North Dakota Administrative Code
Title 33.1 - Department of Environmental Quality
Article 33.1-14 - NORTH DAKOTA BOILER RULES
Chapter 33.1-14-07 - MINIATURE BOILERS - EXISTING INSTALLATIONS
Section 33.1-14-07-06 - Feeding and feedwater piping
Current through Supplement No. 394, October, 2024
1. Every miniature boiler must be provided with at least one feed pump or other mechanical feeding device except if the following conditions exist:
2. Each miniature boiler must be fitted with a feedwater connection that may not be less than one-half inch [12.7 millimeter] iron pipe size. The feed piping must be provided with a check valve near the boiler and a valve or check between the check valve and the boiler.
3. Feedwater may be introduced through the blowoff connection if the boiler is operated without extraction of steam (closed system).
4. Feedwater may not be introduced through the water column or gauge glass connections while the boiler is under pressure.
General Authority: NDCC 23.1-16
Law Implemented: NDCC 23.1-16