North Dakota Administrative Code
Title 33.1 - Department of Environmental Quality
Article 33.1-14 - NORTH DAKOTA BOILER RULES
Chapter 33.1-14-09 - HEATING, LOW PRESSURE, AND HOT WATER SUPPLY BOILERS -EXISTING INSTALLATIONS
Section 33.1-14-09-02 - Nonstandard riveted boilers
Universal Citation: ND Admin Code ยง 33.1-14-09-02
Current through Supplement No. 394, October, 2024
The maximum allowable working pressure on the shell of a noncode riveted heating boiler must be determined in accordance with section 33.1-14-05-01 except that the maximum allowable working pressure of a steam heating boiler may not exceed fifteen pounds [103 kilopascals] and a hot water boiler may not exceed thirty pounds [206.85 kilopascals] at a temperature not exceeding two hundred fifty degrees Fahrenheit [120 degrees Celsius].
General Authority: NDCC 23.1-16
Law Implemented: NDCC 23.1-16
Disclaimer: These regulations may not be the most recent version. North Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.