Current through Register Vol. 39, No. 24, June 16, 2025
(a) Water Pipe
Materials. Water pipes shall be cast iron, ductile iron, reinforced concrete,
plastic, or other material designed for potable water system service and shall
meet AWWA standards, section C, or be certified as meeting the specifications
of ANSI/NSF Standard 61 Drinking Water System Components - Health Effects,
which is incorporated by reference including any subsequent amendments and
editions. Copies of AWWA standards may be obtained for public inspection as set
forth in Rule .0503 of this Subchapter. Copies of ANSI/NSF Standard 61 may be
obtained for public inspection as set forth in Rule .1537 of this Subchapter.
The pressure rating class of the pipe shall be in excess of the maximum design
pressure within that section of the water distribution system. The quality of
pipe to be used shall be stated in the project specifications.
(b) Cross-Connections. No person shall
construct, maintain, or operate a physical arrangement whereby a public water
system has a cross-connection without the use of proper backflow protection.
(1) No person shall introduce any water into
the distribution system of a public water supply through any means other than
from a source of supply duly approved by the Department or its representatives
or make any physical connection between an approved supply and unapproved
supply unless authorized in an emergency by the Department or its
representative.
(2) Service
Connection Relation to Plumbing Code. No supplier of water shall provide a
service connection to any plumbing system that does not comply with the North
Carolina State Building Code, Volume II, and all applicable local plumbing
codes. Where required, the supplier of water shall install or require to be
installed an appropriate testable backflow prevention assembly prior to making
the service connection. Design of backflow prevention assemblies for service
connections shall not require Department review.
(3) Connections Requiring Departmental
Review. Connections between a public water system and the connection types in
Parts (A) through (D) of this Subparagraph shall require review and approval by
the Department prior to making the connection. Installation of a testable
backflow prevention assembly or air gap shall be required if the connection is
non-potable or unapproved. Engineering plans and specifications shall be
submitted in accordance with Section .0300 of this Subchapter.
(A) Any regulated public water
system;
(B) any community
non-regulated public water system. Before providing a connection, a supplier of
water shall ensure that the construction of the non-regulated public water
system either was approved in accordance with Rule .0301(a) of this Subchapter
or that backflow prevention is provided in accordance with this Rule;
(C) non-potable water treatment processes
within a potable water treatment plant; and
(D) all cross-connections between potable
water supplies and non-potable or unprotected supplies that are not
specifically addressed in this Rule or AWWA M-14 Backflow Prevention and Cross
Connection Control.
(4)
Backflow Prevention Not Addressed by the Plumbing Code. The following
requirements shall apply to backflow prevention not addressed by the plumbing
code.
(A) Testable backflow prevention
assemblies shall meet American Society of Sanitary Engineering (ASSE) standards
and carry an ASSE seal, be on the University of Southern California approval
list for testable backflow prevention assemblies, or be on the North Carolina
State Plumbing Code approval list for approved testable backflow prevention
assemblies.
(B) For each identified
water treatment process-related hazard, the supplier of water shall provide the
appropriate backflow prevention assembly or method to protect the water supply
and water treatment employees, in accordance with AWWA M-14 Backflow Prevention
and Cross Connection Control.
(C)
No person shall fill special use tanks or tankers containing pesticides,
fertilizers, other toxic chemicals, or their residues from a public water
system except at a location equipped with an over-the-rim free discharge of
water or a reduced pressure backflow preventer properly installed on the public
water supply. No supplier of water shall permit the filling of such special use
tanks or tankers except at locations so equipped.
(D) A supplier of water shall not authorize
for construction or other temporary, non-emergency use connections to hydrants
that are not equipped with an approved air gap or an installed reduced pressure
principle backflow prevention assembly.
(E) If storage capacity is used only for
non-potable purposes and there is installed either an elevated or ground tank
or a ground reservoir, the following precautions shall be taken:
(i) If the reservoir or tank is filled from a
supply other than a public water supply and the public water supply is used as
a supplemental supply, the pipeline from the public water supply shall be
installed with an air gap.
(ii) If
the reservoir or tank is filled entirely by water from a public water supply
and:
(I) a covered ground reservoir or covered
elevated tank is used, an approved reduced pressure back-flow preventer or an
approved double check valve assembly shall be used; or
(II) an uncovered ground reservoir or
uncovered elevated tank is used, an air gap shall be required.
(F) Installation. The
following installation requirements shall be met, where applicable.
(i) Backflow prevention assemblies shall be
installed in accordance with manufacturers' recommendations and specifications
and shall not be modified in the field.
(ii) Back-flow prevention assemblies shall be
located and installed in such a manner as to function as designed; be
accessible for testing, maintenance, and inspection; and include all necessary
test cocks and drains for testing. Valves shall be installed in the line at
both ends of the back-flow prevention device to provide for replacement and
maintenance.
(iii) Bypass lines
parallel to a backflow prevention assembly shall have an approved backflow
prevention assembly installed that is equal to that on the main line.
(iv) Reduced pressure principle assemblies
shall be installed above ground or below ground in a vault with positive
gravity drainage to atmosphere employing a drain of sufficient size to handle
the full flow of discharge from a discharging assembly, 12-inch minimum
clearance from vault walls and floor, and in accordance with manufacturer's
recommendations. A reduced pressure principle assembly may be installed as
protection for either a high-health or low-health hazard.
(v) Double check valve assemblies shall be
installed either vertically or horizontal and above ground or below ground in a
vault with positive gravity drainage to the atmosphere. A double check valve
assembly shall be installed as protection for a low-health hazard
only.
(vi) Pressure vacuum breaker
assemblies shall be installed only where there is no possibility of a pressure
higher than the supply pressure caused by a pump, elevated tank, boiler, air or
steam pressure, or any other means which may cause backflow, and in accordance
with manufacturer's recommendations. A pressure vacuum breaker shall be
installed as protection for a high-health or low-health hazard that is subject
to backsiphonage only and with no backpressure.
(5) Interconnection to a public water system
shall be subject to the approval of the supplier of water and shall not be made
until authorized by the supplier of water.
(6) A community or non-transient
non-community public water system with five or more testable backflow
prevention assemblies protecting the distribution system, as required pursuant
to this Rule, shall maintain the following records beginning on January 1,
2020:
(A) records of the location, type,
installation date, size, and the associated degree of hazard of backflow
prevention devices whose failure would create a high-health hazard;
(B) a description of specific ongoing plans,
actions, or schedules to inventory existing backflow prevention devices under
Part (b)(5)(A) of this Rule and to identify and address all uncontrolled
cross-connection hazards;
(C) final
results of all backflow prevention assembly field testing and air gap
inspections; and
(D) review of new
service connections and existing service connections during a change of the
account owner to ensure all required backflow prevention devices are properly
installed and tested.
(E) a
supplier of water which contracts with a third-party to implement any part of
their cross-connection program may allow records required by this Paragraph to
be maintained on the premises of the third-party, as long as the records are
available on demand by the supplier of water.
(F) program records under Part (C) of this
Subparagraph shall be maintained for a minimum of four years. Remaining records
referred to in this Paragraph shall be maintained while still current or in
use.
(7) Each supplier
of water shall notify the Department of any known incident of backflow into the
public water system that creates a risk of contamination as soon as practical
upon discovery of the incident but no later than the end of the next business
day. If requested by the Department, the supplier of water shall submit a
written report of the incident describing the nature and severity of the
backflow, the actions taken by the supplier of water in response to the
incident, and the action plan intended to prevent such incidents in the
future.