North Dakota Administrative Code
Title 33.1 - Department of Environmental Quality
Article 33.1-14 - NORTH DAKOTA BOILER RULES
Chapter 33.1-14-07 - MINIATURE BOILERS - EXISTING INSTALLATIONS
Section 33.1-14-07-07 - Blowoff piping

Current through Supplement No. 394, October, 2024

1. Each miniature boiler must be provided with a blowoff connection not less than one-half inch [12.7 millimeter] iron pipe size, directly connected with the lowest water space.

2. Blowoff piping may not be galvanized and must be provided with a valve or cock.

General Authority: NDCC 23.1-16

Law Implemented: NDCC 23.1-16

Disclaimer: These regulations may not be the most recent version. North Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.