cover or a flexible fabric sleeve
seal.
(g) Each unslotted guide pole
must be equipped with a gasketed cap on the end of the pole.
(h) Each slotted guide pole must be equipped
with a gasketed float or other device which closes off the liquid surface from
the atmosphere.
(i) Each gauge
hatch and each sample well must be equipped with a gasketed cover.
b. The owner or operator
shall operate the tank in accordance with the following requirements:
(1) When the floating roof is resting on the
leg supports, the process of filling, emptying, or refilling must be continuous
and must be completed as soon as practical.
(2) Except for automatic bleeder vents, rim
space vents, roof drains, and leg sleeves, each opening in the roof must be
secured and maintained in a closed position at all times except when the
closure device must be open for access.
(3) Covers on each access hatch and each
gauge float well must be bolted or fastened when secured in the closed
position.
(4) Automatic bleeder
vents must be set closed at all times when the roof is floating, except when
the roof is being floated off or is being landed on the leg supports.
(5) Rim space vents must be set to open only
at those times that the roof is being floated off the roof leg supports or when
the pressure beneath the rim seal exceeds the manufacturer's recommended
setting.
(6) The cap on the end of
each unslotted guide pole must be secured in the closed position at all times
except when measuring the level or collecting samples of the liquid in the
tank.
(7) The cover on each gauge
hatch or sample well must be secured in the closed position at all times except
when the hatch or well must be opened for access.
(8) Both the primary seal and the secondary
seal must completely cover the annular space between the external floating roof
and the wall of the tank in a continuous fashion except during
inspections.
c. The owner
or operator shall inspect the external floating roof in accordance with the
procedures specified as follows:
(1) The
owner or operator shall measure the external floating roof seal gaps in
accordance with the following requirements:
(a) The owner or operator shall perform
measurements of gaps between the tank wall and the primary seal within sixty
calendar days after initial operation of the tank following installation of the
floating roof and, thereafter, at least once every five years.
(b) The owner or operator shall perform
measurements of gaps between the tank wall and the secondary seal within sixty
calendar days after initial operation of the tank following installation of the
floating roof and, thereafter, at least once every year.
(c) If a tank ceases to hold hazardous waste
for a period of one year or more, subsequent introduction of hazardous waste
into the tank must be considered an initial operation for the purposes of
subparagraphs a and b.
(d) The
owner or operator shall determine the total surface area of gaps in the primary
seal and in the secondary seal individually using the following procedure:
[1] The seal gap measurements must be
performed at one or more floating roof levels when the roof is floating off the
roof supports.
[2] Seal gaps, if
any, must be measured around the entire perimeter of the floating roof in each
place where a 0.125-inch [0.32-centimeter] diameter uniform probe passes freely
(without forcing or binding against the seal) between the seal and the wall of
the tank and measure the circumferential distance of each such
location.
[3] For a seal gap
measured under this subdivision, the gap surface area must be determined by
using probes of various widths to measure accurately the actual distance from
the tank wall to the seal and multiplying each such width by its respective
circumferential distance.
[4] The
total gap area must be calculated by adding the gap surface areas determined
for each identified gap location for the primary seal and the secondary seal
individually, and then dividing the sum for each seal type by the nominal
diameter of the tank. These total gap areas for the primary seal and secondary
seal are then compared to the respective standards for the seal type as
specified in paragraph 2 of subdivision a.
(e) If the seal gap measurements do not
conform to the specifications in paragraph 2 of subdivision a, the owner or
operator shall repair the defect in accordance with the requirements of
subsection 11.
(f) The owner or
operator shall maintain a record of the inspection in accordance with the
requirements specified in subsection 2 of section
33.1-24-05-459.
(2) The owner or operator shall
visually inspect the external floating roof in accordance with the following
requirements:
(a) The floating roof and its
closure devices must be visually inspected by the owner or operator to check
for defects that could result in air pollutant emissions. Defects include
holes, tears, or other openings in the rim seal or seal fabric of the floating
roof; a rim seal detached from the floating roof; all or a portion of the
floating roof deck being submerged below the surface of the liquid in the tank;
broken, cracked, or otherwise damaged seals or gaskets on closure devices; and
broken or missing hatches, access covers, caps, or other closure
devices.
(b) The owner or operator
shall perform an initial inspection of the external floating roof and its
closure devices on or before the date that the tank becomes subject to this
section. Thereafter, the owner or operator shall perform the inspections at
least once every year except for the special conditions provided for in
subsection 12.
(c) If a defect is
detected, the owner or operator shall repair the defect in accordance with the
requirements of subsection 11.
(d)
The owner or operator shall maintain a record of the inspection in accordance
with the requirements specified in subsection 2 of section
33.1-24-05-459.
(3) Prior to each inspection required by
paragraph 1 or 2, the owner or operator shall notify the department in advance
of each inspection to provide the department with the opportunity to have an
observer present during the inspection. The owner or operator shall notify the
department of the date and location of the inspection as follows:
(a) Prior to each inspection to measure
external floating roof seal gaps as required under paragraph 1, written
notification must be prepared and sent by the owner or operator so that it is
received by the department at least thirty calendar days before the date the
measurements are scheduled to be performed.
(b) Prior to each visual inspection of an
external floating roof in a tank that has been emptied and degassed, written
notification must be prepared and sent by the owner or operator so that it is
received by the department at least thirty calendar days before refilling the
tank except when an inspection is not planned as provided for in subparagraph
c.
(c) When a visual inspection is
not planned and the owner or operator could not have known about the inspection
thirty calendar days before refilling the tank, the owner or operator shall
notify the department as soon as possible, but no later than seven calendar
days before refilling of the tank. This notification may be made by telephone
and immediately followed by a written explanation for why the inspection is
unplanned. Alternatively, written notification, including the explanation for
the unplanned inspection, may be sent so that it is received by the department
at least seven calendar days before refilling the tank.
d. Safety
devices, as defined in section
33.1-24-05-451, may be installed
and operated as necessary on any tank complying with the requirements of this
subsection.
7. The owner
or operator who controls air pollutant emissions from a tank by venting the
tank to a control device shall meet the requirements specified in subdivisions
a through c.
a. The tank must be covered by a
fixed roof and vented directly through a closed-vent system to a control device
in accordance with the following requirements:
(1) The fixed roof and its closure devices
must be designed to form a continuous barrier over the entire surface area of
the liquid in the tank.
(2) Each
opening in the fixed roof not vented to the control device must be equipped
with a closure device. If the pressure in the vapor headspace underneath the
fixed roof is less than atmospheric pressure when the control device is
operating, the closure devices must be designed to operate such that when the
closure device is secured in the closed position there are no visible cracks,
holes, gaps, or other open spaces in the closure device or between the
perimeter of the cover opening and the closure device. If the pressure in the
vapor headspace underneath the fixed roof is equal to or greater than
atmospheric pressure when the control device is operating, the closure device
must be designed to operate with no detectable organic emissions.
(3) The fixed roof and its closure devices
must be made of suitable materials that will minimize exposure of the hazardous
waste to the atmosphere, to the extent practical, and will maintain the
integrity of the fixed roof and closure devices throughout their intended
service life. Factors to be considered when selecting the materials for and
designing the fixed roof and closure devices include organic vapor
permeability, the effects of any contact with the liquid and its vapor managed
in the tank; the effects of outdoor exposure to wind, moisture, and sunlight;
and the operating practices used for the tank on which the fixed roof is
installed.
(4) The closed-vent
system and control device must be designed and operated in accordance with the
requirements of section
33.1-24-05-457.
b. Whenever a hazardous waste is in the tank,
the fixed roof must be installed with each closure device secured in the closed
position and the vapor headspace underneath the fixed roof vented to the
control device except as follows:
(1) Venting
to the control device is not required, and opening of closure devices or
removal of the fixed roof is allowed at the following times:
(a) To provide access to the tank for
performing routine inspection, maintenance, or other activities needed for
normal operations. Examples of such activities include those times when a
worker needs to open a port to sample liquid in the tank, or when a worker
needs to open a hatch to maintain or repair equipment. Following completion of
the activity, the owner or operator shall promptly secure the closure device in
the closed position or reinstall the cover, as applicable, to the
tank.
(b) To remove accumulated
sludge or other residues from the bottom of a tank.
(2) Opening of a safety device, as defined in
section 33.1-24-05-451, is allowed at
any time conditions require doing so to avoid an unsafe
condition.
c. The owner
or operator shall inspect and monitor the air emission control equipment in
accordance with the following procedures:
(1)
The fixed roof and its closure devices must be visually inspected by the owner
or operator to check for defects that could result in air pollutant emissions.
Defects include visible cracks, holes, or gaps in the roof sections or between
the roof and the tank wall; broken, cracked, or otherwise damaged seals or
gaskets on closure devices; and broken or missing hatches, access covers, caps,
or other closure devices.
(2) The
closed-vent system and control device must be inspected and monitored by the
owner or operator in accordance with the procedures specified in section
33.1-24-05-457.
(3) The owner or operator shall perform an
initial inspection of the air emission control equipment on or before the date
that the tank becomes subject to this section. Thereafter, the owner or
operator shall perform the inspections at least once every year except for the
special conditions provided for in subsection 12.
(4) If a defect is detected, the owner or
operator shall repair the defect in accordance with the requirements of
subsection 11.
(5) The owner or
operator shall maintain a record of the inspection in accordance with the
requirements specified in subsection 2 of section
33.1-24-05-459.
8. The owner or operator
who controls air pollutant emissions by using a pressure tank shall meet the
following requirements:
a. The tank must be
designed not to vent to the atmosphere as a result of compression of the vapor
headspace in the tank during filling of the tank to its design
capacity.
b. All tank openings must
be equipped with closure devices designed to operate with no detectable organic
emissions as determined using the procedure specified in subsection 4 of
section 33.1-24-05-453.
c. Whenever a hazardous waste is in the tank,
the tank must be operated as a closed system that does not vent to the
atmosphere except under either of the following conditions as specified in
paragraph 1 or 2:
(1) At those times when
opening of a safety device, as defined in section
33.1-24-05-451, is required to
avoid an unsafe condition.
(2) At
those times when purging of inerts from the tank is required and the purge
stream is routed to a closed-vent system and control device designed and
operated in accordance with the requirements of section
33.1-24-05-457.
9. The owner or operator who controls air
pollutant emissions by using an enclosure vented through a closed-vent system
to an enclosed combustion control device shall meet the requirements specified
in subdivisions a through d.
a. The tank must
be located inside an enclosure. The enclosure must be designed and operated in
accordance with the criteria for a permanent total enclosure as specified in
"Procedure T - Criteria for and Verification of a Permanent or Temporary Total
Enclosure" under
40
CFR 52.741, appendix B. The enclosure may
have permanent or temporary openings to allow worker access; passage of
material into or out of the enclosure by conveyor, vehicles, or other
mechanical means; entry of permanent mechanical or electrical equipment; or
direct airflow into the enclosure. The owner or operator shall perform the
verification procedure for the enclosure as specified in section 5.0 to
"Procedure T - Criteria for and Verification of a Permanent or Temporary Total
Enclosure" initially when the enclosure is first installed and, thereafter,
annually.
b. The enclosure must be
vented through a closed-vent system to an enclosed combustion control device
that is designed and operated in accordance with the standards for either a
vapor incinerator, boiler, or process heater specified in section
33.1-24-05-457.
c. Safety devices, as defined in section
33.1-24-05-451, may be installed
and operated as necessary on any enclosure, closed-vent system, or control
device used to comply with the requirements of subdivisions a and b.
d. The owner or operator shall inspect and
monitor the closed-vent system and control device as specified in section
33.1-24-05-457.
10. The owner or operator shall transfer
hazardous waste to a tank subject to this section in accordance with the
following requirements:
a. Transfer of
hazardous waste, except as provided in subdivision b, to the tank from another
tank subject to this section or from a surface impoundment subject to section
33.1-24-05-455 must be conducted
using continuous hard-piping or another closed system that does not allow
exposure of the hazardous waste to the atmosphere. For the purpose of complying
with this provision, an individual drain system is considered to be a closed
system when it meets the requirements of 40 CFR part 63, subpart RR - National
Emission Standards for Individual Drain Systems.
b. The requirements of subdivision a do not
apply when transferring a hazardous waste to the tank under any of the
following conditions:
(1) The hazardous waste
meets the average VO concentration conditions specified in subdivision a of
subsection 3 of section
33.1-24-05-452 at the point of
waste origination.
(2) The
hazardous waste has been treated by an organic destruction or removal process
to meet the requirements in subdivision b of subsection 3 of section
33.1-24-05-452.
(3) The hazardous waste meets the
requirements of subdivision d of subsection 3 of section
33.1-24-05-452.
11. The owner or operator shall repair each
defect detected during an inspection performed in accordance with the
requirements of subdivision d of subsection 3, subdivision c of subsection 5,
subdivision c of subsection 6, or subdivision c of subsection 7 as follows:
a. The owner or operator shall make first
efforts at repair of the defect no later than five calendar days after
detection, and repair shall be completed as soon as possible but no later than
forty-five calendar days after detection except as provided in subdivision
b.
b. Repair of a defect may be
delayed beyond forty-five calendar days if the owner or operator determines
that repair of the defect requires emptying or temporary removal from service
of the tank and no alternative tank capacity is available at the site to accept
the hazardous waste normally managed in the tank. In this case, the owner or
operator shall repair the defect the next time the process or unit that is
generating the hazardous waste managed in the tank stops operation. Repair of
the defect shall be completed before the process or unit resumes
operation.
12. Following
the initial inspection and monitoring of the cover as required by the
applicable provisions of sections
33.1-24-05-450 through
33.1-24-05-474, subsequent
inspection and monitoring may be performed at intervals longer than one year
under the following special conditions:
a. If
inspecting or monitoring the cover would expose a worker to dangerous,
hazardous, or other unsafe conditions, then the owner or operator may designate
a cover as an "unsafe to inspect and monitor cover" and comply with all of the
following requirements:
(1) Prepare a written
explanation for the cover stating the reasons why the cover is unsafe to
visually inspect or to monitor, if required.
(2) Develop and implement a written plan and
schedule to inspect and monitor the cover, using the procedures specified in
the applicable section of sections
33.1-24-05-450 through
33.1-24-05-474, as frequently as
practicable during those times when a worker can safely access the
cover.
b. If a tank is
buried partially or entirely underground, an owner or operator is required to
inspect and monitor, as required by the applicable provisions of this section,
only those portions of the tank cover and those connections to the tank (for
example, fill ports, access hatches, gauge wells, etc.) that are located on or
above the ground surface.
General Authority: NDCC 23.1-04-03; S.L.
2017, ch. 199, § 1
Law Implemented: NDCC 23.1-04-03,
23.1-04-05; S.L. 2017, ch. 199, §
19