Current through Register Vol. 39, No. 6, September 16, 2024
(a) The following are minimum standards of
design and construction of precast reinforced concrete septic tanks:
(1) The minimum requirement for the liquid
depth is 36 inches.
(2) A minimum
of nine inches freeboard is required, the freeboard being the air space between
the top of the liquid and the bottom side of the lid or cap of the
tank.
(3) The length of the septic
tank shall be at least twice as long as the width.
(4) There shall be three inlet openings in
the tank, one on the tank end and one on each sidewall of the inlet end of the
tank. The blockouts for these openings shall leave a concrete thickness of not
less than one inch in the tank wall. The blockouts shall be made for a minimum
of four-inch pipe or a maximum of six-inch pipe. The outlet pipe penetration of
the tank shall be through a resilient, watertight, sealed, non-corrosive and
flexible connective sleeve. The outlet pipe penetration shall be precast to be
compatible with the connective sleeve. No pipe penetration points or openings
shall be permitted below the tank liquid level.
(5) The inlet pipe in the tank shall be a
straight pipe.
(6) The outlet shall
be through an approved effluent filter secured in place in an effluent filter
support case. The effluent filter support case shall serve as a functioning
sanitary tee with the bottom inlet extending down between 25 and 40 percent of
the liquid depth. The approved effluent filter and support case shall be
furnished by the septic tank manufacturer. The invert of the outlet shall be at
least two inches lower in elevation than the invert of the inlet.
(7) Other equivalent methods of supporting
the effluent filter and for making the pipe penetrations shall be approved by
the On-Site Wastewater Section.
(8)
In order to obtain approval of an effluent filter, the filter manufacturer
shall submit to the State the following information with supporting
documentation:
(A) For each septic tank system
that is designed to treat 3,000 gallons per day or less of sewage, a written
certification that the effluent filter is designed, constructed, and performs
in compliance with
G.S.
130A-335.1(a)(1)(2)(3), and
(4);
(B) Sizing as to capacity and wastewater
strength for all models of proposed filters to be approved; and
(C) Specifications for application,
installation, operation, and maintenance.
(9) All tanks shall be manufactured with a
cast-in-place partition so that the tank contains two compartments. The
partition shall be located at a point not less than two-thirds nor more than
three-fourths the length of the tank from the inlet end. The top of the
partition shall terminate two inches below the bottom side of the tank top in
order to leave space for air or gas passage between compartments. The top and
bottom halves of the partition shall be cast in such manner as to leave a water
passage slot four inches high for the full width of the tank. The partition
(both halves) shall be reinforced by the placing of six-inch by six-inch No. 10
gage welded reinforcing wire. The reinforcing wire shall be bent to form an
angle of 90 degrees on the ends in order to form a leg not less than four
inches long. When the wire is placed in the mold the four-inch legs should lay
parallel with the sidewall wire and adjacent to it. It is recognized that there
are other methods of constructing a partition or two-compartment tank. Any
method other than the one described will be considered on an individual basis
for approval by the On-Site Wastewater Section. However, the tank wall
thickness must remain not less than two and one-half inches thick throughout
the tank except for the pipe penetrations.
(10) Adequate access openings must be
provided in the tank top. Access shall be provided for cleaning or rodding out
of the inlet pipe, for cleaning or clearing the air or gas passage space above
the partition, for pumping of each compartment, and for the maintenance of the
effluent filter. This shall be accomplished by properly locating two manholes
or access openings with each having a minimum opening of 15 inches by 15 inches
or 17 inches in diameter as the opening cuts the plane of the bottom side of
the top of the tank or other equidimensional opening with at least 225 square
inches. The manhole covers shall be beveled on all sides in such manner as to
accommodate a uniform load of 150 pounds per square foot without damage to the
cover or the top of the tank. If the top of the tank is to be multislab
construction, the slabs over the inlet of the tank, partition, and outlet of
the tank must not weigh in excess of 150 pounds each. Multislab construction
allows for the elimination of the manholes. Manhole covers, tank lids, access
opening covers, or slabs shall have a handle of steel or other rot-resistant
material equivalent in strength to a No. 3 reinforcing rod (rebar).
(11) The concrete tank and tank lid shall be
reinforced by using a minimum reinforcing of six-inch by six-inch No. 10 gage
welded steel reinforcing wire in the top, bottom ends, and sides of the tank.
The reinforcing wire shall be lapped at least six inches. Concrete cover shall
be required for all reinforcement. Reinforcement shall be placed to maximize
the structural integrity of the tank. The tank, tank lid, riser and riser cover
shall be able to withstand a uniform live loading of 150 pounds per square foot
in addition to all loads to which an underground tanks, riser, or riser cover
is normally subjected, such as the dead weight of the concrete and soil cover,
active soil pressure on tank walls, and the uplifting force of the ground
water. Additional reinforcement shall be required when the loads on a concrete
tank, riser, or riser cover are exceeded by subjecting it to vehicular traffic
or when the top of the tank is placed deeper than three feet below the finished
grade.
(12) The top, bottom, ends,
and sides of the tank must have a minimum thickness of two and one-half
inches.
(13) A minimum 28-day
concrete compressive strength of 3,500 pounds per square inch shall be used in
the construction of the septic tank, concrete access riser and riser cover. The
concrete shall achieve a minimum compressive strength of 3,000 pounds per
square inch prior to removal of the tank from the place of manufacture. It
shall be the responsibility of the manufacturer to certify that this condition
has been met prior to shipment. A septic tank shall be subject to testing to
ascertain the strength of the concrete prior to its being approved for
installation. Recognized devices for testing the strength of concrete include a
properly calibrated Schmidt Rebound Hammer or Windsor Probe Test. Accelerated
curing in the mold by use of propane gas or other fuels is prohibited, except
in accordance with accepted methods and upon prior approval of the
State.
(14) After curing, tanks
manufactured in two sections and as required, concrete risers shall be joined
and sealed at the joint by using a mastic, butyl rubber, or other pliable
sealant that is waterproof, corrosion-resistant, and approved for use in septic
tanks. The sealant shall have a minimum size of one inch nominal diameter or
equivalent. Before sealing, the joint shall be smooth, intact, and free of all
deleterious substances. Tank halves shall be properly aligned to ensure a tight
seal. The sealant shall be provided by the manufacturer.
(15) All tanks produced shall bear an imprint
identifying the manufacturer, the serial number assigned to the manufacturer's
plans and specifications approved by the State, and the liquid or working
capacity of the tanks. This imprint shall be located to the right of the
blockout made for the outlet pipe on the outlet end of the tank. All tanks
shall also be permanently marked with the date of manufacture adjacent to the
tank imprint or on the top of the tank directly above the imprint.
(16) Risers and access covers shall have a
clear opening sized to allow for maintenance and removal of internal devices of
the septic tank and shall not allow accidental entry. The access cover and tank
lid shall be designed, constructed, and maintained to prevent unauthorized
access. Risers shall be sealed watertight where they join the top of the septic
tank, and constructed to prevent water inflow through the lid or
cover.
(b) Pump tanks
shall meet the construction requirements of Paragraph (a) of this Rule with the
following modifications.
(1) Tanks shall be
cast with a single compartment, or, if a partition is provided, the partition
shall be cast to contain a minimum of two four-inch diameter circular openings,
or equivalent, located no more than 12 inches above the tank bottom.
(2) There shall be no requirement as to tank
length, width, or shape, provided the tank satisfies all otherrequirements of
this Section.
(3) The invert of the
inlet openings shall be located within 12 inches of the tank top. No freeboard
shall be required in the pump tank.
(4) After joining, tanks manufactured in two
sections shall be plastered along the joint with hydraulic cement, cement
mortar, or other waterproofing sealant. Other methods of waterproofing tanks
may be used as specifically approved in the plans and specifications for the
tank. Prior to backfilling, the local health department shall make a finding
that a two section tank is watertight if a soil wetness condition is present
within five feet of the elevation of the top of the tank.
(5) Tanks shall be vented and accessible for
routine maintenance. A watertight access manhole with removable lid shall be
provided over the pump with a minimum diameter of 24 inches. The access manhole
shall extend at least to six inches above finished grade and be designed and
maintained to prevent surface water inflow. Larger or multiple manholes shall
be provided when two or more pumps are required. Pumps shall be removable
without requiring entrance into the tank. Manhole lids and electrical controls
shall be secured against unauthorized access. Manhole risers shall be joined to
the tank top and sealed in accordance with Paragraphs (a)(14) and (b)(4) of
this Rule.
(6) All pump tanks shall
bear an imprint identifying the manufacturer, pump tank serial number assigned
by the Division of Environmental Health, and the liquid or working capacity of
the tank. The imprint shall be located to the left of the outlet blockout. All
tanks shall also be permanently marked with the date of manufacture adjacent to
the tank imprint or on the top of the tank directly above the
imprint.
(c) Plans for
prefabricated tanks, risers and riser covers, other than those approved under
Paragraph (a) or (b) of this Rule shall be approved on an individual basis as
determined by the information furnished by the designer which indicates the
tank, riser or riser cover will provide equivalent effectiveness as those
designed in accordance with the provisions of Paragraphs (a) and (b) of this
Rule.
(d) Tanks other than approved
prefabricated tanks shall be constructed consistent with the provisions of this
Rule except as follows:
(1) Cast-in-place
concrete septic and pump tanks shall have a minimum wall thickness of six
inches.
(2) Concrete block or brick
masonry tanks shall have a minimum wall thickness of at least six inches when
the design volume is less than 1,000 gallons and a minimum wall thickness of at
least eight inches when the design volume is 1,000 gallons or more. All joints
between masonry units shall be mortared using masonry cement mortar or
equivalent. The joints shall have a nominal thickness of three-eighths inch.
All concrete block masonry tanks shall have a minimum wall reinforcement of
number three reinforcing bars on 20-inch centers, or equivalent. The maximum
allowable reinforcement spacing in either direction shall be four feet. All
block wall cores shall be filled with concrete with a minimum compressive
strength of 3,000 pounds per square inch. All tanks constructed of block or
brick shall be plastered on the inside with a 1:3 mix (one part cement, three
parts sand) of Portland cement at least three-eighths inch thick or the
equivalent using other approved waterproofing material.
(3) The bottom of the built-in-place tank
shall be poured concrete with a minimum thickness of four inches. All
built-in-place tanks shall be reinforced to satisfy the structural strength
requirements of Paragraph (a)(9) of this Rule. Reinforcement shall be placed in
both directions throughout the entire tank, including top, bottom, walls, and
ends.
(e) Manufacturers
of septic tanks, effluent filters, pump tanks, risers, and riser locators shall
comply with the General Statutes, this Section, and Approval conditions. If the
approved products or materials are found to be in non-compliance, the Operation
Permit shall not be issued or shall be denied. The State shall suspend or
revoke the product approval upon a finding that the information submitted is
falsified, the product has been subsequently altered, or subsequent experience
with the product results in altered conclusions about its design or
performance. Suspension or revocation of the product approval shall not affect
systems previously installed pursuant to the approval.