Each automatically fired hot water boiler must be protected from over temperature by two temperature-operated controls.

1. Each individual automatically fired water boiler must have a safety limit control that will cut off the fuel supply to prevent water temperature from exceeding the maximum allowable temperature at the boiler outlet. The water temperature safety control must be constructed to prevent a temperature setting above the maximum allowable temperature and be of the manual reset type.

2. Each individual hot water boiler or each system of commonly connected boilers without intervening valves must have a control that will cut off the fuel supply when the water temperature reaches an operating limit, which must be less than the maximum allowable temperature.

General Authority: NDCC 23.1-16

Law Implemented: NDCC 23.1-16

Disclaimer: These regulations may not be the most recent version. North Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.