Section 33.1-14-07-10 - Flue connections

Current through Supplement No. 394, October, 2024

Each gas-fired boiler must be equipped with a four inch [10.16 centimeter] vent pipe or flue extended to an approved location outside the building or connected to a chimney flue. If the horizontal run is more than ten feet [3.05 meters], the vent must be increased to six inches [15.24 centimeters]. A draft hood of approved design must be provided on each boiler.

General Authority: NDCC 23.1-16

Law Implemented: NDCC 23.1-16

Disclaimer: These regulations may not be the most recent version. North Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.