North Dakota Administrative Code
Title 33.1 - Department of Environmental Quality
Article 33.1-14 - NORTH DAKOTA BOILER RULES
Chapter 33.1-14-09 - HEATING, LOW PRESSURE, AND HOT WATER SUPPLY BOILERS -EXISTING INSTALLATIONS
Section 33.1-14-09-19 - Modular hot water heating boilers
Universal Citation: ND Admin Code ยง 33.1-14-09-19
Current through Supplement No. 394, October, 2024
1. Individual modules must be limited to a maximum input of four hundred thousand British thermal units [4.22 x 10 to the eighth power joules] per hour (gas), three gallons [11.36 liters] per hour (oil), or one hundred fifteen kilowatt-hours (electricity).
2. Each module of a modular hot water heating boiler must be equipped with the following:
a. Pressure/altitude gauge (see
section 33.1-14-09-12).
b.
Thermometer (see section 33.1-14-09-13).
c. Operating temperature control (see
subsection 2 of section 33.1-14-09-14).
d. Safety relief valve (see section
33.1-14-09-07).
e. Drain valve (see
section 33.1-14-09-20).
3. The assembled modular hot water heating boiler must be equipped with the following:
a. High-limit temperature control (see
subsection 1 of section 33.1-14-09-14).
b. Low-water fuel cutoff (see section
33.1-14-09-18).
c. Makeup feedwater
connection (see section 33.1-14-09-11).
d. Expansion tank provisions (see section
33.1-14-09-15).
e. Stop valves (see
section 33.1-14-09-10).
General Authority: NDCC 23.1-16
Law Implemented: NDCC 23.1-16
Disclaimer: These regulations may not be the most recent version. North Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.