North Carolina Administrative Code
Title 15A - Environmental Quality
Chapter 18 - ENVIRONMENTAL HEALTH
Subchapter C - WATER SUPPLIES
Section .0900 - DISTRIBUTION SYSTEMS
Section 18C .0904 - PIPE LAYING
Current through Register Vol. 39, No. 6, September 16, 2024
(a) Trenching, pipe laying, and backfilling shall be accomplished in a manner to prevent damage to and misalignment of the pipe. Water mains shall be buried to a depth below the frost line or to a depth sufficient to provide a minimum of 30 inches cover, whichever is greater. In cases where it is impracticable to provide 30 inches of cover taking into consideration feasibility and cost, a deviation may be approved on a case-by-case basis, if supported by data from the design engineer including consideration of pipe material, cover material, land cover, land use, land slope, the depth of the frost line, and the location of other utilities.
(b) To allow for construction and repair, a minimum distance of 12 inches shall be maintained between the outside of the water main and the outside of other utilities.
(c) If an engineer demonstrates it is impractical to maintain the separation distances required by this Rule, taking into consideration feasibility, cost, and the factors set forth in this Paragraph, a deviation may be approved on a case-by-case basis if supported by data and alterative construction criteria submitted by the design engineer. Data and alterative construction criteria submitted by the design engineer to justify the deviation shall describe:
Authority
G.S.
130A-315;
130A-317;
P.L.
93-523;
Eff. January 1,
1977;
Readopted Eff. December 5, 1977;
Pursuant to
G.S.
150B-21.3A, rule is necessary without
substantive public interest Eff. November 23, 2015;
Amended Eff.
July 1, 2019.